| 2001-12-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SBC* 104.1.1A PRODUCT APPROVAL IS |
| | REQUIRED FOR THE ELECTRICAL ROLL DOWN |
| | SHUTTERS. |
| | |
| | 4) SBC 1503.1.2.3THE ROOF SLOPE SHALL |
| | BE MINIMUM 1/4" PER FOOT. |
| | |
| | 5) SBC 2308.2.2.1THE PLYWOOD WALL |
| | SHEATHING SHALL BE MINIMUM 5/8" THICK. |
| | |
| | 6) SBC 2306.2THE WOOD HEADER DETAIL |
| | REFERS TO A SIMPSON MSTA16 CONNECTOR |
| | BETWEEN THE HEADER AND JACK STUD.THIS |
| | IS NOT A VALID SIMPSON REFERENCE. |
| | PROVIDE PRODUCT DETAILS OR A CORRECT |
| | REFERENCE. |
| | |
| | 7) FL ENERGY CODE 103.0COMPLIANCE WITH |
| | THE CODE SHALL BE DEMONSTRATED THROUGH |
| | SUBMITTAL OF CODE COMPLIANCE FORMS. |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |