Plan Review Details - Permit 01111172
Plan Review Stops For Permit 01111172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-11 Cont ID  
Sent By jwitmer Date 2002-01-11 Time 13:25 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-11 00:00:00FL ACC CODE 4.13.5(EXCEP.4:B) ROOMS THAT
 ARE NOT OPEN TO THE GENERAL PUBLIC
 WHICH HOUSE NO MORE THAN (5) PEOPLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-04 Cont ID  
Sent By jwitmer Date 2002-01-04 Time 16:38 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01111172
 1025 26TH ST
 CONT: L & L INTERIOR & REMODELING
 TEL: 699-2844
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- PLANS INDICATE OWNER TO VERIFY
 MINIMUM BEARING VALUE, SBC1804.2.7.2(3)
 2)- SBC TABLE 600 END WALLS 3'-10' ALLOW
 10% OPENINGS.
 3)- SBC F102.2.6. EXTERIOR WALLS TYPE
 IV BUIULDING SHALL HAVE A 2 HR FIRE
 RESISTANCE WHEN WALLS ARE WITHIN 30'.
 4)- FL ACCES CODE PROVIDE A HANDICAPPED
 RAMP MEETING SLOPE REQUIREMENTS, SHOW
 FRAMING, SHOW GAURDRAILS ETC.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-01-11 Cont ID  
Sent By drunnels Date 2002-01-11 Time 11:59 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
2002-01-11 00:00:00ELEC PERMIT ISSUED SEPERATE PER D PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 21:07 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 21:06 Sent To  
Notes
2001-12-26 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE AN ELECTRICAL
 CONTRACTOR WAS NOT SIGNED ON
 APPLICATIONFOR ELECTRICAL PERMIT.
  
 2)NOTE: PLEASE NOTE MODULAR BLDG IS
 EXEMPT FROM ELECTRICAL PLAN REVIEW,
 HOWEVER THE ELECTRICAL RISER AND
 GROUNDING FOR TRAILER HOOK-UP IS REQ`D.
 IF REQUESTED BY GC, SEPARATE PLANS AND
 PERMIT APPLICATION CAN BE SUBMITTED AT
 A LATER DATE IN ORDER TO ISSUE BLDG
 PERMIT.
 PLEASE SUBMIT A RISER DIAGRAM FOR HOOK
 UP AND GROUNDING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-12-20 Cont ID  
Sent By mamini Date 2001-12-20 Time 16:15 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 11:20 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 11:20 Sent To  
Notes
2001-12-27 00:00:00PLEASE BE ADVISED THAT THE LOCATION
 SHOWN ON THE PLANS IS LOCATED WITHIN
 THE CITY FIRE LIMITS. COMPLIANCE IS
 REQUIRED OF THE STANDARD BUILDING CODE,
 APPENDIX F AND CHAPTER 11 OF THE CITY
 CODE. IF THE BUILDING IS IV IT IS
 ALLOWED IN THE CITY FIRE LIMTS. TYPE VI
 CONSTRUCTION IS NOT ALLOWED IN THE
 FIRE LIMITS. PLAN MENTION BOTH TYPES
 OF CONSTRUCTION TYPE VI AND TYPE IV.
 WHAT IS THE PURPOSE OF THE TRAILER AND
 HOW LONG WILL IT BE ON SITE. PLEASE
 SEE STANDARD BUILDING CODE, SECTION
 F102.2.6.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-02 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 07:50 Rev Time 0.30
Received By pkrauss Date 2002-01-02 Time 07:50 Sent To  
Notes
2002-01-02 00:00:00D.C.A. OCCUPANCY - B APPROVED
 #MB023454 TYPE IV

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-01-09 Cont ID  
Sent By kstevens Date 2002-01-09 Time 18:02 Rev Time 0.50
Received By kstevens Date 2002-01-09 Time 18:01 Sent To  
Notes
2002-01-09 00:00:00PASSED/PROVISO
  
 1) PLUMBING PERMIT REQUIRED
 2) IRRIGATION PERMIT REQUIRED
 3) RPZ BACKFLOW REQUIRED ON WATER SER-
 VICE.
 4) PLUMBING CONTRACTOR TO INSTALL VALVE
 AND WATTS N36 VACUUM BREAKER FOR IRRIGA-
 TION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-01-15 Cont ID  
Sent By lmartine Date 2002-01-15 Time 09:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-01-15 00:00:00APPROVED BY JIM MCLHANEY, SEE PLANS
 1/11/02LM

Review Stop Z ZONING
Rev No 1 Status F Date 2001-12-18 Cont ID  
Sent By sgraham Date 2001-12-18 Time 11:44 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-12-18 00:00:00NEED LANDSCAPE PLAN