Plan Review Details - Permit 01120030
| Plan Review Stops For Permit 01120030 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-19 |
Time |
13:34 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | | | | PROVISO DATED 1/8/02 UNDER PERMIT | | | 01120339 | | | | | | CALLED CONTRACTOR - PLANS CONFLICT WITH | | | THE MANUFACTURER'S SPECS. | | | | | | MANUFACTURER TO SUPPLY LETTER ON OVEN | | | TEMP AND DISTANCE OF THE WIND CAP ABOVE | | | THE PARAPET WALL. | | | | | | THIS IS TO BE SUBMITTED PRIOR TO | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-02 |
Time |
10:32 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-01-02 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | ******************DENIED**************** | | | | | | 3RD REVIEW | | | | | | WRONG PERMIT ON SUBMITTAL FORM PERMIT | | | FOR HEAT REMOVAL IS 01120030. | | | | | | COMMENTS FROM 2ND REVIEW NOT ADDRESSED: | | | 1. PROVIDE MANUFACTURES INSTALLATION | | | INTRUCTIONS SHOWING ALLOWABLE | | | CLEARANCE OF B VENT. | | | | | | 2. PROVIDE AREA OF EQUIPMENT LOCATION | | | AND TO DEMONSTRATE ADEQUATE | | | COMBUSTION AIR FOR OVEN AS REQUIRED | | | BY MANUFACTURE. | | | | | | SPECIFICATIONS SUBMITTED 12/27/01, DOES | | | NOT SPECIFY TYPE B VENT.DEVELOPED | | | LENGHT FOR VENT?DRAFT DIVERTER | | | INSTALLED STRAIGHT & 18" - 24" ABOVE | | | CONNECTION.NOTE 2 INDICATES WIND CAP | | | MUST BE INSTALLED AT A MINIMUM OF 4 FT | | | ABOVE ANY OBSTRUCTION (24" INDICATED ON | | | PLAN).TEMPERATURE RANGE UP TO 600 | | | DEGREES F. B VENT FLUE TEMP NOT IN | | | EXCESS OF 550 DEGREES. | | | 1997 SGC 605.3.1. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-12-26 |
Time |
14:01 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-12-26 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | *****************DENIED***************** | | | 1. PROVIDE MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS SHOWING ALLOWABLE | | | DEVELOPED LENGTH OF VENT AND ALLOWABLE | | | CLEARANCE OF B VENT | | | 2. PROVIDE AREA OF EQUIPMENT LOCATION | | | AND TO DEMONSTRATE ADEQUATE COMBUSTION | | | AIR FOR OVEN AS REQUIRED BY MANUFACTURE. | | | 3. PROVIDE INFORMATION FROM MANUFACTURE | | | ON REQUIRED TERMINATION OF HEAT REMOVAL | | | AND COMBUSTION AIR REMOVAL VENTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-07 |
Time |
09:08 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-07 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2001-12-07 00:00:00 | | | | NO PLANS SUBMITTED FOR MAKE-UP AIR FOR | | | HOOD AND FLUE FOR OVEN.THIS IS NOT A | | | GREASE DUCT.FOR HEAT ONLY. | | | | | | CONTRACTOR TO BRING PLANS IN THE WEEK OF | | | 12/10/01PHK |
|
|
|