| Plan Review Stops For Permit 01110917 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-12-31 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-12-31 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2002-12-31 00:00:00 | AS-BUILT PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-10-29 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-10-29 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | THE FOLLOWING IS A REVIEW OF PLANS | | | SUBMITTED FOR 'AS-BUILT' CONDITION. | | | | | | 1) 61G15-23.002, F.A.C.STRUCTURAL PLAN | | | SHEETS S.01 THRU S.07 SHALL BE SEALED, | | | SIGNED AND DATED BY THE ENGINEER. | | | | | | 2) PLAN SHEETS A.04, A.08(DETAILS 2 & 4) | | | S.03, S.04, S.05, S.06, S.07 HAVE ALL | | | BEEN REVISED SINCE THE PERMIT APPROVED | | | PLANS (STAMPED 2-14-02) BUT THE REVISION | | | REFERENCE HAS NOT BEEN CHANGED TO SUIT. | | | ALL REVISIONS SHALL BE CLEARLY SHOWN AND | | | REFERENCED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-24 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-02-08 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | THE SUBMITTED NOTICE OF COMMENCEMENT | | | REFERS TO A PROPERTY CONTROL NUMBER(PCN) | | | WHICH IS NOT VALID.REVISE/RESUBMIT THE | | | NOTICE OF COMMENCEMENT, CORRECTED AS | | | APPROPRIATE, FOR THE RECORD. | | | | | | --PROVISO-- | | | SUBMIT PRODUCT APPROVALS FOR THE MCKEON | | | ROLLING STEEL DOORS AND FOR THE EXTERIOR | | | EXIT DOORS NUMBER 04 AND 06. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-01-25 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-01-25 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2002-01-25 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 12/20/01: | | | | | | 2) --PROVISO-- | | | CONTRARY TO THE REVIEW RESPONSE LETTER | | | DATED 1/14/02 NO NOTICE OF COMMENCEMENT | | | WAS "ATTACHED".A RECORDED COPY OF THE | | | NOTICE OF COMMENCEMENT MUST BE SUBMITTED | | | BEFORE A PERMIT CAN BE ISSUED. | | | | | | 3) --PROVISO-- | | | CONTRARY TO THE REVIEW RESPONSE LETTER | | | DATED 1/14/02 NO ROOF PERMIT APPLICATION | | | WAS "ATTACHED".A SEPARATE ROOFING | | | PERMIT IS REQUIRED (SBC* 104.1.1) | | | | | | 7) FL ACC CODE 4.8.5(2) THE RAMP | | | HANDRAILS SHALL EXTEND AT LEAST 18" | | | BEYOND THE SLOPED SEGMENT AT THE BASE OF | | | THE RAMP. | | | | | | 9) SBC* 1804.2.2CONTRARY TO THE REVIEW | | | RESPONSE LETTER DATED 1/14/02, NO | | | GEOTECHNICAL REPORT WAS "ATTACHED". | | | SUBMIT A COPY OF THE REPORT | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-12-20 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2001-12-20 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE | | | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | FL ENERGY CODE = FLORIDA ENERGY | | | EFFICIENCY CODE FOR BUILD'G CONSTR'N | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) SBC* 104.1.1THE PRIMARY PERMIT | | | APPLICATION SHOWS ROOFING AS BEING OFF | | | PERMIT.A SEPARATE ROOFING PERMIT IS | | | REQUIURED. | | | | | | 4) SBC 704.1.3.3SHEET A.01 FIRST | | | FLOOR PLAN SHOWS THE WALL BETWEEN THE | | | BOILER ROOM AND NEW STORAGE AREA AS 4 HR | | | RATED WITH A REFERENCE TO TYPE B.SHEET | | | A.07 WALL SCHEDULE, WHICH REFERS TO | | | TYPE B AS NON-RATED, SHOULD THEREFORE BE | | | AMENDED TO CONFIRM THE FIRE-RATED | | | CONSTRUCTION REQUIREMENT. | | | | | | 5) SBC 1503.1.2.3THE FLAT ROOF SLOPE | | | SHALL BE AT LEAST 1/2" PER FOOT.THE | | | ROOF LEVELS ON SECTION 1, SHEET A.05 | | | IMPLY A SHALLOWER SLOPE THAN THIS. | | | | | | 6) FL ACC CODE 4.8OUTDOOR PATIO DECK | | | RAMP SHALL HAVE A MAXIMUM SLOPE OF 1:12 | | | AND A MINIMUM WIDTH OF 36 INCHES. | | | ANNOTATE THE PLANS TO SHOW THESE | | | REQUIREMENTS. | | | | | | 7) FL ACC CODE 4.8.5THE RAMP SHALL | | | HAVE HANDRAILS ON BOTH SIDES WHICH MEET | | | THE REQUIREMENTS OF FL ACC CODE 4.8.5 | | | AND SBC 1608.2.1 | | | | | | 8) SBC 1608.2.2SUBMIT DETAILS TO | | | DEMONSTRATE COMPLIANCE WITH THE | | | REQUIREMENTS FOR THE DESIGN AND | | | CONSTRUCTION OF THE OUTDOOR PATIO DECK | | | GUARDRAILS. | | | | | | 9) SBC* 1804.2.2SUBMIT A COPY OF THE | | | GEOTECHNICAL REPORT. | | | | | | 10) SBC 1604.3WHAT ITEMS WILL BE | | | STORED?IF STORAGE RACKING IS TO BE | | | USED, THE FLOOR SLAB SHALL BE CHECKED | | | FOR PUNCHING SHEAR UNDER RESULTING | | | CONCENTRATED LOAD AT THE RACKING SUPPORT | | | | | | 11) SBC 1606.2STATE THE DESIGN WIND | | | PRESSURES AND SUBMIT DETAILS TO DESCRIBE | | | THE STRUCTURAL SYSTEM FOR TRANSFER OF | | | WIND LOADS TO THE FOUNDATIONS. | | | | | | 12) SBC 1608.1.1SUBMIT DETAILS TO | | | DEMONSTRATE THE LATERAL RESTRAINT OF THE | | | NEW RETAINING WALL WERE IT INTERSECTS | | | WITH THE EXISTING WALL (ADJACENT GRID | | | REF CC/17A). | | | | | | 13) PROVISO: FL ENERGY CODE 101.5.3IF | | | THE SPACE IS TO BE HEATED OR COOLED BY | | | MECHANICAL MEANS, CODE COMPLIANCE SHALL | | | BE DEMONSTRATED BY SUBMITTAL OF ENERGY | | | CODE COMPLIANCE FORMS (FL ENERGY CODE | | | 103.0). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-24 |
