Plan Review Details - Permit 01120360
Plan Review Stops For Permit 01120360
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 08:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By hmoser Date 2002-05-15 Time 19:47 Rev Time 0.50
Received By hmoser Date 2002-05-15 Time 19:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-12-20 Cont ID  
Sent By hmoser Date 2001-12-20 Time 18:37 Rev Time 0.33
Received By hmoser Date 2001-12-20 Time 18:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-21 Cont ID  
Sent By kstevens Date 2001-12-21 Time 20:39 Rev Time 0.50
Received By kstevens Date 2001-12-21 Time 20:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-16 Cont ID  
Sent By rmcdouga Date 2002-05-16 Time 15:26 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-16 00:00:00REVISION TO ENCLOSE LANAI OK NO IMPACT
 FEES OWED 5-16-02 RM

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-01-11 Cont ID  
Sent By rmcdouga Date 2002-01-11 Time 16:25 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-11 00:00:00************BUILDING PROVISO************
  
 1) STRUCTURE IS LOCATED IN AN A8 FLOOD
 ZONE. AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 2) RESUBMIT STORM PANEL INFORMATION WITH
 MASTERED DRAWINGS. THE ONES SUBMITTED
 ARE COPIES OF ENGINEERED DRAWINGS THAT
 WERE VALID ONLY FOR ONE TIME PERMIT, AS
 STAMPED ON THE DRAWINGS.
  
 3) REVISE TYPICAL EXTERIOR CEILING
 DETAIL TO COMPLY WITH ASTM C-1063, WHICH
 REQUIRES 1-3/4" PENETRATION INTO
 HORIZONTAL WOOD FRAMING MEMBERS BY
 FASTENERS. (2" STAPLES)

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-11 Cont ID  
Sent By nleiva Date 2001-12-11 Time 07:40 Rev Time 0.25
Received By nleiva Date   Time   Sent To  
Notes
***NONE***