Plan Review Details - Permit 01111208
Plan Review Stops For Permit 01111208
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-12-18 Cont ID  
Sent By mcarsill Date 2001-12-18 Time 15:30 Rev Time 0.00
Received By mcarsill Date 2001-12-18 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-12-18 Cont ID  
Sent By mcarsill Date 2001-12-18 Time 15:31 Rev Time 0.00
Received By mcarsill Date 2001-12-18 Time 15:31 Sent To  
Notes
2001-12-18 00:00:001) 2 1/2 TO 1/2 REDUCERS WILL BE
 REQUIRED ON THE STANDPIPES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FS  
Rev No 1 Status F Date 2001-12-06 Cont ID  
Sent By mcarsill Date 2001-12-06 Time 10:34 Rev Time 0.00
Received By mcarsill Date 2001-12-06 Time 10:34 Sent To  
Notes
2001-12-06 00:00:001) PLEASE INDICATE ON THE PLANS THAT
 TEMPORARY STANDPIPE(S) ARE REQUIRED WHEN
 THE BUILDING REACHES THREE STORIES AND
 FIFTY FEET IN HEIGHT WHILE IT IS UNDER
 CONSTRUCTION.
 2) THE TWO FIRE DEPARTMENT CONNECTIONS
 MUST BE WITHIN 150 FEET OF A FIRE
 HYDRANTS.
 3) PLEASE REVIEW NFPA 14, 1993 EDITION
 SECTION 5-3.2 (E) STANDPIPE CONNECTIONS.
 4) PLEASE INDICATE ON THE PLANS ANY
 AREAS OF THE BUILDING THAT ARE NOT
 SPRINKLERED AND PROVIDE THE APPLICABLE
 CODE REFERENCE.
 5) NO CUT SHEETS PROVIDED ON FIRE
 SPRINKLER HEADS PLANNED FOR USE.
 6) VALUE OF PERMIT INDICATES A VALUE
 OF 272,000 DOLLARS. PLEASE PROVIDE
 DOCUMENTATION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-18 Cont ID  
Sent By mcarsill Date 2001-12-18 Time 15:31 Rev Time 0.00
Received By mcarsill Date 2001-12-18 Time 15:31 Sent To  
Notes
***NONE***