Time |
08:00 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-24 |
Time |
07:53 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-18 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-10-18 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2002-10-18 00:00:00 | *************** ON HOLD *************** | | | | | | WAITING FOR PAID BZ TO PROCESS PLANS. | | | PLEASE NOTE , BZ TO BE PAID AT TIME | | | OF SUBMITTAL. | | | SUBJECT TO 4X FEE PER CITY-WIDE | | | ADMINISTRATIVE CODE. SEC 104 | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-04 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-04 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
21:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-05 |
Time |
21:36 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE ADDRESS FIRE COMMENTS | | | FOR USE OF STORAGE. | | | | | | NOTE;PLEASE NEED CLARIFICATION ON THE | | | FOLLOWING ITEMS. | | | | | | 2)NOTE: PLEASE NOTE THAT GENERATOR | | | ENCLOSURE ON E.01 APPEARS TO BE IN AN | | | ENCLOSED ROOM??? PLEASE SEE INSIDE | | | LIGHTING ,EM LT, RECEPT?? PLEASE NOTE | | | THAT ON SHEET E.02, IT APPEARS TO BE | | | IN A FENCED IN AREA? PLEASE NOTE THAT | | | ALL CIRCUITS NEED TO HAVE A MEANS OF | | | DISCONNECT FOR DETACHED STRUCTURE PER | | | 225-31. GROUNDING PER 250-32 | | | | | | 3)NOTE: PLEASE SHOW GROUNDING OF NEW | | | TRANSFORMER, 250-30 | | | | | | 4)NOTE: PLEASE NOTE THAT SHEET E.01 | | | SHOWS FEED COMING FROM BRKR ON GEN. AND | | | SHOWS A CIRCLE W/ "G-1" PLEASE CLARIFY | | | THIS?? | | | | | | 5)NOTE: PLEASE NOTE THAT SHEET C.01 | | | SHOWS A "NEW" GENERATOR AND E-SHEETS | | | DO NOT SHOW ANY DETAIL FOR THIS? GEN, | | | SIZE, WIRING,CONDUITS WHERE,WHAT, LOAD? | | | ALL EXSITING??? PLEASE CLARFIY. | | | | | | 6)NOTE: PLEASE NOTE THAT "DP-1" SHOWN | | | AS "DIST PANEL"? IS THERE ANY OTHER | | | LOADS? EXISTING? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-27 |
Time |
10:56 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-11-27 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2003-01-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-03 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-03 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-11-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-11-06 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-06 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2002-11-06 00:00:00 | 1) PLEASE INDICATE HOW THE SECURITY DOOR | | | OPERATE. | | | | | | 2) ARE THESE DOORS DELAYED-EGRESS | | | LOCKING DEVICES, IF SO DOES IT COMPLY | | | WITH CH.7.2.1.6.1, NFPA 101 2000. | | | | | | 3) ARE THESE DOORS ACESS-CONTROLLED | | | EGRESS, IF SO DOES IT COMPLY WITH | | | CH.7.2.1.6.2, NFPA 101 2000. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-29 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-29 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2002-01-29 00:00:00 | 1) NO ACETYLENE IS TO BE STORED IN THE | | | BUILDING. | | | 2) NEW STAIRS TO COMPLY WITH NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-26 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-26 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | 1) WHAT WILL BE STORED IN THE PROPOSED | | | STORAGE ADDITION. ARE ANY HAZARDOUS | | | CHEMICALS, OR FLAMMABLE LIQUIDS PLANNED | | | FOR THIS LOCALE. | | | 2) ONE TREAD AND TWO RISERS SHOWN TO | | | ACCESS THE OUTDOOR PATO DECK. ANY | | | CHANGES IN ELEVATION LESS THAN 21" | | | SHALL BE BY RAMPS. STEPS WHEN PROVIDED | | | SHALL CONTAIN AT LEAST THREE. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER PROTECTION PLANNED | | | FOR THE STORAGE AREA AND ADDITION. | | | 4) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE ALARM EQUIPMENT PLANNED | | | FOR STORAGE AREA AND BOLIER ROOM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
16:51 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | MANUFACT. INFO REQUIRED SHALL BE SUBMIT- | | | TED ON GAS PERMIT #02020471 | | | REGULATOR INFORMATION WILL BE SUBMITTED | | | THEN ALSO. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-29 |
Time |
08:15 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-10-28 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | AS BUILT DWGS FOR THE BOILER IN-LINE | | | PUMPS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-02-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-05 |
Time |
15:18 |
Rev Time |
1.40 |
| Received By |
pkrauss |
Date |
2002-02-05 |
Time |
12:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-10 |
Time |
09:12 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-12-10 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | ********************DENIED************** | | | | | | | | | CLARIFY WHAT IS BEING SUBMITTED WITH | | | THIS PERMIT APPLICATION. | | | | | | 1.MECHANICAL PLANS ARE FOR THE BOILER | | | ROOM.PLEASE PROVIDE CALCULATIONS | | | FOR COMBUSTION AIR. | | | | | | 2.STORAGE ROOM ADDITION. | | | | | | A. WHAT IS BEING "STORED" IN THIS | | | AREA? | | | B. PROVIDE AIR BALANCE SCHEDULE | | | SHOWING COMPLIANCE WITH 1997 SMC | | | 501.2. | | | | | | 3.PLAN SHEET M.03 EF-3, CLARIFY SHAFT, | | | DOES THIS HAVE A FIRE RATING?WHAT | | | IS THE RATING OF THE WALL SEPARATING | | | THE STORAGE AREA FROM THE EXISTING | | | BUILDING? | | | | | | 4.BOILER ROOM, WHAT IS THE FIRE | | | RATING OF THIS ROOM?PLEASE NOTE | | | THERE ARE NO FIRE DAMPERS INDICATED | | | ON DUCTS PENETRATING THE WALL | | | BETWEEN THE BOILER ROOM AND THE | | | EXISTING BUILDING. | | | | | | IF YOU HAVE ANYQUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-05 |
Time |
14:40 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-11-05 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2002-11-05 00:00:00 | AS BUILT REVISIONS OK - SHTS P.01, P.02, | | | P.03 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
17:00 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
17:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-04 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-02-02 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2002-02-04 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW. - FOLLOWING IN- | | | FORMATION REQUIRED FOR GAS PERMIT. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER STANDARD | | | GAS CODE. | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER THE STANDARD GAS | | | CODE SECS. 402.4 THRU 402.4.4.7. | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER STANDARD GAS CODE SEC. 305.2. IF | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | STANDARD GAS CODE SEC. 402. | | | -- ALSO A SHUT OFF VALVE AND UNION ARE | | | REQUIRED UPSTREAM OF ALL REGULATORS.- | | | | | | 2) FROM PREVIOUS REVIEW. SHT P.03, WATER | | | PIPING ISOMETRIC, POOL MAKE UP WATER TO | | | HAVE AN AIR GAP, WATTS N36 VACUUM BREAK- | | | ER, OR AN RPZ BACKFLOW. PLUMBER TO PROV- | | | IDE FOR POOL CONTRACTOR. PLEASE PROVIDE | | | DETAILS FOR PROTECTION OF POTABLE WATER. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-04 |
Time |
10:52 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2001-12-04 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SEPARATE GAS PERMIT REQUIRED. SEE | | | ATTACHED SHEET FOR PERMIT APPLICATION | | | REQUIREMENTS. PLEASE RESPOND TO #'S 1, | | | 6, 7, & 9. | | | 2) SHT P.03 GAS PIPING ISOMETRIC, TOTAL | | | BTU'S ADD UP TO 6,225,000. 7,225,000 IS | | | SHOW, PLEASE CLAIRFY. | | | 3) SHT P.03, WATER PIPING ISOMETRIC, | | | POOL MAKE UP WATER TO HAVE AN AIR GAP, | | | OR A WATTS N36 VACUUM BREAKER. PLEASE | | | SHOW DETAILS. - ALL WATER HAMMER ARRES- | | | TORS SHALL BE LOCATED IN AN EFFECTIVE | | | RANGE, (CLOSE TO), FIXTURE NOT AT TOP OF | | | DROP AS SHOWN AT POOL MAKE UP WATER. | | | 4) SHT P.01 COLUMN LINE BB/14A, WHAT ARE | | | THE (2) 2" CAPPED LINES FOR? | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-13 |
Time |
13:12 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-01-24 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | INFORMAL SITE PLAN STILL PENDING | | | 01-24-02 SG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-12-19 |
Time |
14:24 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|