Plan Review Details - Permit 01120298
Plan Review Stops For Permit 01120298
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By hpiskura Date 2002-01-31 Time 17:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-17 Cont ID  
Sent By hpiskura Date 2001-12-17 Time 15:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-12-17 00:00:00IT APPEARS THAT THIS BUILDING IS LOCATED
 DIRECTLY TO THE 14' WIDE ALLEY.THUS
 THE ASSUMED PROPERTY LINE IS AT 7' AND
 SBC 705.1.1.2 REQUIRES OPENING
 PROTECTIVES FOR THE EXISTING AND THE
 PROPOSED OPENINGS ON THE SOUTH SIDE.
  
  
 SHOW A BRIEF LIFE SAFETY PLAN SKETCH FOR
 THE SPACE TO THE EAST CONTINUING TO
 MEET EGRESS REQUIREMENTS.SEE SBC
 104.2.
  
 WHAT IS THE OCCUPANCY USE OF THIS
 SPACE? SEE SBC 104.1.5.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 18:44 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 18:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-07 Cont ID  
Sent By dpalmer Date 2001-12-07 Time 06:54 Rev Time 0.00
Received By dpalmer Date 2001-12-07 Time 06:54 Sent To  
Notes
2001-12-07 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SHOW LAYOUT AROUND NEW
 SPRAY BOOTH TO MEET 516.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN MAIN PANEL
 AND PANEL "B".
  
 3)NOTE: PLEASE NOTE MISSING PANEL "B"
 PANEL SCHEDULE, PANEL "C"???
  
 4)NOTE: PLEASE CLARFIY 3/0`S FROM 100A
 OCP SHOWN ON PANEL "A" FEEDING "B".
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 6)NOTE: PLEASE CLARIFY IF ONLY HALF OF
 THE EXSITING SERVICE WILL BE ELIMINATED?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By mcarsill Date 2002-01-31 Time 14:50 Rev Time 0.00
Received By mcarsill Date 2002-01-31 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By mcarsill Date 2001-12-11 Time 07:44 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 07:44 Sent To  
Notes
2001-12-11 00:00:001) WHAT WILL THE SPRAY BOOTH BE USED
 FOR.
 2) THE SPRAY BOOTH REQUIRES A FIRE
 SUPPRESSION SYSTEM. SEPARATE PLANS AND
 PERMITS REQUIRED FOR SPRAY BOOTH.
 3) THE SPRAY BOOTH REQUIRES THREE FEET
 AROUND IT FOR CLEANING PURPOSES.
 4) THE SPRAY BOOTH REQUIRES GROUNDING.
 5) IF THE SPRAY BOOTH IS USED TO SPRAY
 FLAMMABLE OR COMBUSTIBLE LIQUIDS, WHERE
 WILL THESE ITEMS BE STORED WHEN NOT
 BEING SPRAYED.
 6) PLEASE DEMONSTRATE COMPLIANCE WITH
 THE STANDARD MECHANICAL CODE, SECTION
 506.1 WHICH REQUIRES THE EXHAUST DUCT
 TO BE AT LEAST 10 FEET FROM THE
 BUILDING, ADJACENT BUILDINGS,
 PROPERTIES, PARKING AREAS, ETC.
 7) NO ELEVATION DRWAINGS OF THE
 BUILDING PROVIDED.
 8) PLEASE INDICATE HOW MAKE-UP AIR IS
 BEING PROVIDED FOR THE SPRAY BOOTH.
 9) PLEASE INDICATE LOCATIONS OF FIRE
 EXTINGUISHERS.
 10) PLEASE INDICATE LOCATIONS OF
 WRNING SIGNS ASSOCIATED WITH SPRAY
 BOOTH.
 11) ELECTRICAL REQUIREMENTS TO COMPLY
 WITH NFPA 33 REQUIREMENTS.
 12) IS THE WALL ADJACENT TO THE SPRAY
 BOOTH A DEMISING WALL OR AN EXTERIOR
 WALL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-02-08 Cont ID  
Sent By pkrauss Date 2002-02-08 Time 11:06 Rev Time 0.35
Received By pkrauss Date 2002-02-08 Time 11:06 Sent To  
Notes
2002-02-08 00:00:00 
 SEPARATE PERMIT FOR SPRAY BOOTH -
  
 AS PER CONVERSATION WITH RENE TERCILLA,
 EXHAUST DUCT SHALL COMPLY WITH 506.1.
  
 RENE TO GET MANUFACTURER RECOMMENDATION
 FOR EX FAN FOR DISTANCE OF THE DUCT RUN
 AND FITTINGS.
  
 SUBMIT PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-01-31 Cont ID  
Sent By pkrauss Date 2002-01-31 Time 07:09 Rev Time 0.35
Received By pkrauss Date 2002-01-31 Time 07:07 Sent To  
Notes
2002-01-31 00:00:00*******************DENIED***************
  
  
 COMMENT #2 FROM REVIEW DATED 12-18-0 WAS
 NOT ADDRESSED.
  
 PROVIDE DETAIL OF EXHAUST TERMINATION.
 AS PER NFPA 33 AIR EXHAUSTED SHALL BE
 CONDUCTED BY DUCTS DIRECTLY TO THE
 OUTSIDE OF THE BUILDING BY THE MOST
 DIRECT ROUTE TO THE POINT OF DISCHARGE.
 (SHALL NOT PENETRATE FIRE WALL)THE
 EXHAUST DUCT DISCHARGE SHALL BE AT
 LEAST 6 FT FROM ANY EXTERIOR WALL OR
 ROOF.DUCT SHALL NOT DISCHARGE IN THE
 DIRECTION OF ANY COMBUSTIBLE
 CONSTRUCTION THAT IS WITHIN 25 FT OF
 THE EXHAUST DISCHARGE POINT NOR SHALL
 IT DISCHARGE IN THE DIRECTIONS OF ANY
 UNPROTECTED IN NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE CONSTRUCTIONS THAT
 IS WITHIN 25 FT OF THE EXHAUST
 DISCHARGE POINT.
  
 INDICATE ON PLAN HOW EXHAUST DUCT
 TERMINATION WILL BE SECURED TO THE ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-18 Cont ID  
Sent By pkrauss Date 2001-12-18 Time 08:30 Rev Time 0.45
Received By pkrauss Date 2001-12-18 Time 08:02 Sent To  
Notes
2001-12-18 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE ADDITIONAL MANUFACTURER
 INSTALLATION INSTRUCTIONS FOR THE
 MODULAR OFFICE.INDICATE WHAT TYPE OF
 AC SYSTEM IS BEING INSTALLED WITH THIS
 MODULAR OFFICE SPACE.
  
 ADDITIONAL PLANS AND PERMIT REQUIRED FOR
 THE SPRAY BOOTH.PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW WITH PERMIT
 APPLICATION.
  
 1.INDICATE WHAT TYPE OF APPLICATION IS
 BEING DONE IN THE SPRAY BOOTH.
  
 2.INDICATE LOCATION/TERMINATION OF
 EXHAUST TO SPARY BOOTH. PLEASE NOTE
 AS PER 1997 SMC 506.1, EXHAUST OUT-
 LETS FOR DUCTS CONVEYING NOXIOUS
 GASES, FLAMMABLE VAPORS & CORROSIVE
 VAPORS, SHALL TERMINATE OUTSIDE THE
 BUILDING & SHALL BE LOCATED 10 FT
 FROM ANY ADJACENT BUILDING, PARKING
 AREA, PROPERTY LINE, WINDOW, DOOR,
 OR AIR INTAKE AND 10 FT ABOVE THE
 ADJOINING GRADE LEVEL.SHOULD
 EXHAUST TERMINATE ABOVE THE ROOF IT
 SHALL BE A MINIMUM OF 40" ABOVE THE
 ROOF SURFACE.
  
 PLEASE SEE FIRE DEPT COMMENTS FOR
 ADDITIONAL INFORMATION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT 8388.

Review Stop P PLUMBING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2002-04-05 00:00:00PLUMBING REVISIONS REQUIESTED BY PLUMB.
 INSPECTOR.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 11:26 Rev Time 1.00
Received By kstevens Date 2002-02-08 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-02 Cont ID  
Sent By kstevens Date 2002-02-02 Time 10:34 Rev Time 0.50
Received By kstevens Date 2002-02-02 Time 10:34 Sent To  
Notes
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-1 SHOW CLEAR FLOOR SPACE AND
 TURNING RADIUS FOR TOILET ROOM.
 2) SHT A-1 MINIMUM FIXTURES REQUIREMENTS
 SPC TABLE 407 REQUIRE A DRINKING FOUNT-
 AIN.
 3) SHT A-1 SANT RISER DIAGRAM, MOP SINK
 NOT SHOWN.
 4) SHT A-1 WATER RISER DIAGRAM, PLEASE
 LOCATE WATER HAMMER ARRESTORS NEAR FIX-
 TURES IN "EFFECTIVE RANGE" NOT AT TOP OF
 DROP AS SHOWN PER PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-03 Cont ID  
Sent By hpiskura Date 2002-01-31 Time 17:13 Rev Time 1.25
Received By kstevens Date 2002-01-03 Time 09:30 Sent To  
Notes
2002-01-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE SUBMIT CALCULATIONS FOR MIN-
 IMUM FACILITIES PER SPC TABLE 407. GIVE
 INFORMATION ON NUMBER OF PERSONS WORKING
 PER SHIFT ECT. SQUARE FOOTAGE OF SPACE
 REQUIRED.
  
 2) SHT A1, WATER RISER DIAGRAM, AIR
 CHAMBERS SHALL HAVE ACCESS PANELS AND
 SHALL BE RECHARGEABLE PER SPC SEC
 607.8.3. APPROVED WATER HAMMER ARRESTORS
 DO NOT REQUIRE ACCESS AND ARE NOT RECHAR
 GEABLE.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT 8377