| 2001-12-20 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) THE PRIVACY WALL DETAIL (F-13) ON A-1 |
| | INDICATES FILLED CELLS W/ VERTICLE |
| | REINFORCEMENT AT 24" O.C. AND THE PLAN |
| | SHOWS 8"X16" BLOCK W/2 #5 VERTICLE BARS |
| | SPACED 5' O.C. PLEASE CORRECT. |
| | |
| | 2) THE WALL SECTION ON A-2 INDICATES A |
| | 20" DEEP FOOTER AND THE FOOTER SCHEDULE |
| | ON A-1 HAS THE FOOTER DEPTH OF 18". |
| | PLEASE CORRECT. |
| | |
| | 3) THE ROOF NOTES ON THE WALL SECTION ON |
| | A-2 SPECIFIES THE SHEATHING NAILED 4" |
| | O.C. THRU-OUT THE ENTIRE ROOF AND THE |
| | STRUCTURAL NOTES ON A-4 CALL FOR THE |
| | ROOF SHEATHING TO BE NAILED 4" ON THE |
| | EDGES AND 6" IN THE FIELD. PLEASE |
| | CORRECT. |
| | |
| | 4) THE DOOR FROM THE GARAGE TO THE |
| | CONDITIONED SPACE IS REQUIRED TO BE |
| | INSULATED OR SOLID CORE PER FLORIDA |
| | ENERGY EFFICIENCY CODE. |
| | |
| | 5) THE STRUCTURE IS LOCATED IN AN "A8" |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. |
| | |
| | 6) A DESIGN CERTIFICATION FORM IS |
| | REQUIRED, UNLESS ALL THE INFORMATION |
| | REQUIRED ON THE FORM IS ON THE PLANS. |
| | NOT ALL REQUIRED INFORMATION HAS BEEN |
| | PROVIDED. INDICATE IF BUILDING IS |
| | DESIGNED AS OPEN,ENCLOSED,ETC. INDICATE |
| | THE IMPORTANCE FACTOR, BASIC WIND |
| | VELOCITY, IF REVIEWED FOR SHEAR WALL |
| | REQUIREMENTS. SEE FORM ATTACHED. |
| | |
| | 7) HUGHES AND SEMCO HAVE BEEN PURCHASED |
| | BY USP AND SOME VALUES HAVE CHANGED. |
| | PLEASE REVIEW TRUSS CONNECTOR SCHEDULE. |
| | |
| | 8) INDICATE THE SIZE AND LENGTHS OF THE |
| | TAPCONS AND WOOD SCREWS THAT ARE TO BE |
| | USED TO ATTACH THE P.T. 2X8S SHOWN ON |
| | THE DOOR FRAME DETAIL ON A-6. |
| | |
| | 9) SPECIFY THE SIZE, NUMBER AND LENGTH |
| | OF THE FASTENERS THAT WILL BE USED WITH |
| | THE #7 ALTERNATE CONNECTOR SHOWN ON A-6. |
| | INDICATE THE UPLIFT THAT THIS CONNECTOR |
| | IS CAPABLE OF RESISTING. |
| | |
| | 10) INDICATE THE SPACING OF THE DN 72P8 |
| | FASTENERS USED TO ANCHOR THE DOOR BUCKS |
| | IN THE BUCK DETAIL ON A-6. |
| | |
| | 11) PROVIDE BUCK DETAILS FOR THE 8 FEET |
| | WIDE SLIDING GLASS DOORS. THE BUCK |
| | DETAIL ON A-6 IS FOR SLIDING GLASS DOORS |
| | UP TO 6' WIDE. |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR GLASS BLOCK. PROVIDE |
| | FIRE RATING INFORMATION FOR GLASS BLOCK. |
| | |
| | ROBERT MCDOUGAL |