| 2002-01-07 00:00:00 | CHECKLIST: |
| | 1-BRING DRAWINGS TO PALM BEACH COUNTY TO |
| | CONFIRM IF IMPACT FEES ARE DUE OR NOT. |
| | BRING BACK STAMPED DRAWINGS AND PAID |
| | RECEIPT. |
| | 2-CLARIFY NEW CONCRETE EDGE CONSTRUCT'N: |
| | A)HOW IS NEW CONCRETE EDGE ATTACHED TO |
| | EXISTING CONCRETE SLAB?. |
| | B)HOW CAN YOU HAVE 9" OF COMPACTED FILL |
| | BETWEEN EXIST'G CONC. SLAB & NEW SLAB? |
| | -HOW IS IT COMPACTED? HOW IS NEW SLAB |
| | FORMED? IS IT GOOD IDEA TO HAVE FILL |
| | IN BETWEEN TWO SLABS? PROVIDE MORE |
| | INFORMATION AS REQUIRED TO CLARIFY. |
| | C)CLARIFY INSTALLATION OF NEW BOTTOM AND |
| | TOP WOOD PLATES. ARE THEY CONTINUOUS |
| | OR THEY WILL BE STOPPED AT EA. EXIST'G |
| | STUD? WHAT ABOUT THE EXISTING STUDS? |
| | ARE THEY GOING TO BE BURIED BY NEW |
| | CONCRETE EDGE? HOW ARE THEY GOING TO |
| | BE ISOLATED FROM THE CONCRETE? |
| | 3-SPECIFY FIREBLOCKING AT CONCEALED |
| | SPACES. SEE SEC. 2305 SBC 1997. |
| | 4-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | ROUND WINDOW AND EXTERIOR FRENCH DOORS |
| | SPECIFY ALL FASTENERS. SECTION 104.2.2 |
| | CITY AMENDMENTS TO SBC 1997. |
| | 5-CLARIFY WHICH GLAZING AREAS ARE GOING |
| | TO HAVE STORM SHUTTERS OR MISSILE |
| | IMPACT GLAZING. PRODUCT APPROVALS |
| | SUBMITTED ARE FOR BOTH. |
| | -IF STORM SHUTTERS ARE USED, THEN |
| | SPECIFY ON PRODUCT APPROVAL SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR AND |
| | SPACING TO BE USED ACCORDING TO THE |
| | STRUCTURE TO BE ATTACHED TO. ALSO, |
| | PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE ATTACHED. |
| | 6-PROVIDE LEGIBLE PRODUCT APPROVAL FOR: |
| | A)FLAT ROOF SYSTEM TO BE USED. |
| | B)ROUND WINDOW. PRODUCT APPROVAL GIVEN |
| | IS FOR RECTANGULAR WINDOWS, NOT ROUND |
| | WINDOWS. SEE APPROVED DRAWINGS. |
| | C)STORM SHUTTERS WITH LEGIBLE DRAWINGS |
| | IS STORM SHUTTERS WILL BE USED. |
| | 7-OWES $101.00 FOR UPDATED VALUATION. |
| | PLEASE PAID ATTACHED RECEIPT AND BRING |
| | BACK PAID RECEIPT. |
| | 8-NEED TO PROVIDE ONE HOUR FIRE RATED |
| | WALL AT NORTH AND WEST SIDE OF BLDG. |
| | AS REQUIRED BY TABLE 600 SBC 1997. |
| | 9-PROVIDE UPLIFT CALCULATIONS FOR ROOF |
| | TRUSSES AND SPECIFY HURRICANE ANCHORS |
| | AS REQUIRED. |
| | 10-REVISE ENERGY CALCULATIONS: |
| | -IF THERE IS A WINDOW UNIT HOW COME |
| | THERE IS A DUCTWORK WITH R-6 INSULAT'N |
| | -ITEM #13 APPLIES TO MANUFACTURED HOMES |
| | ONLY. SEE NOTE WITH ASTERISK. |