| Plan Review Stops For Permit 01120278 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-06 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-06 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2001-12-06 00:00:00 | 1) IF A FIRE SPRINKLER SYSTEM EXISTS, | | | THEN FLOW AND TAMPER SWITCHES ARE TO | | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | 2) DUCT SMOKE DETECTORS ARE REQUIRED | | | IN HVAC SYSTEMS OVER 2000 CFM. NONE | | | ARE SHOWN. | | | 3) NO DEVICES SHOWN FOR FIRST FLOOR. | | | ARE ANY EXISTING DEVICES PRESENT. | | | APPROVED PROVISO: | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|