| Plan Review Stops For Permit 01120298 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-31 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-17 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-17 00:00:00 | IT APPEARS THAT THIS BUILDING IS LOCATED | | | DIRECTLY TO THE 14' WIDE ALLEY.THUS | | | THE ASSUMED PROPERTY LINE IS AT 7' AND | | | SBC 705.1.1.2 REQUIRES OPENING | | | PROTECTIVES FOR THE EXISTING AND THE | | | PROPOSED OPENINGS ON THE SOUTH SIDE. | | | | | | | | | SHOW A BRIEF LIFE SAFETY PLAN SKETCH FOR | | | THE SPACE TO THE EAST CONTINUING TO | | | MEET EGRESS REQUIREMENTS.SEE SBC | | | 104.2. | | | | | | WHAT IS THE OCCUPANCY USE OF THIS | | | SPACE? SEE SBC 104.1.5. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-30 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-30 |
Time |
18:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-07 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-07 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2001-12-07 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW LAYOUT AROUND NEW | | | SPRAY BOOTH TO MEET 516. | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS BETWEEN MAIN PANEL | | | AND PANEL "B". | | | | | | 3)NOTE: PLEASE NOTE MISSING PANEL "B" | | | PANEL SCHEDULE, PANEL "C"??? | | | | | | 4)NOTE: PLEASE CLARFIY 3/0`S FROM 100A | | | OCP SHOWN ON PANEL "A" FEEDING "B". | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | 6)NOTE: PLEASE CLARIFY IF ONLY HALF OF | | | THE EXSITING SERVICE WILL BE ELIMINATED? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-31 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-31 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-11 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-11 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2001-12-11 00:00:00 | 1) WHAT WILL THE SPRAY BOOTH BE USED | | | FOR. | | | 2) THE SPRAY BOOTH REQUIRES A FIRE | | | SUPPRESSION SYSTEM. SEPARATE PLANS AND | | | PERMITS REQUIRED FOR SPRAY BOOTH. | | | 3) THE SPRAY BOOTH REQUIRES THREE FEET | | | AROUND IT FOR CLEANING PURPOSES. | | | 4) THE SPRAY BOOTH REQUIRES GROUNDING. | | | 5) IF THE SPRAY BOOTH IS USED TO SPRAY | | | FLAMMABLE OR COMBUSTIBLE LIQUIDS, WHERE | | | WILL THESE ITEMS BE STORED WHEN NOT | | | BEING SPRAYED. | | | 6) PLEASE DEMONSTRATE COMPLIANCE WITH | | | THE STANDARD MECHANICAL CODE, SECTION | | | 506.1 WHICH REQUIRES THE EXHAUST DUCT | | | TO BE AT LEAST 10 FEET FROM THE | | | BUILDING, ADJACENT BUILDINGS, | | | PROPERTIES, PARKING AREAS, ETC. | | | 7) NO ELEVATION DRWAINGS OF THE | | | BUILDING PROVIDED. | | | 8) PLEASE INDICATE HOW MAKE-UP AIR IS | | | BEING PROVIDED FOR THE SPRAY BOOTH. | | | 9) PLEASE INDICATE LOCATIONS OF FIRE | | | EXTINGUISHERS. | | | 10) PLEASE INDICATE LOCATIONS OF | | | WRNING SIGNS ASSOCIATED WITH SPRAY | | | BOOTH. | | | 11) ELECTRICAL REQUIREMENTS TO COMPLY | | | WITH NFPA 33 REQUIREMENTS. | | | 12) IS THE WALL ADJACENT TO THE SPRAY | | | BOOTH A DEMISING WALL OR AN EXTERIOR | | | WALL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-08 |
Time |
11:06 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | | | | SEPARATE PERMIT FOR SPRAY BOOTH - | | | | | | AS PER CONVERSATION WITH RENE TERCILLA, | | | EXHAUST DUCT SHALL COMPLY WITH 506.1. | | | | | | RENE TO GET MANUFACTURER RECOMMENDATION | | | FOR EX FAN FOR DISTANCE OF THE DUCT RUN | | | AND FITTINGS. | | | | | | SUBMIT PLANS AND MANUFACTURER SUBMITTAL | | | DATA WITH PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-31 |
Time |
