| Plan Review Stops For Permit 01110923 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-27 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-27 |
Time |
07:46 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-04 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-04 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2002-02-04 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOTE #3 FROM | | | FIRST REVIEW NEEDS TO BE SUBMITTED. | | | PLEASE SUBMIT AIC RATING(S) FOR ALL | | | NEW SERVICE EQUIPMENT. 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-11 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-11 |
Time |
06:24 |
Sent To |
|
|
| Notes |
| 2001-12-11 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS THAT ARE | | | SIGNED, DATED AND SEALED BY AN ENGINEER | | | MUST HAVE A TITLE BLOCK, PER61G15-23.002 | | | OF FAC/FS. | | | | | | 2)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | | RISER DIAGRAM ON 6OF6 NEEDS TO BE ON THE | | | ELECTRICAL PLAN. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | PLEASE NOTE THAT NOTE SAYS GROUND ROD | | | DRIVEN 6', PLEASE SEE NEC FOR MIN BURIAL | | | DEPTH. | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | PLEASE CLARIFY IF IT IS AN OUTLET SHOWN | | | FOR WALL IN FAMILY ROOM? | | | | | | 8) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. MISSING FRONT REC | | | | | | 9) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.2 | | | MECHANICAL CODE. | | | | | | 10)NOTE: PLEASE NOTE MISSING COND UNIT | | | FOR A/C AND DISC PER 440-11. | | | | | | 11)NOTE: PLEASE NOTE OUTLETS SHOWN IN | | | GARAGE NEED TO BE SHOWN AS GFI/GFI | | | PROTECTED ALONG WITH ALL OUTSIDE OUTLETS | | | (BACK PORCH). PER 210-8. | | | | | | 12)PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | PLEASE SEE BATHROOM BETWEEN BEDROM 2-3, | | | PLEASE NOTE TWO RECEPTS SHOWN??? | | | NO LIGHT OR LIGHT SWITCH. PLEASE CORRECT | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
12:56 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-04-23 |
Time |
12:56 |
Sent To |
R |
|
| Notes |
| 2002-04-23 00:00:00 | PROVISO: | | | | | | PLANS INDICATE 1500 CFM & MANUAL J | | | INDICATES 1263 CFM.PLEASE PROVIDE | | | MANUFACTURER INFORMATION FOR THE | | | EQUIPMENT PRIOR TO FINAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-27 |
Time |
14:04 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-03-27 |
Time |
14:04 |
Sent To |
P |
|
| Notes |
| 2002-03-27 00:00:00 | | | | COMMENTS FROM PREVIOUS REVIEW NEVER | | | ADDRESSED. | | | | | | ONLY ONE SET OF MANUAL J CALCS SUBMITTED | | | | | | PLANS INDICATE 1500 CFM DISTRIBUTION, | | | PLEASE SUBMIT MANUFACTURER SUBMITTAL | | | DATA FOR EQUIPMENT SHOWING 3 TON SYSTEM | | | WITH CAPACITY FOR 1500 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-27 |
Time |
07:46 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-11 |
Time |
07:43 |
Sent To |
R |
|
| Notes |
| 2002-02-11 00:00:00 | | | | *******************DENIED*************** | | | | | | | | | CFM DISTRIBUTION ON PLAN SHEET 5 OF | | | 6 INDICATES 1500 CFM.MANUAL J | | | CALCULATIONS INDICATE 1248 FOR A 3 | | | TON UNIT.PROVIDE MANUFACTURER | | | SUBMITTAL DATA FOR THE 3 TON UNIT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
R |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-12-10 |
Time |
17:53 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-12-10 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | PERMIT WILL BE REQUIRED FOR THIS WORK | | | PLANS AND FEES REQUIRED AT TIME OF | | | PERMIT APPLICATION BY AIRCONDITIONING | | | CONTRACTOR12/10/01H.M. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-04-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-10 |
Time |
19:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-10 |
Time |
19:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-27 |
Time |
14:17 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-10 00:00:00 | PLUMBING PLAN REVIEW,DENIEDPES | | | IOMETRIC DOES NOT MATCH FLOOR PLAN, | | | ALSO 2 PLUMBING FIXTURES IN MASTER BATH | | | MISSING,SPC-94SEC 104. 3 | | | PAUL SCHMITZ561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-07 |
Time |
16:22 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-12-07 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-08-16 |
Time |
18:47 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-16 00:00:00 | SOIL REPORT, DOOR PRODUCT APPROVAL AND | | | REVISION TO SUPPORT W.W.M. FROM ENGINEER | | | AS REQUESTED IN PROVISO. 8-16-02 RM |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-04-24 |
Time |
10:48 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2002-04-24 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2002-04-24 00:00:00 | APPROVED WITH PROVISO: | | | 1-ENGINEER OF RECORD TO PROVIDE 2X | | | STRUCTURAL BUCK DETAIL FOR ENTRY DOORS | | | AS REQUIRED BY THE PRODUCT APPROVAL | | | SUBMITTED. | | | 2-PROVIDE SLIDING GLASS DOORS APPROVED | | | DRAWINGS. PRODUCT APPROVAL SUBMITTED | | | IS MISSING THIS INFORMATION. | | | 3-PROVIDE APPROVED DRAWINGS FOR SINGLE | | | HUNG WINDOWS. PRODUCT APPROVAL IS | | | MISSING THIS INFORMATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2002-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
13:04 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2002-04-15 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2002-04-15 00:00:00 | CHECKLIST: | | | 1-NEED TO RECORD NOTICE OF COMMENCEMENT. | | | 2-PAY IMPACT FEES TO PALM BEACH COUNTY. | | | BRING PAID RECEIPT AND STAMPED DWGS. | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | A)DOUBLE ENTRY DOORS. | | | B)SINGLE HUNG WINDOWS PRODUCT APPROVAL | | | IS EXPIRED AND NEED THE APPROVED DWGS. | | | C)SLIDING GLASS DOORS PRODUCT APPROVAL | | | NEED THE APPROVED DRAWINGS. | | | D)WINDOW MULLIONS. | | | 4-ENERGY CALCULATIONS: | | | OWNER/AGENT TO SIGN AND DATE THE | | | ENERGY CALCULATIONS AT BOTTOM OF FORM. | | | 5-PROVIDE SBCCI OR DADE COUNTY PRODUCT | | | APPROVAL AND COMPLETE INFORMATION FOR | | | STORM SHUTTERS: KEY PLAN AND COMPLETE | | | INSTALLATION SCHEDULE. AND, CLEARLY | | | INDICATE ON DRAWINGS SPECIFIC MOUNTING | | | AND ANCHOR TYPE AND SPACING TO BE USED | | | ACCORDING TO THE MEAN ROOF HEIGHT, | | | DESIGN PRESSURES, PANEL SPAN, EDGE | | | DISTANCE, CONNECTION TYPE & STRUCTURE | | | TO BE ATTACHED TO (MASONRY). |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-02-19 |
Time |
19:51 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2002-02-19 |
Time |
19:51 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | SECOND CHECKLIST: | | | 1-MOST OF THE ITEMS REQUESTED ON FIRST | | | CHECKLIST WERE NOT ADDRESSED. | | | **SEE PREVIOUS CHECKLIST ATTACHED. | | | 2-AREA CALCULATIONS DON'T ADD UP. | | | 3-CLARIFY SECTION DETAIL AT ENTRY PORCH. | | | HOW ARE ROOF TRUSSES EMBEDED INTO THE | | | MASONRY WALL SEE COMMENTS ON DWG. | | | 4-UPDATE TRUSS ANCHOR SCHEDULE & SECTION | | | DETAILS WHEN SPECIFYING SIMPSOM ETA | | | CONNECTORS. THEY ARE NOT LONGER LISTED | | | ON SIMPSON CATALOGUES. | | | 5-PLEASE PAY ATTACHED RECEIPT FOR BLDG | | | UPDATED VALUE & RADON FEES ($535.38) | | | AND BRING BACK COPY OF PAID RECEIPT. | | | **NOTE: ADDITIONAL FEES WILL BE CHARGED | | | FOR RE-SUBMITTALS. SEE ATTACHED FORM. | | | 6-ENGINEER OF RECORD TO CLEARLY INDICATE | | | ON LINTEL PRODUCT APPROVAL DRAWINGS | | | THE COMPONENTS THAT ARE GOING TO BE | | | USED IN THIS PROJECT AS REQUIRED ON | | | BUILDING PERMIT REQUIREMENTS ON SHEET | | | 2 OF PRODUCT APPROVAL. | | | 7-SEE COMMENTS BY THE OTHER TRADES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2002-01-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-11 |
Time |
08:50 |
Rev Time |
3.50 |
| Received By |
jgomez |
Date |
2002-01-09 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2002-01-09 00:00:00 | CHECKLIST: | | | 1-NEED TO RECORD NOTICE OF COMMENCEMENT. | | | 2-AFTER ORIGINAL DRAWINGS ARE REVISED, | | | BRING THEM TO PALM BEACH COUNTY TO PAY | | | IMPACT FEES. BRING PAID RECEIPT AND | | | STAMPED DRAWINGS. | | | 3-PROFESSIONAL ENGINEER OF RECORD TO | | | HAVE ALL HIS INFORMATION ON ALL DWGS | | | AS REQ'D BY CHAPTER 471 FL. STATUTES. | | | -ENG'R TO DATE DWGS AT TIME OF SEALING. | | | 4-PROVIDE AREA CALCULATIONS FOR A/C AND | | | NON A/C AREAS TO DETERMINE RADON FEES | | | AND VALUATION. | | | 5-SPECIFY SAFETY GLASS WHERE REQUIRED. | | | SEE PLANS AND SEC. 2405.2 SBC 1997. | | | 6-SPECIFY MINIMUM BEARING SIZE REQUIRED | | | AT THE ENDS OF LINTELS. | | | -SEE OPENING SIZES & LINTELS SPECIFIED. | | | REVISE AS REQUIRED. | | | 7-PROVIDE COMPLETE SECTION/DETAILS AND | | | SPECS FOR CONNECTION OF LINTEL TO | | | CONCRETE BLOCK COLUMNS AT REAR PORCH. | | | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 | | | 8-PROVIDE COMPLETE DETAILS/SPECS FOR | | | CONNECTION OF 2X WOOD BEAM TO CONCRETE | | | COLUMNS & TO TIE BEAM AT ENTRY PORCH. | | | NOTE: ENTRY SECTION IN PAGE 6 OF 6 IS | | | MISSING SOME INFORMATION. SEE COMMENTS | | | 9-SPECIFY CEILING CONSTRUCTION AT ENTRY | | | AND REAR PORCH. SPECIFY ALL MATERIALS | | | AND FASTENERS AS REQUIRED BY ASTM | | | C1063 AND ASTM C926. SEE SECTION | | | 2504.2 SBC 1997. | | | 10-SPECIFY ROOF SHEATHING FASTENINGS | | | TYPE AND SPACING. SEE TABLE 2306.1OF | | | CITY AMENDMENTS TO SBC 1997. | | | 11-SPECIFY SIZE OF SCREEN VENTS THAT | | | COMPLY WITH SEC. 2309.7 SBC 1997. | | | 12-COMPLETE INFORMATION ON TOP OF DESIGN | | | CERTIFICATION FOR BUILDING CODE COM- | | | PLIANCE FORM. ALSO, USE LEGIBLE FORM. | | | 13-SPECIFY THE DESIGN PRESSURES THAT | | | WERE CALCULATED AT EACH EXTERIOR OPN'G | | | FOR COMPONENTS AND CLADDING. SEE SEC. | | | 1606 SBC 1997. | | | 14-PROVIDE PRODUCT APPROVAL FOR: | | | A)ENTRY DOORS WITH TRANSOM ABOVE SINGLE | | | ASSEMBLY AS SHOWN ON PLANS. | | | B)SINGLE HUNG WINDOWS PRODUCT APPROVAL | | | EXPIRED AND NEED APPROVED DRAWINGS. | | | C)SLIDING GLASS DOORS NEED THE APPROVED | | | DRAWINGS. | | | | | | 15-REVISE ENERGY CALCULATIONS: | | | A)USE FORM 600 A-97. | | | B)FILL TOP OF FORM. | | | C)OWNER OR AGENT TO SIGN AND DATE THE | | | BOTTOM OF FORM. | | | | | | 16-PROVIDE PRODUCT APPROVAL AND COMPLETE | | | INFORMATION FOR STORM SHUTTERS AS | | | REQUIRED. SEE PROCEDURE AND SAMPLE FOR | | | STORM SHUTTERS ATTACHED. | | | NOTE: IF INFORMATION IS INCOMPLETE, | | | THEN CONTRACTOR MAY APPLY FOR SEPARATE | | | PERMIT. | | | 17-SEE PLANS FOR ADDITIONAL COMMENTS. | | | INCLUDING COMMENTS BY OTHER TRADES. | | | PLEASE, RETURN REVIEWED SET AFTER | | | CORRECTIONS ARE DONE TO ORIGINAL DWGS | | | IN ORDER TO EXPEDITE THE REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-07-29 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-07-29 |
Time |
11:13 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-11-29 |
Time |
15:16 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|