Plan Review Details - Permit 01120445
Plan Review Stops For Permit 01120445
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-04-04 Cont ID  
Sent By jgomez Date 2002-04-04 Time 11:57 Rev Time 0.33
Received By jgomez Date 2002-04-04 Time 11:56 Sent To  
Notes
2002-04-04 00:00:00TRUSS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-03-25 Cont ID  
Sent By jgomez Date 2002-03-25 Time 17:24 Rev Time 0.33
Received By jgomez Date 2002-03-25 Time 17:24 Sent To  
Notes
2002-03-25 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEER OF RECORD NEED TO REVIEW
 ALL TRUSS DRAWINGS PRIOR TO SUBMITTAL.
 IF POSSIBLE, THEN USE AN STANDARD
 REVIEW STAMP TO SHOW WHO REVIEW IT.
 2-TRUSS ENGINEER FAILURE TO COMPLY WITH
 CHAPTER 471 OF FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS:
 A)PROVIDE ALL HIS INFORMATION: NAME,
 LICENSE NUMBER, ADDRESS, PHONE, ETC.
 B)PROVIDE ORIGINAL SIGNATURE, NOT RUBBER
 STAMP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-02-27 Cont ID  
Sent By jgomez Date 2002-02-27 Time 17:28 Rev Time 0.50
Received By jgomez Date 2002-02-27 Time 17:27 Sent To  
Notes
2002-02-27 00:00:00PRODUCT APPROVAL AND REVISED DRAWING
 WITH CLARIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By jgomez Date 2002-01-30 Time 18:53 Rev Time 1.50
Received By jgomez Date 2002-01-30 Time 18:53 Sent To  
Notes
2002-01-30 00:00:00APPROVED WITH PROVISO:
  
