Plan Review Details - Permit 01120066
Plan Review Stops For Permit 01120066
Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-19 Cont ID  
Sent By kstevens Date 2001-12-19 Time 14:21 Rev Time 1.25
Received By kstevens Date 2001-12-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 13:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-15 00:00:00PLAN REVIEW, DENIED 3RD TIME.
 PLEASE ADDRESS PREVIOUS COMMENTS.
 PAUL SCHMITZ 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-09 Cont ID  
Sent By pschmitz Date 2001-12-09 Time 17:02 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-09 00:00:00PLUMBING PLAN REVIEW, DENIED 2ND TIME.
 ADDRESS PREVIOUS NOTES BY DATED 12-04-01
 NEW COMMENTS, PROVIDE CUT SHTS FOR
 REGULATORS. SHOW SOV AND UNION AT EACH
 REGULATOR.SGC-97 SEC 104.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-12-04 Cont ID  
Sent By kstevens Date 2001-12-04 Time 15:03 Rev Time 0.50
Received By kstevens Date 2001-12-04 Time 15:03 Sent To  
Notes
2001-12-04 00:00:00DENIED
 REFERENCE: SGC-97
  
 1) PER TABLE 305.4A, 1-1/4" PIPE REQUIR-
 ED FOR 130'-290,000 BTU'S.
 2) MANUFACTURE SHEET REQUIRED FOR POOL
 HEATER PER SGC SEC 402.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377