| 2001-12-07 00:00:00 | ***************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMITA CONTRACT TO |
| | VERFIY VALUE FOR COMPLETE SCOPE OF WORK. |
| | PLEASE NOTE THAT PER PALM BEACH COUNTY |
| | AND CITY-WIDE ADMINISTRATIVE CODE 104.7. |
| | 5.. VALUE OS TO INCLUDE ALL LABOR AND |
| | MATERIALS. EVEN OF SOME PART IS OWNER |
| | SUPPLIED. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THERE IS NOT |
| | ENOUGH INFORMATION FOR SERVICE CHANGE. |
| | PLEASE SUBMIT A RISER DIAGRAM SHOWING |
| | MORE DETAIL FOR CONDUIT SIZES, WIRE , |
| | GROUNDING ETC.215-5 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 7) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 8) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | |
| | 9) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | PLEASE CLARIFY ON REAR BEDROOM.#2 |
| | |
| | 10)NOTE: PLEASE NOTE MISSING CIRCUITS |
| | REQ`D TO BE MIN FOR WASHER/SM APPLIANCE |
| | |
| | 11)NOTE: PLEASE CLARIFY IF THERE IS ANY |
| | A/C UNITS? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION AND |
| | PLEASE SUBMIT TWO COPIES FOR REVIEW. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |