Plan Review Details - Permit 01110923
Plan Review Stops For Permit 01110923
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-27 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2002-03-27 Time 07:46 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 11:14 Sent To  
Notes
2002-02-04 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NOTE #3 FROM
 FIRST REVIEW NEEDS TO BE SUBMITTED.
 PLEASE SUBMIT AIC RATING(S) FOR ALL
 NEW SERVICE EQUIPMENT. 110-9/215-5
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 06:24 Rev Time 0.00
Received By dpalmer Date 2001-12-11 Time 06:24 Sent To  
Notes
2001-12-11 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS THAT ARE
 SIGNED, DATED AND SEALED BY AN ENGINEER
 MUST HAVE A TITLE BLOCK, PER61G15-23.002
 OF FAC/FS.
  
 2)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 RISER DIAGRAM ON 6OF6 NEEDS TO BE ON THE
 ELECTRICAL PLAN.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 PLEASE NOTE THAT NOTE SAYS GROUND ROD
 DRIVEN 6', PLEASE SEE NEC FOR MIN BURIAL
 DEPTH.
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE CLARIFY IF IT IS AN OUTLET SHOWN
 FOR WALL IN FAMILY ROOM?
  
 8) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC. MISSING FRONT REC
  
 9) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 10)NOTE: PLEASE NOTE MISSING COND UNIT
 FOR A/C AND DISC PER 440-11.
  
 11)NOTE: PLEASE NOTE OUTLETS SHOWN IN
 GARAGE NEED TO BE SHOWN AS GFI/GFI
 PROTECTED ALONG WITH ALL OUTSIDE OUTLETS
 (BACK PORCH). PER 210-8.
  
 12)PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE SEE BATHROOM BETWEEN BEDROM 2-3,
 PLEASE NOTE TWO RECEPTS SHOWN???
 NO LIGHT OR LIGHT SWITCH. PLEASE CORRECT
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 12:56 Rev Time 0.40
Received By pkrauss Date 2002-04-23 Time 12:56 Sent To R
Notes
2002-04-23 00:00:00PROVISO:
  
 PLANS INDICATE 1500 CFM & MANUAL J
 INDICATES 1263 CFM.PLEASE PROVIDE
 MANUFACTURER INFORMATION FOR THE
 EQUIPMENT PRIOR TO FINAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-03-27 Cont ID  
Sent By pkrauss Date 2002-03-27 Time 14:04 Rev Time 0.35
Received By pkrauss Date 2002-03-27 Time 14:04 Sent To P
Notes
2002-03-27 00:00:00 
 COMMENTS FROM PREVIOUS REVIEW NEVER
 ADDRESSED.
  
 ONLY ONE SET OF MANUAL J CALCS SUBMITTED
  
 PLANS INDICATE 1500 CFM DISTRIBUTION,
 PLEASE SUBMIT MANUFACTURER SUBMITTAL
 DATA FOR EQUIPMENT SHOWING 3 TON SYSTEM
 WITH CAPACITY FOR 1500 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-11 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 07:46 Rev Time 0.45
Received By pkrauss Date 2002-02-11 Time 07:43 Sent To R
Notes
2002-02-11 00:00:00 
 *******************DENIED***************
  
  
 CFM DISTRIBUTION ON PLAN SHEET 5 OF
 6 INDICATES 1500 CFM.MANUAL J
 CALCULATIONS INDICATE 1248 FOR A 3
 TON UNIT.PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE 3 TON UNIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status R Date 2001-12-10 Cont ID  
Sent By hmoser Date 2001-12-10 Time 17:53 Rev Time 0.33
Received By hmoser Date 2001-12-10 Time 17:53 Sent To  
Notes
2001-12-10 00:00:00PERMIT WILL BE REQUIRED FOR THIS WORK
 PLANS AND FEES REQUIRED AT TIME OF
 PERMIT APPLICATION BY AIRCONDITIONING
 CONTRACTOR12/10/01H.M.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-10 Cont ID  
Sent By kstevens Date 2002-04-10 Time 19:38 Rev Time 0.00
Received By kstevens Date 2002-04-10 Time 19:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-10 Cont ID  
Sent By pkrauss Date 2002-03-27 Time 14:17 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-10 00:00:00PLUMBING PLAN REVIEW,DENIEDPES
 IOMETRIC DOES NOT MATCH FLOOR PLAN,
 ALSO 2 PLUMBING FIXTURES IN MASTER BATH
 MISSING,SPC-94SEC 104. 3
 PAUL SCHMITZ561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-07 Cont ID  
Sent By kstevens Date 2001-12-07 Time 16:22 Rev Time 0.33
Received By kstevens Date 2001-12-07 Time 16:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2002-08-16 Cont ID  
Sent By rmcdouga Date 2002-08-16 Time 18:47 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-16 00:00:00SOIL REPORT, DOOR PRODUCT APPROVAL AND
 REVISION TO SUPPORT W.W.M. FROM ENGINEER
 AS REQUESTED IN PROVISO. 8-16-02 RM

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-04-24 Cont ID  
Sent By jgomez Date 2002-04-24 Time 10:48 Rev Time 2.50
Received By jgomez Date 2002-04-24 Time 10:47 Sent To  
Notes
2002-04-24 00:00:00APPROVED WITH PROVISO:
 1-ENGINEER OF RECORD TO PROVIDE 2X
 STRUCTURAL BUCK DETAIL FOR ENTRY DOORS
 AS REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED.
 2-PROVIDE SLIDING GLASS DOORS APPROVED
 DRAWINGS. PRODUCT APPROVAL SUBMITTED
 IS MISSING THIS INFORMATION.
 3-PROVIDE APPROVED DRAWINGS FOR SINGLE
 HUNG WINDOWS. PRODUCT APPROVAL IS
 MISSING THIS INFORMATION.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-04-15 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 13:04 Rev Time 2.50
Received By jgomez Date 2002-04-15 Time 13:42 Sent To  
Notes
2002-04-15 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING PAID RECEIPT AND STAMPED DWGS.
 3-PROVIDE PRODUCT APPROVAL FOR:
 A)DOUBLE ENTRY DOORS.
 B)SINGLE HUNG WINDOWS PRODUCT APPROVAL
 IS EXPIRED AND NEED THE APPROVED DWGS.
 C)SLIDING GLASS DOORS PRODUCT APPROVAL
 NEED THE APPROVED DRAWINGS.
 D)WINDOW MULLIONS.
 4-ENERGY CALCULATIONS:
 OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS AT BOTTOM OF FORM.
 5-PROVIDE SBCCI OR DADE COUNTY PRODUCT
 APPROVAL AND COMPLETE INFORMATION FOR
 STORM SHUTTERS: KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. AND, CLEARLY
 INDICATE ON DRAWINGS SPECIFIC MOUNTING
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE, CONNECTION TYPE & STRUCTURE
 TO BE ATTACHED TO (MASONRY).

