Plan Review Details - Permit 01120364
| Plan Review Stops For Permit 01120364 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-22 |
Time |
14:02 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-31 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-31 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2001-12-31 00:00:00 | ***************** UNSAT************** | | | | | | 1)NOTE: PLEASE NOTE ELECTRICAL PANEL | | | "A" SHOWS MCB AND PANEL SCHEDULE SHOW | | | MLO?, PLEASE NOTE PANEL"A" IS SHOWN | | | COMING FROM METER AND NOT THE 200A RT | | | PANEL, PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE CLARIFY MISSING DOOR | | | UPSTAIRS BEDROOM? | | | | | | 3)NOTE: PLEASE NOTE A EXTRA SD NEEDS TO | | | BE INSTALLED IN HALLWAY UPSTAIRS OR | | | MOVE ONE SHOWN AROUND CORNER. NFPA-72 | | | 2-2.1.1.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-12-27 |
Time |
17:38 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2001-12-27 |
Time |
17:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-12-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-21 |
Time |
21:44 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-12-21 |
Time |
21:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-02-06 |
Time |
12:23 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2002-02-06 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | TRUSS DRAWINGS REVIEW: | | | | | | 1-ENGINEER OF RECORD TO CLEARLY PROVIDE | | | DETAILS AND CONNECTOR SPECIFICATIONS | | | THAT RESIST THE UPLIFT LOADS | | | CALCULATED ON THE ENGINEERED TRUSSES | | | G3, G2 AND G1. | | | SEE ENGINEERED TRUSSES FOR CALCULATED | | | LOADS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-01-14 |
Time |
18:25 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2002-01-14 |
Time |
18:25 |
Sent To |
|
|
| Notes |
| 2002-01-14 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE A8. NEED THE ELEVATION | | | CERTIFICATE. | | | 2-RESUBMIT STORM PANELS PRODUCT APPROVAL | | | DRAWINGS SUBMITTED ARE VALID FOR ONE | | | PERMIT ONLY. SEE NOTE ON DRAWINGS. | | | 3-PROVIDE UPDATED PRODUCT APPROVAL FOR | | | ENTRY DOOR. | | | 4-REVISE SPECIFICATIONS FOR CEILING | | | INSTALLATION AT ENTRY AND REAR PORCH. | | | SEE ASTM C926 AND ASTM C1063. | | | 5-SUBMIT CURRENT PRODUCT APPROVAL FOR | | | GARAGE DOOR. PRODUCT APPROVAL | | | SUBMITTED WAS DELETED BY SBCCI. | | | 6-SLIDING GLASS DOORS OPTION WILL NOT | | | BE ALLOWED BECAUSE IT WILL EXCEED THE | | | MAXIMUM PERCENTAGE OF OPENINGS | | | ALLOWED BY TABLE 600 SBC 1997. | | | 7-CLARIFY SPECIFICATIONS FOR ROOF | | | SHEATHING FASTENING. SEE NOTE ON | | | STRUCTURAL NOTES AND NOTE ON WALL | | | SECTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
nleiva |
Date |
2001-12-11 |
Time |
07:43 |
Rev Time |
0.25 |
| Received By |
nleiva |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|