Plan Review Details - Permit 01110998
| Plan Review Stops For Permit 01110998 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-10 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | PLANS ARE APPROVED WITH THE PROVISION | | | THAT THE EGRESS DOORS EQUIPPED WITH | | | CARD READERS OR OTHER LOCKING DEVICES | | | ARE CONFIGURED IN ACCORDANCE WITH | | | THE REQUIREMENTS OF SBC | | | 1012.7 FOR ACCESS CONTROLLED EGRESS | | | DOORS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-07-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-16 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
21:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-05 |
Time |
21:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-10 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-24 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-24 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-29 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-29 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2001-11-29 00:00:00 | 1) NO INTERIOR FINISH CALSSIFICATION | | | INFORMATION FOR WALLS AND CEILINGS. | | | 2) CARD READERS NOTED ON DOORS USED FOR | | | EXITING. PLEASE EXPLAIN. DOORS USED FOR | | | EXITING THAT POSSESS ANY LOCKING OR | | | SECURITY DEVICES MUST COMPLY WITH | | | "SPECIAL LOCKING ARRANGEMENTS" OF THE | | | LIFE CODE. IS EGRESS POSSIBLE FROM THE | | | TENANT SIDE REGARDLESS OF THE USE OF A | | | CARD. FREE EGRESS OR FAIL SAFE, OR ARE | | | THE DOORS FAIL SECURE. PLEASE PROVIDE | | | MORE INFORMATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-05-25 |
Time |
07:42 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-05-25 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-10 |
Time |
10:22 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-12-10 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | ******************DENIED**************** | | | | | | | | | PLAN SHEET M-1.1 NOTE 2, EXHAUST FOR BLU | | | E PRINT ROOM TO BE SCH 40 PVC.THIS IS | | | PROHIBITED IN A RETURN AIR PLENUM AS PER | | | 1997 SMC 609.1.1. | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | 2.PLEASE PROVIDE AIR BALANCE SCHEDULE | | | SHOWING COMPLIANCE WITH 1997 SMC | | | 501.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-10 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|