Plan Review Details - Permit 01120030
Plan Review Stops For Permit 01120030
Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-02-19 Cont ID  
Sent By pkrauss Date 2002-02-19 Time 13:34 Rev Time 0.50
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-19 00:00:00 
 PROVISO DATED 1/8/02 UNDER PERMIT
 01120339
  
 CALLED CONTRACTOR - PLANS CONFLICT WITH
 THE MANUFACTURER'S SPECS.
  
 MANUFACTURER TO SUPPLY LETTER ON OVEN
 TEMP AND DISTANCE OF THE WIND CAP ABOVE
 THE PARAPET WALL.
  
 THIS IS TO BE SUBMITTED PRIOR TO
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-01-02 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 10:32 Rev Time 0.50
Received By pkrauss Date 2002-01-02 Time 10:32 Sent To  
Notes
2002-01-02 00:00:00******************DENIED****************
  
 3RD REVIEW
  
 WRONG PERMIT ON SUBMITTAL FORM PERMIT
 FOR HEAT REMOVAL IS 01120030.
  
 COMMENTS FROM 2ND REVIEW NOT ADDRESSED:
 1. PROVIDE MANUFACTURES INSTALLATION
 INTRUCTIONS SHOWING ALLOWABLE
 CLEARANCE OF B VENT.
  
 2. PROVIDE AREA OF EQUIPMENT LOCATION
 AND TO DEMONSTRATE ADEQUATE
 COMBUSTION AIR FOR OVEN AS REQUIRED
 BY MANUFACTURE.
  
 SPECIFICATIONS SUBMITTED 12/27/01, DOES
 NOT SPECIFY TYPE B VENT.DEVELOPED
 LENGHT FOR VENT?DRAFT DIVERTER
 INSTALLED STRAIGHT & 18" - 24" ABOVE
 CONNECTION.NOTE 2 INDICATES WIND CAP
 MUST BE INSTALLED AT A MINIMUM OF 4 FT
 ABOVE ANY OBSTRUCTION (24" INDICATED ON
 PLAN).TEMPERATURE RANGE UP TO 600
 DEGREES F. B VENT FLUE TEMP NOT IN
 EXCESS OF 550 DEGREES.
 1997 SGC 605.3.1.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-12-26 Cont ID  
Sent By ndenmark Date 2001-12-26 Time 14:01 Rev Time 0.50
Received By ndenmark Date 2001-12-26 Time 14:01 Sent To  
Notes
2001-12-26 00:00:00*****************DENIED*****************
 1. PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS SHOWING ALLOWABLE
 DEVELOPED LENGTH OF VENT AND ALLOWABLE
 CLEARANCE OF B VENT
 2. PROVIDE AREA OF EQUIPMENT LOCATION
 AND TO DEMONSTRATE ADEQUATE COMBUSTION
 AIR FOR OVEN AS REQUIRED BY MANUFACTURE.
 3. PROVIDE INFORMATION FROM MANUFACTURE
 ON REQUIRED TERMINATION OF HEAT REMOVAL
 AND COMBUSTION AIR REMOVAL VENTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-07 Cont ID  
Sent By pkrauss Date 2001-12-07 Time 09:08 Rev Time 0.40
Received By pkrauss Date 2001-12-07 Time 09:08 Sent To  
Notes
2001-12-07 00:00:00 
 NO PLANS SUBMITTED FOR MAKE-UP AIR FOR
 HOOD AND FLUE FOR OVEN.THIS IS NOT A
 GREASE DUCT.FOR HEAT ONLY.
  
 CONTRACTOR TO BRING PLANS IN THE WEEK OF
 12/10/01PHK