Plan Review Details - Permit 01111098
| Plan Review Stops For Permit 01111098 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-15 |
Time |
14:55 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-12 |
Time |
10:44 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-12-10 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | BUILDING PLAN DREVIEW | | | PERMIT # 01111098 | | | 2611 MOHAWK CI | | | CONT CREATIVE CONST CORP | | | TEL: 691-9257 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SITE PLAN REQUIRED FOR TABLE 600 | | | ISSUES. | | | | | | 2)- SBC 1606.2.6.2COMPONENTS & CLADDING | | | WINDOW & DOOR BUCK ATTACHMENT. | | | | | | 3)- SBC 1606.4.1/ 1707.4.1* CITY | | | REQUIRES 2 COPIES OF PRODUCT APPROVAL | | | FOR GLAZED OPENINGS, W/ LARGE MISSLE | | | IMPACT TESTING. SBCCI OR DADE COUNTY | | | REPORTS ARE ACCEPTED. | | | | | | 4)- ROOF COVERINGS:SBC 1503.3.2. | | | ROOFING IS TO BE TESTED FOR 110 MPH | | | WIND ZONE. | | | | | | 5)-PLANS ARE TO BE SUMMITTED TO PALM | | | BEACH COUNTY FOR ASSESMENT, IMPACT FEES. | | | | | | 6)- RADON FEES $3.52 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
20:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-05 |
Time |
20:15 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-12 |
Time |
10:41 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-01-12 |
Time |
10:41 |
Sent To |
B |
|
| Notes |
| 2002-01-12 00:00:00 | | | | MECHANICAL PERMIT REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
20:16 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-07 |
Time |
10:24 |
Sent To |
P |
|
| Notes |
| 2001-12-07 00:00:00 | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | 1.MAKE, MODEL, BTU, KW HEAT STRIP | | | FOR THE AHU AND SEER OF CONDENSER. | | | (NEW EQUIPMENT) | | | | | | 2.PROVIDE SIZE, MATERIAL, DUCT LAYOUT, | | | AND CFM DISTRIBUTION. | | | | | | 3.PROVIDE ENERGY AND MANUAL J | | | CALCULATIONS. | | | | | | 4.INDICATE LOCATION OF CONDENSER | | | UNIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-12-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-07 |
Time |
10:33 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-12-08 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-11-30 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-11-30 |
Time |
14:54 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|