Plan Review Details - Permit 01111142
Plan Review Stops For Permit 01111142
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-17 Cont ID  
Sent By mcarsill Date 2001-12-17 Time 11:54 Rev Time 0.00
Received By mcarsill Date 2001-12-17 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-05 Cont ID  
Sent By mcarsill Date 2001-12-05 Time 14:42 Rev Time 0.00
Received By mcarsill Date 2001-12-05 Time 14:42 Sent To  
Notes
2001-12-05 00:00:001) FIRE ALARM NOTES INDICATES CLASS B
 CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS
 WILL BE PERMITTED.
 2) FIRE ALARM NOTES INDICATES THAT WHEN
 DUCT SMOKE DETECTORS ARE ACTIVATED, THEY
 WILL CAUSE A SUPERVISORY SIGNAL. THEY
 MUST INITIATE AN ALARM.
 3) THE FIRE ALARM NOTES INDICATE
 SECURITY FEATURES. PLEASE BE ADVISED
 THAT LOCKS ON EXIT DOORS MUST COMPLY
 WITH SPECIAL LOCKING ARRANGEMENTS OF
 THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910