Plan Review Details - Permit 01111245
Plan Review Stops For Permit 01111245
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-09 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2002-01-09 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-09 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2002-01-09 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2001-12-06 Cont ID  
Sent By mcarsill Date 2001-12-06 Time 11:17 Rev Time 0.00
Received By mcarsill Date 2001-12-06 Time 11:17 Sent To  
Notes
2001-12-06 00:00:001) WHAT PREVENTS THE HOSE FROM KINKING
 AFTER IT IS CONNECTED TO THE FIRE
 DEPARTMENT CONNECTION SINCE THE RISERS
 WILL BE LOCATED ON THE SIDES OF THE
 BUILDING.
 2) IT WAS NOTED IN THE SPEC BOOKS AND
 THE PLANS THAT CENTRAL BRAND FIRE
 SPRINKLER HEADS TYPE LF WILL BE
 USED. LF SPRINKLER HEADS WERE NOTED
 ON THE VOLUNTARY RECALL LIST FROM
 CENTRAL, PLEASE SEE WWW.SPRINKLER
 REPLACEMENT.COM.
 3) A 2 1/2 FIRE DEPARTMENT CONNECTION
 IS REQUIRED.
 4) PLEASE EXPLAIN WHY THE SPARE
 SPRINKLER HEADS WILL BE STORED IN THE
 CLUBHOUSE AS OPPOSED TO THE INDIVIDUAL
 BUILDINGS.
 5) WHAT PREVENTS THE VALVE FROM BEING
 CLOSED ON THE UNDERGROUND FIRE LINE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-09 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2002-01-09 Time 13:34 Sent To  
Notes
***NONE***