Plan Review Details - Permit 01120203
Plan Review Stops For Permit 01120203
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-29 Cont ID  
Sent By btrobaug Date 2002-01-29 Time 09:20 Rev Time 1.00
Received By btrobaug Date 2002-01-29 Time 07:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-01-15 Cont ID  
Sent By dpalmer Date 2002-01-15 Time 12:08 Rev Time 0.00
Received By dpalmer Date 2002-01-15 Time 12:08 Sent To  
Notes
2002-01-15 00:00:00******************* UNSAT *************
  
 PLEASE NOTE THAT NOT ALL NOTES FORM THE
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE NOTE A ONE-LINE RISER
 DIAGRAM NEEDS TO BE SUBMITTED FOR REVIEW
 215-5
 2)NOTE: PLANS SHOW 3-#2`S BUT WHAT SIZE
 IS THE PANEL?215-5/310-15/AND ART 240
 FOR CORRELATION OF OCP.
  
 3)NOTE: PLEASE NOTE THAT THE PANEL
 SCHEDULE NEEDS TO SHOW OCP AND ALL WIRE
 SIZES, THE NOTE SAYS #12 AND 20A OCP,
 WHAT ABOUT RANGE? DRYER?
  
 4)NOTE: PLEASE NOTE PLANS SHOW A WATER
 HEATER, PLEASE CLARIFY IF GAS OR ELEC?
 IF ELEC, PLEASE LIST.
  
 5)NOTE: PLEASE NOTE, PLANS STILL MISSING
 FRONT AND REAR RECEPT, 210-52E
  
 6)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE SYSTEM NEEDS TO BE SHOWN ON
 RISER DIAGRAM ALSO. SHOW GROUNDING
 ELECTRODE SIZE PER 250-66 AND SHOW
 ELECTRODE SYSTEM PER 250-50 TO INCLUDE
 COLD WATER PIPE AND GAS BOND IF ANY.
  
 7)NOTE: PLEASE NOTE, OUTLET SPACING IS
 MISSING SOME OUTLETS REQ`D PER 210-52.
 BEDROOMS 1&2 AND KITCHEN.
  
 8)NOTE: PLEASE CLARFIY OUTLET SPACING
 FOR KITCHEN COUNTER. PLANS SHOW OUTLET
 ON WALL AT KITCHEN PENINSULAR, PLEASE
 CLARFIY. 210-52-C-1
  
 9)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 CAN NOT BE INSTALLED IN KITCHENS, OR
 BATHS PER NFPA-72 2-5.2.1.6
  
 10)NOTE: PLEASE CLARIFY "TWO" SMALL APPL
 CIRCUITS. 210-52B
  
 11)NOTE: PLEASE SUBMIT TWO COPIES OF
 PLANS FOR REVIEW.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-07 Cont ID  
Sent By dpalmer Date 2001-12-07 Time 06:24 Rev Time 0.00
Received By dpalmer Date 2001-12-07 Time 06:24 Sent To  
Notes
2001-12-07 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMITA CONTRACT TO
 VERFIY VALUE FOR COMPLETE SCOPE OF WORK.
 PLEASE NOTE THAT PER PALM BEACH COUNTY
 AND CITY-WIDE ADMINISTRATIVE CODE 104.7.
 5.. VALUE OS TO INCLUDE ALL LABOR AND
 MATERIALS. EVEN OF SOME PART IS OWNER
 SUPPLIED.
  
 2)NOTE: PLEASE NOTE THAT THERE IS NOT
 ENOUGH INFORMATION FOR SERVICE CHANGE.
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 MORE DETAIL FOR CONDUIT SIZES, WIRE ,
 GROUNDING ETC.215-5
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 7) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 8) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
  
 9) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE CLARIFY ON REAR BEDROOM.#2
  
 10)NOTE: PLEASE NOTE MISSING CIRCUITS
 REQ`D TO BE MIN FOR WASHER/SM APPLIANCE
  
 11)NOTE: PLEASE CLARIFY IF THERE IS ANY
 A/C UNITS?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 PLEASE SUBMIT TWO COPIES FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372