Plan Review Details - Permit 01120092
Plan Review Stops For Permit 01120092
Review Stop P PLUMBING
Rev No 4 Status F Date 2002-01-07 Cont ID  
Sent By pschmitz Date 2002-01-07 Time 10:01 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-07 00:00:00DENIED, BLDGDOES NOT MEET SET BACK. PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-18 Cont ID  
Sent By kstevens Date 2001-12-18 Time 12:12 Rev Time 1.00
Received By kstevens Date 2001-12-18 Time 12:12 Sent To  
Notes
2001-12-18 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) OPENING FOR WATER CLOSET, LAV. AND
 SHOWER SHALL BE MINIMUM OF 95" ROUGH
 OPENING. 15" OFF FINISHED WALL TO CENTER
 LINE OF W/C, 30" CENTER OF W/C TO C/L OF
 LAV, LAV TO BE MINIMUM OF 4" OFF SHOWER
 WALL, AND SHOWER TO MINIMUM OF 30" IN-
 SIDE FINISHED SIDE TO SIDE.
 SPC SEC 403.4 - SEC 417.4
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-16 Cont ID  
Sent By pschmitz Date 2001-12-16 Time 10:25 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00PLUMBING PLAN REVIEW DENIED.
 MIN FACILITIES REQ. LAV IN BATH RM.
 SHOW ALL EX FACILITIES INC WASHING
 MACHINE LOCATION.
 END OF COMMENTS PAUL SCHMITZ
 659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.50
Received By kstevens Date 2001-12-04 Time 18:14 Sent To  
Notes
2001-12-04 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) DRY VENT NOT ACCEPTABLE PER SPC SEC
 906.2.1.
  
 2) MINIMUM 3" VENT REQUIRED FOR EACH
 SEPARATE BLDG DRAIN. SPC SEC 904.3.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377