Plan Review Details - Permit 01120265
Plan Review Stops For Permit 01120265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By jwitmer Date 2002-03-07 Time 10:18 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-07 00:00:00PROVISO: SLEEPING ROOMS 2ND FLOOR SHALL
 HAVE AN EMERGENCY EGRESS WINDOW WITH A
 MINIMUM HORIZONTAL LENGTH OF 20" AND
 A MINIMUM OF 5.7 SQ. FT CLEAR.
  
 HANDRAIL VS GUARD RAIL, EXTERIOR STEPS
 WITH 4 OR MORE RISERS SHALL REQUIRE
 A HAND RAIL 1007.5.1. GUARDRAILS SHALL
 NOT BE REQUIRED UNLESS PORCHES, ARE MORE
 THAN 30" ABOVE GRADE 1015.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-01 Cont ID  
Sent By dpalmer Date 2002-03-05 Time 17:20 Rev Time 5.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-01 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01120265
 202 WESTMINISTER RD
 CONT: LEVESQUE CONST
 TEL: 758-1939
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
  
 1)- DISCREPANCY BETWEEN THE SURVEY WEST
 SETBACK OF 5'-8" ON SURVEY VS 7'-0" ON
 THE PLOT PLAN.
  
 2)- SBC 1606.2.6.2/ PRODUCT APPROVALS:
 A) DOOR # 19 MISSING PRODUCT APPROVAL
 FOR INSWING FRONT DOOR.
 B) DOOR #3 & 4 OVERHEAD GARAGE DOORS,
 PLANS INDICATE THE DOORS TO BE 9'-0"X
 7'-0" THE PRODUCT APPROVAL IS FOR A
 9'-0"X 8'-0" ONLY.
 C) FRENCH DOORS INDICATE A TRANSOM
 ABOVE, THE PRODUCT APPROVALS ARE FOR
 "LIMITATIONS" TESTED FOR A SINGLE
 UNIT. PRODUCT TESTING REPORT FOR
 MULLIONS SHALL BE REQUIRED.
 THE SAME SITUATION EXIST WITH THE
 USE OF MULIPLE WINDOWS, SEE LIMIT-
 ATIONS.
 D) FRENCH DOORS WITH A SIDELITE SHALL
 ALSO BE TESTED IN THIS SAME MANNER.
 SEE LIMITATIONS.
 E) FIXED GLASS PRODUCT LIMITATION
 ONE UNIT SHALL REQUIRE MULLION REPORT
  
 3) SBC 1005.4.4 EMERGENCY ESCAPE & RES-
 CUE OPENINGS:MINIMUM SIZE, CLEAR OPENING
 SEE ATTACHMENT, ALSO 5.7 SQ. FT REQUIRED
 OPEN AREA FOR SLEEPING ROOMS ABOVE THE
 FIRST FLOOR.
  
 4)- FACTORY BUILT FIREPLACES & CHIMNEYS:
 SBC 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH &
 MEET THE REQUIREMENTS OF UL 127 & SEC.
 2806. SBC 2810 FRESH AIR INTAKE.
  
 5)- SHEET 8 FIREPLACE CHIMNEY FRAMING,
 INDICATE THE SYSTEM TO RESIST MOMENT OF
 OVERTURNING, FRAMING DETAILS, GIRDER
 TRUSS AND ATTACHMENT TO RESIST 110 MPH
 WINDS!
  
 6)- DOOR #20 INTERIOR DOOR INDICATES
 SAME AS 14, A POCKET DOOR, WHILE PLANS
 INDICATE SWING?
  
 7)- SHEET 3 SBC 2309.6 ATTIC ACCESS:
 22'X36", HOUSE & 2ND FLOOR GARAGE.
  
 8)- SHEET 9-4 MISSING POST TO BUILT UP
 BEAM CONNECTION.
  
