| Plan Review Stops For Permit 01111172 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-11 |
Time |
13:25 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-11 00:00:00 | FL ACC CODE 4.13.5(EXCEP.4:B) ROOMS THAT | | | ARE NOT OPEN TO THE GENERAL PUBLIC | | | WHICH HOUSE NO MORE THAN (5) PEOPLE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-04 |
Time |
16:38 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01111172 | | | 1025 26TH ST | | | CONT: L & L INTERIOR & REMODELING | | | TEL: 699-2844 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- PLANS INDICATE OWNER TO VERIFY | | | MINIMUM BEARING VALUE, SBC1804.2.7.2(3) | | | 2)- SBC TABLE 600 END WALLS 3'-10' ALLOW | | | 10% OPENINGS. | | | 3)- SBC F102.2.6. EXTERIOR WALLS TYPE | | | IV BUIULDING SHALL HAVE A 2 HR FIRE | | | RESISTANCE WHEN WALLS ARE WITHIN 30'. | | | 4)- FL ACCES CODE PROVIDE A HANDICAPPED | | | RAMP MEETING SLOPE REQUIREMENTS, SHOW | | | FRAMING, SHOW GAURDRAILS ETC. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2002-01-11 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-11 00:00:00 | ELEC PERMIT ISSUED SEPERATE PER D PALMER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-26 |
Time |
21:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-26 |
Time |
21:06 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE AN ELECTRICAL | | | CONTRACTOR WAS NOT SIGNED ON | | | APPLICATIONFOR ELECTRICAL PERMIT. | | | | | | 2)NOTE: PLEASE NOTE MODULAR BLDG IS | | | EXEMPT FROM ELECTRICAL PLAN REVIEW, | | | HOWEVER THE ELECTRICAL RISER AND | | | GROUNDING FOR TRAILER HOOK-UP IS REQ`D. | | | IF REQUESTED BY GC, SEPARATE PLANS AND | | | PERMIT APPLICATION CAN BE SUBMITTED AT | | | A LATER DATE IN ORDER TO ISSUE BLDG | | | PERMIT. | | | PLEASE SUBMIT A RISER DIAGRAM FOR HOOK | | | UP AND GROUNDING. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-12-20 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-27 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-27 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2001-12-27 00:00:00 | PLEASE BE ADVISED THAT THE LOCATION | | | SHOWN ON THE PLANS IS LOCATED WITHIN | | | THE CITY FIRE LIMITS. COMPLIANCE IS | | | REQUIRED OF THE STANDARD BUILDING CODE, | | | APPENDIX F AND CHAPTER 11 OF THE CITY | | | CODE. IF THE BUILDING IS IV IT IS | | | ALLOWED IN THE CITY FIRE LIMTS. TYPE VI | | | CONSTRUCTION IS NOT ALLOWED IN THE | | | FIRE LIMITS. PLAN MENTION BOTH TYPES | | | OF CONSTRUCTION TYPE VI AND TYPE IV. | | | WHAT IS THE PURPOSE OF THE TRAILER AND | | | HOW LONG WILL IT BE ON SITE. PLEASE | | | SEE STANDARD BUILDING CODE, SECTION | | | F102.2.6. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-02 |
Time |
07:50 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-01-02 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | D.C.A. OCCUPANCY - B APPROVED | | | #MB023454 TYPE IV |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-01-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-09 |
Time |
18:02 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-09 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2002-01-09 00:00:00 | PASSED/PROVISO | | | | | | 1) PLUMBING PERMIT REQUIRED | | | 2) IRRIGATION PERMIT REQUIRED | | | 3) RPZ BACKFLOW REQUIRED ON WATER SER- | | | VICE. | | | 4) PLUMBING CONTRACTOR TO INSTALL VALVE | | | AND WATTS N36 VACUUM BREAKER FOR IRRIGA- | | | TION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-01-15 |
Time |
09:25 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-15 00:00:00 | APPROVED BY JIM MCLHANEY, SEE PLANS | | | 1/11/02LM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-12-18 |
Time |
11:44 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-18 00:00:00 | NEED LANDSCAPE PLAN |
|
|