Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-22 Cont ID  
Sent By pkrauss Date 2002-01-22 Time 10:45 Rev Time 0.40
Received By pkrauss Date 2002-01-22 Time 10:39 Sent To  
Notes
2002-01-22 00:00:00*******************PROVISO**************
  
  
 PLANS INDICATE WOOD SHOP.NO
 SANDING, GRINDING, OR FINISHING OF ANY
 MATERIAL THAT CAN BE RECIRCULATED
 THROUGH THE VENTILATION SYSTEM.
  
 FIRE DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 & SHALL BEAR THE
 LABLE OF AN APPROVED TESTING AGENCY.
 (1997 SMC 610.1.1)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By pkrauss Date 2001-11-30 Time 13:32 Rev Time 0.45
Received By pkrauss Date 2001-11-30 Time 13:32 Sent To  
Notes
2001-11-30 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.IS THIS A NEW SERVICE OR CHANGEOUT/
 UPGRADE.ENERGY CALCULATIONS ARE
 REQUIRED.
  
 2.PLEASE INDICATE WHAT TYPE OF WOOD
 WORK IS BEING DONE.NO SANDING,
 GRINDING, FINISHING.AS PER NFPA
 90A 2-3.7.1 AIR SHALL NOT BE RE-
 CIRCULATED FROM ANY SPACE IN WHICH
 FLAMMABLE VAPORS, FLYINGS, OR DUST
 IS PRESENT IN QUANTITIESAND
 CONCENTRATIONS THAT WOULD INTRODUCE
 HAZARDOUS CONDITION INTO THE RETURN
 AIR SYSTEM.
  
 3.WHAT IS BEING STORED IN THE STORAGE
 ROOM?SHOW COMPLAINCE WITH 1997
 SMC 501.2 (300 CFM BEING SUPPLIED -
 NO RETURN AIR.
  
 4.DETAIL OF ROOF CURB, ATTACHMENT TO
 JOIST & LOAD CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.