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-02-19 Cont ID  
Sent By jgomez Date 2002-02-19 Time 19:51 Rev Time 2.50
Received By jgomez Date 2002-02-19 Time 19:51 Sent To  
Notes
2002-02-19 00:00:00SECOND CHECKLIST:
 1-MOST OF THE ITEMS REQUESTED ON FIRST
 CHECKLIST WERE NOT ADDRESSED.
 **SEE PREVIOUS CHECKLIST ATTACHED.
 2-AREA CALCULATIONS DON'T ADD UP.
 3-CLARIFY SECTION DETAIL AT ENTRY PORCH.
 HOW ARE ROOF TRUSSES EMBEDED INTO THE
 MASONRY WALL SEE COMMENTS ON DWG.
 4-UPDATE TRUSS ANCHOR SCHEDULE & SECTION
 DETAILS WHEN SPECIFYING SIMPSOM ETA
 CONNECTORS. THEY ARE NOT LONGER LISTED
 ON SIMPSON CATALOGUES.
 5-PLEASE PAY ATTACHED RECEIPT FOR BLDG
 UPDATED VALUE & RADON FEES ($535.38)
 AND BRING BACK COPY OF PAID RECEIPT.
 **NOTE: ADDITIONAL FEES WILL BE CHARGED
 FOR RE-SUBMITTALS. SEE ATTACHED FORM.
 6-ENGINEER OF RECORD TO CLEARLY INDICATE
 ON LINTEL PRODUCT APPROVAL DRAWINGS
 THE COMPONENTS THAT ARE GOING TO BE
 USED IN THIS PROJECT AS REQUIRED ON
 BUILDING PERMIT REQUIREMENTS ON SHEET
 2 OF PRODUCT APPROVAL.
 7-SEE COMMENTS BY THE OTHER TRADES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-01-09 Cont ID  
Sent By pkrauss Date 2002-02-11 Time 08:50 Rev Time 3.50
Received By jgomez Date 2002-01-09 Time 13:59 Sent To  
Notes
2002-01-09 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT.
 2-AFTER ORIGINAL DRAWINGS ARE REVISED,
 BRING THEM TO PALM BEACH COUNTY TO PAY
 IMPACT FEES. BRING PAID RECEIPT AND
 STAMPED DRAWINGS.
 3-PROFESSIONAL ENGINEER OF RECORD TO
 HAVE ALL HIS INFORMATION ON ALL DWGS
 AS REQ'D BY CHAPTER 471 FL. STATUTES.
 -ENG'R TO DATE DWGS AT TIME OF SEALING.
 4-PROVIDE AREA CALCULATIONS FOR A/C AND
 NON A/C AREAS TO DETERMINE RADON FEES
 AND VALUATION.
 5-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 6-SPECIFY MINIMUM BEARING SIZE REQUIRED
 AT THE ENDS OF LINTELS.
 -SEE OPENING SIZES & LINTELS SPECIFIED.
 REVISE AS REQUIRED.
 7-PROVIDE COMPLETE SECTION/DETAILS AND
 SPECS FOR CONNECTION OF LINTEL TO
 CONCRETE BLOCK COLUMNS AT REAR PORCH.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 8-PROVIDE COMPLETE DETAILS/SPECS FOR
 CONNECTION OF 2X WOOD BEAM TO CONCRETE
 COLUMNS & TO TIE BEAM AT ENTRY PORCH.
 NOTE: ENTRY SECTION IN PAGE 6 OF 6 IS
 MISSING SOME INFORMATION. SEE COMMENTS
 9-SPECIFY CEILING CONSTRUCTION AT ENTRY
 AND REAR PORCH. SPECIFY ALL MATERIALS
 AND FASTENERS AS REQUIRED BY ASTM
 C1063 AND ASTM C926. SEE SECTION
 2504.2 SBC 1997.
 10-SPECIFY ROOF SHEATHING FASTENINGS
 TYPE AND SPACING. SEE TABLE 2306.1OF
 CITY AMENDMENTS TO SBC 1997.
 11-SPECIFY SIZE OF SCREEN VENTS THAT
 COMPLY WITH SEC. 2309.7 SBC 1997.
 12-COMPLETE INFORMATION ON TOP OF DESIGN
 CERTIFICATION FOR BUILDING CODE COM-
 PLIANCE FORM. ALSO, USE LEGIBLE FORM.
 13-SPECIFY THE DESIGN PRESSURES THAT
 WERE CALCULATED AT EACH EXTERIOR OPN'G
 FOR COMPONENTS AND CLADDING. SEE SEC.
 1606 SBC 1997.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS PRODUCT APPROVAL
 EXPIRED AND NEED APPROVED DRAWINGS.
 C)SLIDING GLASS DOORS NEED THE APPROVED
 DRAWINGS.
  
 15-REVISE ENERGY CALCULATIONS:
 A)USE FORM 600 A-97.
 B)FILL TOP OF FORM.
 C)OWNER OR AGENT TO SIGN AND DATE THE
 BOTTOM OF FORM.
  
 16-PROVIDE PRODUCT APPROVAL AND COMPLETE
 INFORMATION FOR STORM SHUTTERS AS
 REQUIRED. SEE PROCEDURE AND SAMPLE FOR
 STORM SHUTTERS ATTACHED.
 NOTE: IF INFORMATION IS INCOMPLETE,
 THEN CONTRACTOR MAY APPLY FOR SEPARATE
 PERMIT.
 17-SEE PLANS FOR ADDITIONAL COMMENTS.
 INCLUDING COMMENTS BY OTHER TRADES.
 PLEASE, RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-07-29 Cont ID  
Sent By sgraham Date 2002-07-29 Time 11:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-29 Cont ID  
Sent By sgraham Date 2001-11-29 Time 15:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***