Plan Review Details - Permit 01110917
Plan Review Stops For Permit 01110917
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-12-31 Cont ID  
Sent By rbrown Date 2002-12-31 Time 11:56 Rev Time 0.00
Received By rbrown Date 2002-12-31 Time 11:55 Sent To  
Notes
2002-12-31 00:00:00AS-BUILT PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-10-29 Cont ID  
Sent By rbrown Date 2002-10-29 Time 15:39 Rev Time 0.00
Received By rbrown Date 2002-10-29 Time 15:39 Sent To  
Notes
2002-10-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 THE FOLLOWING IS A REVIEW OF PLANS
 SUBMITTED FOR 'AS-BUILT' CONDITION.
  
 1) 61G15-23.002, F.A.C.STRUCTURAL PLAN
 SHEETS S.01 THRU S.07 SHALL BE SEALED,
 SIGNED AND DATED BY THE ENGINEER.
  
 2) PLAN SHEETS A.04, A.08(DETAILS 2 & 4)
 S.03, S.04, S.05, S.06, S.07 HAVE ALL
 BEEN REVISED SINCE THE PERMIT APPROVED
 PLANS (STAMPED 2-14-02) BUT THE REVISION
 REFERENCE HAS NOT BEEN CHANGED TO SUIT.
 ALL REVISIONS SHALL BE CLEARLY SHOWN AND
 REFERENCED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-02-08 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 08:00 Rev Time 0.00
Received By rbrown Date 2002-02-08 Time 18:48 Sent To  
Notes
2002-02-08 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE SUBMITTED NOTICE OF COMMENCEMENT
 REFERS TO A PROPERTY CONTROL NUMBER(PCN)
 WHICH IS NOT VALID.REVISE/RESUBMIT THE
 NOTICE OF COMMENCEMENT, CORRECTED AS
 APPROPRIATE, FOR THE RECORD.
  
 --PROVISO--
 SUBMIT PRODUCT APPROVALS FOR THE MCKEON
 ROLLING STEEL DOORS AND FOR THE EXTERIOR
 EXIT DOORS NUMBER 04 AND 06.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-25 Cont ID  
Sent By rbrown Date 2002-01-25 Time 15:52 Rev Time 0.00
Received By rbrown Date 2002-01-25 Time 15:51 Sent To  
Notes
2002-01-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/20/01:
  
 2) --PROVISO--
 CONTRARY TO THE REVIEW RESPONSE LETTER
 DATED 1/14/02 NO NOTICE OF COMMENCEMENT
 WAS "ATTACHED".A RECORDED COPY OF THE
 NOTICE OF COMMENCEMENT MUST BE SUBMITTED
 BEFORE A PERMIT CAN BE ISSUED.
  
 3) --PROVISO--
 CONTRARY TO THE REVIEW RESPONSE LETTER
 DATED 1/14/02 NO ROOF PERMIT APPLICATION
 WAS "ATTACHED".A SEPARATE ROOFING
 PERMIT IS REQUIRED (SBC* 104.1.1)
  
 7) FL ACC CODE 4.8.5(2) THE RAMP
 HANDRAILS SHALL EXTEND AT LEAST 18"
 BEYOND THE SLOPED SEGMENT AT THE BASE OF
 THE RAMP.
  
 9) SBC* 1804.2.2CONTRARY TO THE REVIEW
 RESPONSE LETTER DATED 1/14/02, NO
 GEOTECHNICAL REPORT WAS "ATTACHED".
 SUBMIT A COPY OF THE REPORT
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-20 Cont ID  
Sent By rbrown Date 2001-12-20 Time 16:33 Rev Time 0.00
Received By rbrown Date 2001-12-20 Time 16:33 Sent To  
Notes
2001-12-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SBC* 104.1.1THE PRIMARY PERMIT
 APPLICATION SHOWS ROOFING AS BEING OFF
 PERMIT.A SEPARATE ROOFING PERMIT IS
 REQUIURED.
  
 4) SBC 704.1.3.3SHEET A.01 FIRST
 FLOOR PLAN SHOWS THE WALL BETWEEN THE
 BOILER ROOM AND NEW STORAGE AREA AS 4 HR
 RATED WITH A REFERENCE TO TYPE B.SHEET
 A.07 WALL SCHEDULE, WHICH REFERS TO
 TYPE B AS NON-RATED, SHOULD THEREFORE BE
 AMENDED TO CONFIRM THE FIRE-RATED
 CONSTRUCTION REQUIREMENT.
  
 5) SBC 1503.1.2.3THE FLAT ROOF SLOPE
 SHALL BE AT LEAST 1/2" PER FOOT.THE
 ROOF LEVELS ON SECTION 1, SHEET A.05
 IMPLY A SHALLOWER SLOPE THAN THIS.
  
 6) FL ACC CODE 4.8OUTDOOR PATIO DECK
 RAMP SHALL HAVE A MAXIMUM SLOPE OF 1:12
 AND A MINIMUM WIDTH OF 36 INCHES.
 ANNOTATE THE PLANS TO SHOW THESE
 REQUIREMENTS.
  
 7) FL ACC CODE 4.8.5THE RAMP SHALL
 HAVE HANDRAILS ON BOTH SIDES WHICH MEET
 THE REQUIREMENTS OF FL ACC CODE 4.8.5
 AND SBC 1608.2.1
  
 8) SBC 1608.2.2SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR THE DESIGN AND
 CONSTRUCTION OF THE OUTDOOR PATIO DECK
 GUARDRAILS.
  
 9) SBC* 1804.2.2SUBMIT A COPY OF THE
 GEOTECHNICAL REPORT.
  
 10) SBC 1604.3WHAT ITEMS WILL BE
 STORED?IF STORAGE RACKING IS TO BE
 USED, THE FLOOR SLAB SHALL BE CHECKED
 FOR PUNCHING SHEAR UNDER RESULTING
 CONCENTRATED LOAD AT THE RACKING SUPPORT
  
 11) SBC 1606.2STATE THE DESIGN WIND
 PRESSURES AND SUBMIT DETAILS TO DESCRIBE
 THE STRUCTURAL SYSTEM FOR TRANSFER OF
 WIND LOADS TO THE FOUNDATIONS.
  
 12) SBC 1608.1.1SUBMIT DETAILS TO
 DEMONSTRATE THE LATERAL RESTRAINT OF THE
 NEW RETAINING WALL WERE IT INTERSECTS
 WITH THE EXISTING WALL (ADJACENT GRID
 REF CC/17A).
  
 13) PROVISO: FL ENERGY CODE 101.5.3IF
 THE SPACE IS TO BE HEATED OR COOLED BY
 MECHANICAL MEANS, CODE COMPLIANCE SHALL
 BE DEMONSTRATED BY SUBMITTAL OF ENERGY
 CODE COMPLIANCE FORMS (FL ENERGY CODE
 103.0).

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-10-24 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 08:00 Rev Time 0.50
Received By dpalmer Date 2002-10-24 Time 07:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-10-18 Cont ID  
Sent By dpalmer Date 2002-10-18 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2002-10-18 Time 07:28 Sent To  
Notes
2002-10-18 00:00:00*************** ON HOLD ***************
  
 WAITING FOR PAID BZ TO PROCESS PLANS.
 PLEASE NOTE , BZ TO BE PAID AT TIME
 OF SUBMITTAL.
 SUBJECT TO 4X FEE PER CITY-WIDE
 ADMINISTRATIVE CODE. SEC 104
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 16:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 21:51 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 21:36 Sent To  
Notes
2001-12-05 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE ADDRESS FIRE COMMENTS
 FOR USE OF STORAGE.
  
 NOTE;PLEASE NEED CLARIFICATION ON THE
 FOLLOWING ITEMS.
  
 2)NOTE: PLEASE NOTE THAT GENERATOR
 ENCLOSURE ON E.01 APPEARS TO BE IN AN
 ENCLOSED ROOM??? PLEASE SEE INSIDE
 LIGHTING ,EM LT, RECEPT?? PLEASE NOTE
 THAT ON SHEET E.02, IT APPEARS TO BE
 IN A FENCED IN AREA? PLEASE NOTE THAT
 ALL CIRCUITS NEED TO HAVE A MEANS OF
 DISCONNECT FOR DETACHED STRUCTURE PER
 225-31. GROUNDING PER 250-32
  
 3)NOTE: PLEASE SHOW GROUNDING OF NEW
 TRANSFORMER, 250-30
  
 4)NOTE: PLEASE NOTE THAT SHEET E.01
 SHOWS FEED COMING FROM BRKR ON GEN. AND
 SHOWS A CIRCLE W/ "G-1" PLEASE CLARIFY
 THIS??
  
 5)NOTE: PLEASE NOTE THAT SHEET C.01
 SHOWS A "NEW" GENERATOR AND E-SHEETS
 DO NOT SHOW ANY DETAIL FOR THIS? GEN,
 SIZE, WIRING,CONDUITS WHERE,WHAT, LOAD?
 ALL EXSITING??? PLEASE CLARFIY.
  
 6)NOTE: PLEASE NOTE THAT "DP-1" SHOWN
 AS "DIST PANEL"? IS THERE ANY OTHER
 LOADS? EXISTING?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-11-27 Cont ID  
Sent By mamini Date 2001-11-27 Time 10:56 Rev Time 1.00
Received By mamini Date 2001-11-27 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-01-03 Cont ID  
Sent By mcarsill Date 2003-01-03 Time 09:53 Rev Time 0.00
Received By mcarsill Date 2003-01-03 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-11-06 Cont ID  
Sent By mcarsill Date 2002-11-06 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2002-11-06 Time 14:37 Sent To  
Notes
2002-11-06 00:00:001) PLEASE INDICATE HOW THE SECURITY DOOR
 OPERATE.
  
 2) ARE THESE DOORS DELAYED-EGRESS
 LOCKING DEVICES, IF SO DOES IT COMPLY
 WITH CH.7.2.1.6.1, NFPA 101 2000.
  
 3) ARE THESE DOORS ACESS-CONTROLLED
 EGRESS, IF SO DOES IT COMPLY WITH
 CH.7.2.1.6.2, NFPA 101 2000.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By mcarsill Date 2002-01-29 Time 13:10 Rev Time 0.00
Received By mcarsill Date 2002-01-29 Time 13:07 Sent To  
Notes
2002-01-29 00:00:001) NO ACETYLENE IS TO BE STORED IN THE
 BUILDING.
 2) NEW STAIRS TO COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 13:20 Sent To  
Notes
2001-11-26 00:00:001) WHAT WILL BE STORED IN THE PROPOSED
 STORAGE ADDITION. ARE ANY HAZARDOUS
 CHEMICALS, OR FLAMMABLE LIQUIDS PLANNED
 FOR THIS LOCALE.
 2) ONE TREAD AND TWO RISERS SHOWN TO
 ACCESS THE OUTDOOR PATO DECK. ANY
 CHANGES IN ELEVATION LESS THAN 21"
 SHALL BE BY RAMPS. STEPS WHEN PROVIDED
 SHALL CONTAIN AT LEAST THREE.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER PROTECTION PLANNED
 FOR THE STORAGE AREA AND ADDITION.
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM EQUIPMENT PLANNED
 FOR STORAGE AREA AND BOLIER ROOM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 16:51 Rev Time 1.25
Received By kstevens Date 2002-02-08 Time 16:50 Sent To  
Notes
2002-02-08 00:00:00MANUFACT. INFO REQUIRED SHALL BE SUBMIT-
 TED ON GAS PERMIT #02020471
 REGULATOR INFORMATION WILL BE SUBMITTED
 THEN ALSO.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 08:15 Rev Time 0.50
Received By pkrauss Date 2002-10-28 Time 16:47 Sent To  
Notes
2002-10-29 00:00:00AS BUILT DWGS FOR THE BOILER IN-LINE
 PUMPS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-05 Cont ID  
Sent By pkrauss Date 2002-02-05 Time 15:18 Rev Time 1.40
Received By pkrauss Date 2002-02-05 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-10 Cont ID  
Sent By pkrauss Date 2001-12-10 Time 09:12 Rev Time 1.00
Received By pkrauss Date 2001-12-10 Time 09:04 Sent To  
Notes
2001-12-10 00:00:00********************DENIED**************
  
  
 CLARIFY WHAT IS BEING SUBMITTED WITH
 THIS PERMIT APPLICATION.
  
 1.MECHANICAL PLANS ARE FOR THE BOILER
 ROOM.PLEASE PROVIDE CALCULATIONS
 FOR COMBUSTION AIR.
  
 2.STORAGE ROOM ADDITION.
  
 A. WHAT IS BEING "STORED" IN THIS
 AREA?
 B. PROVIDE AIR BALANCE SCHEDULE
 SHOWING COMPLIANCE WITH 1997 SMC
 501.2.
  
 3.PLAN SHEET M.03 EF-3, CLARIFY SHAFT,
 DOES THIS HAVE A FIRE RATING?WHAT
 IS THE RATING OF THE WALL SEPARATING
 THE STORAGE AREA FROM THE EXISTING
 BUILDING?
  
 4.BOILER ROOM, WHAT IS THE FIRE
 RATING OF THIS ROOM?PLEASE NOTE
 THERE ARE NO FIRE DAMPERS INDICATED
 ON DUCTS PENETRATING THE WALL
 BETWEEN THE BOILER ROOM AND THE
 EXISTING BUILDING.
  
 IF YOU HAVE ANYQUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 14:40 Rev Time 1.25
Received By kstevens Date 2002-11-05 Time 14:40 Sent To  
Notes
2002-11-05 00:00:00AS BUILT REVISIONS OK - SHTS P.01, P.02,
 P.03

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 17:00 Rev Time 1.50
Received By kstevens Date 2002-02-08 Time 17:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-04 Cont ID  
Sent By kstevens Date 2002-02-04 Time 09:36 Rev Time 0.00
Received By kstevens Date 2002-02-02 Time 15:12 Sent To  
Notes
2002-02-04 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) FROM PREVIOUS REVIEW. - FOLLOWING IN-
 FORMATION REQUIRED FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 -- ALSO A SHUT OFF VALVE AND UNION ARE
 REQUIRED UPSTREAM OF ALL REGULATORS.-
  
 2) FROM PREVIOUS REVIEW. SHT P.03, WATER
 PIPING ISOMETRIC, POOL MAKE UP WATER TO
 HAVE AN AIR GAP, WATTS N36 VACUUM BREAK-
 ER, OR AN RPZ BACKFLOW. PLUMBER TO PROV-
 IDE FOR POOL CONTRACTOR. PLEASE PROVIDE
 DETAILS FOR PROTECTION OF POTABLE WATER.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-12-04 Cont ID  
Sent By kstevens Date 2001-12-04 Time 10:52 Rev Time 3.00
Received By kstevens Date 2001-12-04 Time 10:52 Sent To  
Notes
2001-12-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED SHEET FOR PERMIT APPLICATION
 REQUIREMENTS. PLEASE RESPOND TO #'S 1,
 6, 7, & 9.
 2) SHT P.03 GAS PIPING ISOMETRIC, TOTAL
 BTU'S ADD UP TO 6,225,000. 7,225,000 IS
 SHOW, PLEASE CLAIRFY.
 3) SHT P.03, WATER PIPING ISOMETRIC,
 POOL MAKE UP WATER TO HAVE AN AIR GAP,
 OR A WATTS N36 VACUUM BREAKER. PLEASE
 SHOW DETAILS. - ALL WATER HAMMER ARRES-
 TORS SHALL BE LOCATED IN AN EFFECTIVE
 RANGE, (CLOSE TO), FIXTURE NOT AT TOP OF
 DROP AS SHOWN AT POOL MAKE UP WATER.
 4) SHT P.01 COLUMN LINE BB/14A, WHAT ARE
 THE (2) 2" CAPPED LINES FOR?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2002-02-13 Cont ID  
Sent By sgraham Date 2002-02-13 Time 13:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-01-24 Cont ID  
Sent By sgraham Date 2002-01-24 Time 14:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2002-01-24 00:00:00INFORMAL SITE PLAN STILL PENDING
 01-24-02 SG

Review Stop Z ZONING
Rev No 1 Status F Date 2001-12-19 Cont ID  
Sent By sgraham Date 2001-12-19 Time 14:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***