 1-PROVIDE PRODUCT APPROVAL FOR ROUND
 WINDOW WITH LEGIBLE DRAWINGS.
 2-PRODUCT APPROVAL FOR ROUND WINDOWS TO
 SHOW SQUARE FRAME FOR ROUND WINDOW AS
 SPECIFIED BY ENGINEER OR ENGINEER OF
 RECORD TO PROVIDE COMPLETE FRAMING
 DETAILS AND SPECIFICATIONS.
 3-SEE STORM PANELS APPROVED DRAWINGS FOR
 ANCHOR TYPE AND SPACING TO BE USED.
 4-REVISE ROOF FRAMING PLAN AS REQUIRED.
 HOW ARE ROOF TRUSSES ATTACHED TO THE
 WALL?. CONNECTOR SPECIFIED IS TO
 ATTACH STUD TO TOP PLATE.
 -REVISE UPLIFT LOADS SPECIFIED FOR
 SIMPSON LTS16 STRAP. SEE SIMPSON
 CATALOGUE AND REVISE ACCORDING TO
 NAILING AND STRUCTURAL WOOD USED.
 SEE COMMENTS ON SHEET 2 OF 2.
 5-SEE PLANS FOR ADDITIONAL COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-07 Cont ID  
Sent By jgomez Date 2002-01-07 Time 18:55 Rev Time 2.00
Received By jgomez Date 2002-01-08 Time 10:49 Sent To  
Notes
2002-01-07 00:00:00CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY TO
 CONFIRM IF IMPACT FEES ARE DUE OR NOT.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 2-CLARIFY NEW CONCRETE EDGE CONSTRUCT'N:
 A)HOW IS NEW CONCRETE EDGE ATTACHED TO
 EXISTING CONCRETE SLAB?.
 B)HOW CAN YOU HAVE 9" OF COMPACTED FILL
 BETWEEN EXIST'G CONC. SLAB & NEW SLAB?
 -HOW IS IT COMPACTED? HOW IS NEW SLAB
 FORMED? IS IT GOOD IDEA TO HAVE FILL
 IN BETWEEN TWO SLABS? PROVIDE MORE
 INFORMATION AS REQUIRED TO CLARIFY.
 C)CLARIFY INSTALLATION OF NEW BOTTOM AND
 TOP WOOD PLATES. ARE THEY CONTINUOUS
 OR THEY WILL BE STOPPED AT EA. EXIST'G
 STUD? WHAT ABOUT THE EXISTING STUDS?
 ARE THEY GOING TO BE BURIED BY NEW
 CONCRETE EDGE? HOW ARE THEY GOING TO
 BE ISOLATED FROM THE CONCRETE?
 3-SPECIFY FIREBLOCKING AT CONCEALED
 SPACES. SEE SEC. 2305 SBC 1997.
 4-PROVIDE COMPLETE FRAMING DETAILS FOR
 ROUND WINDOW AND EXTERIOR FRENCH DOORS
 SPECIFY ALL FASTENERS. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 5-CLARIFY WHICH GLAZING AREAS ARE GOING
 TO HAVE STORM SHUTTERS OR MISSILE
 IMPACT GLAZING. PRODUCT APPROVALS
 SUBMITTED ARE FOR BOTH.
 -IF STORM SHUTTERS ARE USED, THEN
 SPECIFY ON PRODUCT APPROVAL SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR AND
 SPACING TO BE USED ACCORDING TO THE
 STRUCTURE TO BE ATTACHED TO. ALSO,
 PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE. SEE CITY SAMPLE ATTACHED.
 6-PROVIDE LEGIBLE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM TO BE USED.
 B)ROUND WINDOW. PRODUCT APPROVAL GIVEN
 IS FOR RECTANGULAR WINDOWS, NOT ROUND
 WINDOWS. SEE APPROVED DRAWINGS.
 C)STORM SHUTTERS WITH LEGIBLE DRAWINGS
 IS STORM SHUTTERS WILL BE USED.
 7-OWES $101.00 FOR UPDATED VALUATION.
 PLEASE PAID ATTACHED RECEIPT AND BRING
 BACK PAID RECEIPT.
 8-NEED TO PROVIDE ONE HOUR FIRE RATED
 WALL AT NORTH AND WEST SIDE OF BLDG.
 AS REQUIRED BY TABLE 600 SBC 1997.
 9-PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES AND SPECIFY HURRICANE ANCHORS
 AS REQUIRED.
 10-REVISE ENERGY CALCULATIONS:
 -IF THERE IS A WINDOW UNIT HOW COME
 THERE IS A DUCTWORK WITH R-6 INSULAT'N
 -ITEM #13 APPLIES TO MANUFACTURED HOMES
 ONLY. SEE NOTE WITH ASTERISK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-06 Cont ID  
Sent By btrobaug Date 2002-05-06 Time 12:58 Rev Time 0.00
Received By btrobaug Date 2002-05-06 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-23 Cont ID  
Sent By dpalmer Date 2002-01-23 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2002-01-23 Time 14:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-19 Cont ID  
Sent By dpalmer Date 2001-12-19 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2001-12-19 Time 16:41 Sent To  
Notes
2001-12-19 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE CLARIFY A MAIN DISCONNECT
 AND A MCB PANEL SHOWN AT CABANA?
  
 2)NOTE: PLEASE CLARIFY GROUNDING FROM
 MAIN PANEL TO DETACHED STRUCTURE PER
 250-32.
  
 3)NOTE: PLEASE NOTE 50KW SHOWN FOR
 CABANA ON MAIN PANEL SCHEDULE. MUST BE
 A MISPRINT. PLEASE CORRECT
  
 4)NOTE: PLEASE CLARIFY #4 INTO A 2P50
 BRKR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-27 Cont ID  
Sent By ndenmark Date 2001-12-27 Time 10:36 Rev Time 0.25
Received By ndenmark Date 2001-12-27 Time 10:36 Sent To  
Notes
2001-12-27 00:00:00SELF CONTAINED WALL UNIT (WINDOW) AC
 DOES NOT REQUIRE PERMIT.
 ADDITIONAL MECHANICAL WORK INCLUDING
 DRYER VENT WILL REQUIRE INSPECTION TO
 ASSURE CODE COMPLIANCE

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2002-01-23 Time 14:27 Rev Time 0.33
Received By jleech Date 2001-12-24 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-10 Cont ID  
Sent By sgraham Date 2001-12-10 Time 14:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***