 9)- TRUSS & GIRDER LOADS,VERTICAL,
 HORIZONTAL & GRAVITY, HURRICANE ANCHOR-
 ING SCHEDULE WITH MANUFAC. LOADS, UPLIFT
 VALUES, PLY, 12 OR 3 TRUSS
  
 10)- GARAGE 2ND STORY OVER 500 SQ FT
 SBC 2305.2.2 DRAFT STOPPING REQUIRED
  
 11)- SHEET 9, SHEET 10 ANCHOR LEDGER
 BOLTS, LENGTH?
  
 12)- SHEET 4&5 GUARDRAILS SEE SECTION
 1015.3 OPENINGS, A 4" SPHERE CAN NOT
 PASS THROUGH PICKETS, BOTTOM RAIL
 A 2" SPHERE CAN NOT PASS BETWEEN THE
 FLOOR AND BOTTOM RAIL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2002-03-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-05 Cont ID  
Sent By dpalmer Date 2002-03-05 Time 17:07 Rev Time 0.00
Received By dpalmer Date 2002-03-05 Time 17:04 Sent To B
Notes
2002-03-05 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOTE #1 FROM
 FIRST REVIEW WAS NOT ADDRESSED.
 AIC RATING IS REQ`D AT THE TIME THE
 PLANS ARE SUBMITTED FOR REVIEW.110-/
 215-5
  
 2)NOTE: PLEASE NOTE THAT ALL OTHER
 CHANGES THAT WERE MADE TO PLANS NEED TO
 BE SIGNED AND DATED BY THE ARCH OF
 RECORD OR HAVE PLANS COPIED AND RE-
 SIGNED, DATED AND SEALED BY THE ARCH OF
 RECORD. 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE MAKE THE ABOVE CHANGES.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-24 Cont ID  
Sent By dpalmer Date 2002-01-24 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2002-01-24 Time 13:20 Sent To B
Notes
2002-01-24 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 6)NOTE: PLEASE NOTE THAT OUTLET SPACING
 FOR KITCHEN NEEDS TO MEET 210-52C-1,2,3,
  
 7)NOTE: PLEASE NOTE, ALL OUTLET NEEDS TO
 BE SHOWN AS GFI FOR GARAGE/OUTSIDE ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-09 Cont ID  
Sent By pkrauss Date 2002-09-09 Time 15:03 Rev Time 0.00
Received By pkrauss Date 2002-09-09 Time 15:03 Sent To  
Notes
2002-09-09 00:00:00MECHANICAL PERMIT 01120268

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-16 Cont ID  
Sent By hmoser Date 2002-01-16 Time 19:39 Rev Time 0.50
Received By hmoser Date 2002-01-16 Time 19:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-23 Cont ID  
Sent By jleech Date 2002-02-23 Time 07:35 Rev Time 0.33
Received By jleech Date 2002-02-23 Time 07:35 Sent To  
Notes
2002-02-23 00:00:00ADDITIONAL PERMIT REQUIRED FOR GAS.
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-12 Cont ID  
Sent By jleech Date 2002-01-12 Time 09:12 Rev Time 0.50
Received By jleech Date 2002-01-12 Time 09:12 Sent To  
Notes
2002-01-12 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE.
 A.UPSTAIRS BATH (LEFT) SHOWER DRAIN
 UNVENTED.
 B.W/M REQUIRES A TRAP.
 C.UP STAIRS BATH (RIGHT) W/C FLUSH-
 ING PAST UNVENTED SHOWER.
 D.MASTER BATH TUB AND SHOWER ARE NOT
 VENTED.
 E.1/2 BATH AND KITCHEN SINK ARE NOT
 SHOWN ON RISER DIAGRAM.
 F.PIPING SIZING IS NOT CORRECT.
 2.ADDITIONAL PERMIT AND PLANS ARE
 REQUIRED FOR GAS.
 3.SHOW CALKULATIONS FOR LAUNDRY ROOM.
 SEE 97 SGC CHAPTER 2 (CONFINED SPACE)
 FOR EQUATION.IF ROOM IS TOO SMALL SHOW
 VENTS, SIZE AND LOCATION TO COMPLY
 WITH THE 97 SGC.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-07 Cont ID  
Sent By sgraham Date 2002-01-07 Time 16:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***