Plan Review Details - Permit 01110797
Plan Review Stops For Permit 01110797
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-19 Cont ID  
Sent By rmcdouga Date 2001-12-19 Time 14:33 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-19 00:00:00OK PER D.PALMER 12-4-01 RM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 09:44 Rev Time 0.40
Received By pkrauss Date 2002-01-24 Time 09:43 Sent To R
Notes
2002-01-24 00:00:00MECHANICAL PERMIT 01110850

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-01 Cont ID  
Sent By hmoser Date 2001-12-01 Time 11:15 Rev Time 0.33
Received By hmoser Date 2001-12-01 Time 11:15 Sent To  
Notes
2001-12-01 00:00:00PLAN DENIED
 NO MANUALJ WITH ENERGY CALCS
 PLAN REVIEW BY HAROLD MOSER
 [561] 659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-27 Cont ID  
Sent By jleech Date 2001-11-27 Time 18:31 Rev Time 0.33
Received By jleech Date 2001-11-27 Time 18:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-01-28 Cont ID  
Sent By rmcdouga Date 2002-01-28 Time 10:58 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-28 00:00:00************BUILDING PROVISO************
  
 1) STRUCTURE IS LOCATED IN AN A8 FLOOD
 ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 2) RESUBMIT STORM PANEL INFORMATION WITH
 MASTERED DRAWINGS. THE DRAWINGS
 SUBMITTED STATE THAT THEY ARE GOOD FOR
 ONE PERMIT ONLY.
  
 3) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ONE HOUR RATED GLASS BLOCK
 - GARAGE DOOR, THE ONE SUBMITTED HAS
 BEEN DELETED BY SBCCI

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-12-19 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 09:47 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-19 00:00:00*************BUILDING UNSAT*************
  
 1) THE PRIVACY WALL DETAIL (F-13) ON A-1
 INDICATES FILLED CELLS WITH VERTICLE
 REINFORCEMENT AT 24 " O.C. AND THE PLAN
 SHOWS 8"X16" BLOCK W/2 #5 VERTICLE BARS
 SPACED 5' O.C. PLEASE CLARIFY.
  
 2) THE WALL SECTION ON A-2 INDICATES A
 20" DEEP FOOTER AND THE FOOTER SCHEDULE
 ON A-1 HAS THE FOOTER DEPTH AS 18".
 PLEASE CLARIFY.
  
 3) THE ROOF NOTES ON THE WALL SECTION ON
 A-2 SPECIFIES THE SHEATHING TO BE NAILED
 4" O.C. THRU-OUT THE ENTIRE ROOF AND THE
 STRUCTURAL NOTES ON A-4 CALLS FOR THE
 ROOF SHEATHING TO BE NAILED 4" ON THE
 EDGES AND 6" IN FIELD. PLEASE CLARIFY.
  
 4) THE BUCKET DETAIL ON A-3 DOES NOT
 PROVIDE ENOUGH INFORMATION. INDICATE THE
 HEIGHT,WIDTH,SPACING OF HOLES,TYPE OF
 WELD,ETC.
  
 5) THE TRUSSES AT THE CENTER OF THE
 STRUCTURE ARE INDICATED ON A-3 WITH AN
 UPLIFT OF 1648# AND #1 CONNECTOR WITH
 CAPACITY OF 1365# (PER SCHEDULE) IS
 SPECIFIED. PLEASE CORRECT.
  
 6) SPECIFY THE SIZE,NUMBER AND LENGTH OF
 THE FASTENERS THAT WILL BE USED WITH THE
 #7 ALTERNATE CONNECTOR SHOWN ON A-6.
 INDICATE THE UPLIFT THIS CONNECTOR IS
 CAPABLE OF RESISTING.
  
 7) SPECIFY THE SIZES AND LENGTHS OF THE
 TAPCONS AND WOOD SCREWS THAT ARE USED TO
 ATTACH THE P.T. 2X8S SHOWN ON THE DOOR
 FRAME DETAIL ON A-6.
  
 8) THE WINDOW/DOOR BUCK DETAIL ON A-6
 DOES NOT INDICATE THE SPACING OF THE
 DN72P8 FASTENERS FOR THE 2X4 DOOR BUCKS.
 PLEASE PROVIDE DOOR BUCK CONNECTION
 INFORMATION.
  
 9) PROVIDE BUCK DETAILS FOR THE 8' WIDE
 SLIDING GLASS DOOR. THE DETAIL ON A-6 IS
 FOR S.G. DOORS UP TO 6 FEET WIDE.
  
 10) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
  
 11) STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 12) A DESIGN CERTIFICATION FORM IS
 REQUIRED UNLESS ALL OF THE INFORMATION
 REQUIRED ON THE FORM IS PROVIDED ON THE
 PLANS. NOT ALL OF THE INFORMATION HAS
 BEEN PROVIDED. PLEASE REVIEW THE
 ATTACHED FORM AND PROVIDE THE
 INFORMATION ON THE PLAN OR SUBMIT
 COMPLETED FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-21 Cont ID  
Sent By sgraham Date 2001-11-21 Time 12:28 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***