Plan Review Details - Permit 01110813
Plan Review Stops For Permit 01110813
Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-26 Cont ID  
Sent By pschmitz Date 2002-01-26 Time 15:41 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-26 00:00:00PLUMBING PLAN REVIEW,DENIED 2ND TIME.
 PLEASE ADDRESS PREVIOUS COMMENTS.
 RECOMMEND THAT YOU HIRE A LICENSED
 PLUMBING CONTRACTOR TO DRAW A PLUMBING
 ISOMETRIC THAT MEETS CODE AND MATCHES
 BUILDINGLAYOUT, ALSO TO INSTALL THE
 PLUMBING
 END OF COMMENTSPAUL SCHMITZ
 561 659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By kstevens Date 2001-11-26 Time 08:57 Rev Time 0.50
Received By kstevens Date 2001-11-26 Time 08:57 Sent To  
Notes
2001-11-26 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) ALL PLANS WITH A TITLE BLOCK SHALL BE
 SIGNED AND SEALED BY ENGINEER OF RECORD
 PER FS 61G15-23.002
 2) PAGE 1 OF 2 STATES THAT NO PLUMBING
 INCLUDED WITH THESE PLANS. PLEASE CLAIR-
 IFY.
 3) 2ND FLOOR RISER DIAGRAM NOT TO CODE
 BATH TUB NOT VENTED PROPERLY PER SPC SEC
 913.2
 4) 1ST FLOOR PLAN, WHAT FIXTURE IS BEING
 DRAINED AT WATER HEATER. MORE INFORMAT-
 ION REQUIRED.
 5) PAGE 1 0F 2, KITCHEN SINK NOT VENTED
 PROPERLY.
 6) PAGE 1 OF 2, FIXTURES NOT IDENTIFIED
 IN LAUNDRY ROOM. 1ST FIXTURE NOT VENTED
 PROPERLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377