| Plan Review Stops For Permit 01120062 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-10 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-11 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-07 |
Time |
09:26 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-07 |
Time |
09:26 |
Sent To |
FIRE |
|
| Notes |
| 2001-12-07 00:00:00 | ******************PROVISO*************** | | | | | | | | | NOTE, DUCTS SERVING FOOD COOKING AND | | | PROCESSING EQUIPMENT, SHALL TERMINATE | | | 10 FT FROM ANY ADJACENT BUILDING, | | | PARKING AREA, ADJACENT PROPERTY LINE, | | | WINDOW, DOOR, OR AIR INTAKE.EXHAUST | | | OUTLET SHALL TERMINATE 40 INCHES ABOVE | | | THE ROOF.(1997 SMC 605.1) | | | | | | MINIMUM SLOPE SHALL NOT BE LESS THAN 1 | | | INCH PER FOOT AS PER 1997 SMC 505.4. | | | | | | | | | ALL WELDS TO BE INSPECTED PRIOR TO | | | INSTALLATION OF WRAP OR ENCLOSURE OF | | | DUCTWORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|