Plan Review Details - Permit 01120192
Plan Review Stops For Permit 01120192
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By ndenmark Date 2002-04-04 Time 10:23 Rev Time 0.25
Received By ndenmark Date 2002-04-04 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-12-10 Cont ID  
Sent By pkrauss Date 2001-12-10 Time 13:22 Rev Time 0.45
Received By pkrauss Date 2001-12-10 Time 13:22 Sent To  
Notes
2001-12-10 00:00:00*******************PROVISO**************
  
 (ON PLAN)
  
 AIR FROM RESTROOMS SHALL NOT BE
 RECIRCULATED. 1997 SMC 503.3.1.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS FOR
 SYSTEMS WITH FAN CAPACITY GREATER THAN
 2,000 CFM.NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS.
 1997 SMC 406.1 & NFPA 90A 4-.4.4.3.