| Plan Review Stops For Permit 01120136 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-17 |
Time |
15:01 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-21 |
Time |
14:13 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-03-21 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01120136 | | | 820 RIDGEWOOD DR | | | CONT: GARRETT CONST CORP | | | TEL: 792-6090 | | | THIRD REVIEW | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | FLORIDA STATE STATUTE 553.80.2(B) THE | | | LOCAL GOVERNMENT SHALL IMPOSE, EACH TIME | | | AFTER THE THIRD SUCH REVIEW THE PLANS | | | ARE REJECTED FOR THE SAME VIOLATION, A | | | FEE OF FOUR TIMES THE AMOUNT OF THE | | | PROPORTION OF THE PERMIT FEE ATTRIBUTED | | | TO PLAN REVIEW. | | | | | | 1)- ROOF ASSEMBLY: THE PRODUCT APPROVAL | | | SUBMITTED FOR THE "MASTER RIB" METAL | | | ROOFING IS EXPIRED. ONLY THE TOP PAGE | | | WAS SUBMITTED.THE CITY SEARCHED THE | | | METRO-DADE PRODUCT APPROVAL SITE USING | | | ADVANCED SEARCH THROUGH ROOFING AS WELL | | | AS PANELS AND DIDNOT FIND ANY CURRENT RE | | | PORT FOR THE COMPANY UNION CORRUGATED | | | COMPANY, A SEARCH FOR ACCEPTANCE NO. | | | 98-04211. ALSO HAD NO RESULTS. | | | THE PRODUCT TESTING REPORT SHALL INDI- | | | CATE IF THE STEEL ROOFING IS TESTED AS | | | STRUCTURAL PANELS WHICH WOULD NOT | | | REQUIRE SOLID SHEATHING BENEATH OR WILL | | | INDICATE A NON-STRUCTURAL PANEL REQUIR- | | | ING SOLID SHEATHING. A MANUFACTURERS | | | SPEC SHALL ALSO BE REQUIRED FOR THE | | | ATTACHMENT METHOD. | | | SEE SBC1509 & 1510 FOR STEEL ROOFING | | | REQUIREMENTS. | | | | | | 2)- CONTRACTOR SHALL SUBMIT PLANS TO THE | | | COUNTY FOR IMPACT FEE ASSESSMENT. | | | | | | 3)- PAY RADON FEES OF $8.64. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-05 |
Time |
09:35 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-02-05 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2002-02-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01120136 | | | 820 RIDGEWOOD DR | | | CONT: GARRETT CONST CORP | | | TEL: 792-6090 | | | SECOND REVIEW | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- SBC 2304.2.2 ALL POST POLES & | | | COLUMNS SUPPORTING PERMANENT STRUCTURES | | | AND EMBEDDED IN CONCRETE WHICH IS IN | | | CONTACT WITH GROUND SHALL BE APPROVED | | | PRESERVATIVE-TREATED WOOD SUITABLE FOR | | | GROUND CONTACT USE. | | | | | | 2) SBC 1606.2.6.2 COMPONENTS & CLADDING | | | PRODUCT APPROVALS (2 COPIES) SHALL BE RE | | | QUIRED FOR THE FOLLOWING ITEMS: | | | | | | GARAGE OR OVERHEAD DOORS: OPENING SIZE | | | IS 10'WX 8'H THE REPORT FURNISHED IS | | | MAX AT 9'WX 8H'. | | | ROOF ASSEMBLY TOP SHEET OF REPORT NOT | | | ACCEPTABLE, REPORT IS EXPIRED. | | | REPORT SHALL INDICATE IF THE METAL | | | PANEL ROOFING IS ARCHITECTURAL | | | METAL REQUIRING SOLID SHEATHING OR | | | SBC 1509 OR STRUCTURAL METAL ROOFING | | | COVERED IN SBC 1510 WHICH WILL ALLOW | | | ATTACHMENT THROUGH PURLIN SYSTEM. | | | IF REPORT DOESN'T INDICATE FREQUENCY | | | OF ATTACHMENT MANUFACTURES SPEC | | | SHALL BE REQUIRED. | | | | | | 3)- CONTRACTOR TO SUBMIT PLANS TO COUNTY | | | FOR IMPACT FEE ASSESMENT. | | | | | | 4) PAY RADON FEES, $8.64. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-11 |
Time |
07:15 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2001-12-11 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2001-12-11 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01120136 | | | 820 RIDGEWOOD DR. | | | CONT: GARRETT CONST. CORP. | | | TEL: 792-6090 | | | | | | SBC= STAANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | DESIGN CERTIFCATION SHEET | | | 1)- OCCUPANCY: PLANS INDICATE S.F.R. | | | CAT. IV.ASCE7-95 TABLE 1-1 MINOR | | | STORAGE FACILITY TYPE I NOT IV | | | | | | 2)- BUILDING PARTIALLY ENCLOSED? PLANS | | | INDICATE TOTALLY ENCLOSED. | | | | | | 3)- DESIGN FOR 7-95 IS 145 WIND ZONE. | | | | | | 4)- IMPORTANCE FACTOR INCORRECT ASCE | | | 7.95 TABLE 0.87 | | | | | | 5)- ASCE 7-95 EXPOSURE NOT GIVEN, 6.5.3. | | | 3.1 EXPOSURE CATORIES | | | | | | 6)- SBC 2304.2.2 ALL POST POLES & COL- | | | UMNS SUPPORTING PERMANENT STRUCTURES AND | | | EMBEDDED IN CONCRETE WHICH IS IN CONTACT | | | WITH GROUND SHALL BE APPROVED PRESERVA- | | | TIVE-TREATED WOOD SUITABLE FOR GROUND | | | CONTACT USE. | | | | | | 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | PRODUCT APPROVALS (2 COPIES) SHALL BE | | | REQUIRED FORTHE FOLLOWING ITEMS: | | | GARAGE OR OVERHEAD DOORS | | | EXTERIOR SWING DOORS | | | ROOFING ASSEMBLIES | | | SBCCI OR DADE COUNTY TEST REPORTS | | | ARE REQUIRED. | | | | | | 8)- SBC 1510 STRUCTURAL METAL ROOFING | | | SUPPLY MANUFACTURES SPECS FOR APPLCATION | | | ALSO SUPPLY INFOR THAT THE ROOF IS | | | CAPABLE OF RESISTING LIVE LOADS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-21 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-21 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-30 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-30 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2002-01-30 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW | | | BEING SHOWN DELETING ELECTRICAL SERVICE | | | AND ELECTRICAL INSIDE GARAGE? | | | PLEASE NOTE THAT PER NEC A LIGHT AND | | | RECEPT IS REQ`D. THEY BOTH CAN BE ON | | | ONE CIRCUIT, BUT MUST CONTAIN A MEANS | | | OF DISCONNECT AT DETACHED BLDG. | | | 225-31 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-11 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-11 |
Time |
19:19 |
Sent To |
Z |
|
| Notes |
| 2001-12-11 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER ZONING REG | | | A SEPARATE SERVICE IS NOT PERMITTED FOR | | | ZONING OF SF-7(SINGLE FAMLIY) PLEASE | | | NOTE THAT ELECTRICAL FOR DETACHED GARAGE | | | WOULD NEED TO COME FROM EXISTING ELEC | | | SERVICE OR FROM NEW SERVICE MOUNTED ON | | | GARAGE AND BY BACK FEEDING EXISTING | | | HOUSE. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL OUTLETS IN | | | GARAGE NEED TO BE SHOWN AS GFI/GFI | | | PROTECTED PER210-8. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-06-18 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-06-18 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-11 |
Time |
19:24 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|