| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-05 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-05 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | 1) FIRE ALARM NOTES INDICATES CLASS B | | | CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS | | | WILL BE PERMITTED. | | | 2) FIRE ALARM NOTES INDICATES THAT WHEN | | | DUCT SMOKE DETECTORS ARE ACTIVATED, THEY | | | WILL CAUSE A SUPERVISORY SIGNAL. THEY | | | MUST INITIATE AN ALARM. | | | 3) THE FIRE ALARM NOTES INDICATE | | | SECURITY FEATURES. PLEASE BE ADVISED | | | THAT LOCKS ON EXIT DOORS MUST COMPLY | | | WITH SPECIAL LOCKING ARRANGEMENTS OF | | | THE LIFE SAFETY CODE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|