07:09 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-01-31 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2002-01-31 00:00:00 | *******************DENIED*************** | | | | | | | | | COMMENT #2 FROM REVIEW DATED 12-18-0 WAS | | | NOT ADDRESSED. | | | | | | PROVIDE DETAIL OF EXHAUST TERMINATION. | | | AS PER NFPA 33 AIR EXHAUSTED SHALL BE | | | CONDUCTED BY DUCTS DIRECTLY TO THE | | | OUTSIDE OF THE BUILDING BY THE MOST | | | DIRECT ROUTE TO THE POINT OF DISCHARGE. | | | (SHALL NOT PENETRATE FIRE WALL)THE | | | EXHAUST DUCT DISCHARGE SHALL BE AT | | | LEAST 6 FT FROM ANY EXTERIOR WALL OR | | | ROOF.DUCT SHALL NOT DISCHARGE IN THE | | | DIRECTION OF ANY COMBUSTIBLE | | | CONSTRUCTION THAT IS WITHIN 25 FT OF | | | THE EXHAUST DISCHARGE POINT NOR SHALL | | | IT DISCHARGE IN THE DIRECTIONS OF ANY | | | UNPROTECTED IN NONCOMBUSTIBLE OR | | | LIMITED COMBUSTIBLE CONSTRUCTIONS THAT | | | IS WITHIN 25 FT OF THE EXHAUST | | | DISCHARGE POINT. | | | | | | INDICATE ON PLAN HOW EXHAUST DUCT | | | TERMINATION WILL BE SECURED TO THE ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-18 |
Time |
08:30 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-12-18 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2001-12-18 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE ADDITIONAL MANUFACTURER | | | INSTALLATION INSTRUCTIONS FOR THE | | | MODULAR OFFICE.INDICATE WHAT TYPE OF | | | AC SYSTEM IS BEING INSTALLED WITH THIS | | | MODULAR OFFICE SPACE. | | | | | | ADDITIONAL PLANS AND PERMIT REQUIRED FOR | | | THE SPRAY BOOTH.PROVIDE THE FOLLOWING | | | INFORMATION FOR REVIEW WITH PERMIT | | | APPLICATION. | | | | | | 1.INDICATE WHAT TYPE OF APPLICATION IS | | | BEING DONE IN THE SPRAY BOOTH. | | | | | | 2.INDICATE LOCATION/TERMINATION OF | | | EXHAUST TO SPARY BOOTH. PLEASE NOTE | | | AS PER 1997 SMC 506.1, EXHAUST OUT- | | | LETS FOR DUCTS CONVEYING NOXIOUS | | | GASES, FLAMMABLE VAPORS & CORROSIVE | | | VAPORS, SHALL TERMINATE OUTSIDE THE | | | BUILDING & SHALL BE LOCATED 10 FT | | | FROM ANY ADJACENT BUILDING, PARKING | | | AREA, PROPERTY LINE, WINDOW, DOOR, | | | OR AIR INTAKE AND 10 FT ABOVE THE | | | ADJOINING GRADE LEVEL.SHOULD | | | EXHAUST TERMINATE ABOVE THE ROOF IT | | | SHALL BE A MINIMUM OF 40" ABOVE THE | | | ROOF SURFACE. | | | | | | PLEASE SEE FIRE DEPT COMMENTS FOR | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-05 00:00:00 | PLUMBING REVISIONS REQUIESTED BY PLUMB. | | | INSPECTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
11:26 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-02 |
Time |
10:34 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-02 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2002-02-02 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT A-1 SHOW CLEAR FLOOR SPACE AND | | | TURNING RADIUS FOR TOILET ROOM. | | | 2) SHT A-1 MINIMUM FIXTURES REQUIREMENTS | | | SPC TABLE 407 REQUIRE A DRINKING FOUNT- | | | AIN. | | | 3) SHT A-1 SANT RISER DIAGRAM, MOP SINK | | | NOT SHOWN. | | | 4) SHT A-1 WATER RISER DIAGRAM, PLEASE | | | LOCATE WATER HAMMER ARRESTORS NEAR FIX- | | | TURES IN "EFFECTIVE RANGE" NOT AT TOP OF | | | DROP AS SHOWN PER PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | 5) BACKFLOW REQUIRED ON WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-31 |
Time |
17:13 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-01-03 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2002-01-03 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PLEASE SUBMIT CALCULATIONS FOR MIN- | | | IMUM FACILITIES PER SPC TABLE 407. GIVE | | | INFORMATION ON NUMBER OF PERSONS WORKING | | | PER SHIFT ECT. SQUARE FOOTAGE OF SPACE | | | REQUIRED. | | | | | | 2) SHT A1, WATER RISER DIAGRAM, AIR | | | CHAMBERS SHALL HAVE ACCESS PANELS AND | | | SHALL BE RECHARGEABLE PER SPC SEC | | | 607.8.3. APPROVED WATER HAMMER ARRESTORS | | | DO NOT REQUIRE ACCESS AND ARE NOT RECHAR | | | GEABLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT 8377 |
|
|