Plan Review Details - Permit 01120102
Plan Review Stops For Permit 01120102
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 09:45 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-21 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 12:30 Rev Time 1.75
Received By dpalmer Date 2001-12-21 Time 16:27 Sent To  
Notes
2001-12-21 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01120102
 1001 SUMMIT BLVD
 O/B SALGADO, BERNARDO
 TEL: 547-3893
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 NEW WINDOWS WILL REQUIRE PRODUCT TESTING
 REPORTS FOR LARGE MISSLE IMPACT RESIS-
 TAANCE TESTING. 2 COPIES EITHER SBCCI OR
 DADE COUNTY PRODUCT TESTING REPORTS ARE
 ACCEPTED.
  
 2)- THE GUEST BEDROOM SHALL REQUIRE A
 SECOND MEANS OF EGRESS( SBC 1005.4.4)
 INDICATE THE SIZE OF THE WINDOW, WHAT
 WILL THE NET CLEAR AREA OF THE OPENING
 BE WHEN WINDOW IS OPEN?
  
 3)- SBC 2309.6 ACCESS TO ATTIC SPACE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-14 Cont ID  
Sent By btrobaug Date 2002-06-14 Time 14:24 Rev Time 0.00
Received By btrobaug Date 2002-06-14 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-01-02 Cont ID  
Sent By dpalmer Date 2002-01-02 Time 06:35 Rev Time 0.00
Received By dpalmer Date 2002-01-02 Time 06:35 Sent To  
Notes
2002-01-02 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEAS ENOTE THAT NO INFORMATION
 WAS SUBMITTED FOR EXISTING SERVICE SIZE?
 PLEASE SHOW SIZE OF EXISITNG, METERCAN
 AND WIRE SERVICE ENTRANCE CONDUCTORS
 NEW LOAD IS SHOWN AT 57AMPS., PLEASE
 CLARIFY LOAD FOR MAIN HOUSE.
 MAIN HOUSE EXISTING SERVICE WAS 150A.
  
 2)NOTE: PLEASE NOTE THAT NO MEANS OF
 DISCONNECT IS SHOWN FOR
 DETACHED BLDG. 225-31. PLEASE NOTE 125A
 PANEL IS SHOWN AS MLO?
  
 3)NOTE: PLEASE NOTE EXISTING GROUNDING
 ELECTRODE SYSTEM IS SHOWN FOR MAIN HOUSE
 BUT NOT FOR DETACHED BLDG? PLEASE
 CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFOAMTION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-10 Cont ID  
Sent By dpalmer Date 2001-12-10 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2001-12-10 Time 14:23 Sent To  
Notes
2001-12-10 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARFIY TWO SMALL APPLI-
 ANCE CIRCUITS SHOWN. AS PER ZOING REQ`-
 -MENTS, KITCHEN NOT PERMITTED.
  
 2)NOTE: PLEASE CLARIFY SIZE OF EXISTING
 SERVICE ENTRANCE CONDCUTORS.
 NEW LOADS BEING ADDED NEED CLARIFICATION
  
 3)NOTE: PLEASE NOTE PLANS SHOW TWO NEW
 MAIN DISC`S ? PLEASE SUBMIT AIC RATINGS
 FOR ALL NEW EQUIPMENT PER 110-9.
  
 4)NOTE: PLEASE SHOW LOAD ON EXSITING
 HOUSE NEEDED FOR CLARIFICATION OF
 EXISTING SERVICE ENTRANCE CONDUCTORS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-01-02 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 12:27 Rev Time 0.35
Received By pkrauss Date 2002-01-02 Time 12:15 Sent To B
Notes
2002-01-02 00:00:00 
  
 NOTE ON RESUB INDICATES MECHANICAL
 CONTRACTOR TO ADDRESS COMMENTS FROM 1ST
 REVIEW.(SUPPLY ENERGY CALCS & MANUAL
 J)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-18 Cont ID  
Sent By pkrauss Date 2001-12-18 Time 14:50 Rev Time 0.40
Received By pkrauss Date 2001-12-18 Time 14:48 Sent To B
Notes
2001-12-18 00:00:00*******************DENIED***************
  
 AN HVAC SIZING CALCULATION SHALL BE
 PERFORMED ON THE BUILDING AND SHALL BE
 ATTACHED TO THE FORM 600 SUBMITTED WHEN
 APPLICATION IS MADE.SIZING OF THE
 HVAC SYSTEM SHALL BE DETERMINED FOR
 EACH ZONE WITHIN A DWELLING IN
 ACCORDANCE WITH ACCA MANUAL J.
  
 PLEASE PROVIDE THE ABOVE INFORMATION FOR
 REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 13:58 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-05 Cont ID  
Sent By sgraham Date 2001-12-05 Time 10:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***