Plan Review Details - Permit 01110769
Plan Review Stops For Permit 01110769
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 18:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2001-12-11 Time 18:38 Sent To M
Notes
2001-12-11 00:00:00*************** UNSAT ******************
  
  
 1)NOTE: PLEASE CLARIFY IF SERVICE SHOWN
 IS NEW OR EXISTING? PLEASE NOTE, IF NEW,
 THERE IS MORE INFORMATION NEEDED. AIC
 RATING, GROUNDING ELECTRODE DETAIL?
 PLEASE NOTE THAT NO PANEL SCHEDULES,
 WERE SUBMITTED.PLEASE SHOW MIN REQ`D
 CIRCUITS.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-12 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 18:45 Rev Time 0.40
Received By pkrauss Date 2001-12-12 Time 11:38 Sent To  
Notes
2001-12-12 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status N Date 2002-01-23 Cont ID  
Sent By pschmitz Date 2002-01-15 Time 15:08 Rev Time 0.50
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-15 00:00:00PLUMBING PLAN REVIEWDENIED
 PLANS FOR GAS PIPING, SHOW EXISTING AND
 NEW. SEC 104.1
 COMPLY WITH SGC-97 SEC 504.1 PROHIBITED
 LOCATION OF GAS WATER HEATER IN BED RM.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status N Date 2002-01-17 Cont ID  
Sent By pschmitz Date 2002-01-15 Time 15:16 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-15 00:00:00PLUMBING PLAN REVIEW, PROVISO.
 SEC 104.1 PROVIDE A PLUMBING ISOMETRIC
 OF THE DWV SYSTEM.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-12-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 18:57 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-14 00:00:00PLBG ISOMETRIC AT TIME OF PERMIT
 APPLICATION.PES

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-01-23 Cont ID  
Sent By rmcdouga Date 2002-01-23 Time 12:55 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-23 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED FIXED GLASS WINDOWS AS SHOWN ON
 SOUTH AND EAST ELEVATIONS.
 - STRUCTURAL MULLIONS
  
 2) PROVIDE PRODUCT APPROVALS FOR ROOFING
 UNDER A SEPARATE PERMIT.
  
 3) PROVIDE PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 THIS WILL BE REQUIRED FOR ANY NEW
 GLAZING THAT IS NOT IMPACT RATED.
  
 4) SEPARATE PERMITS WILL BE REQUIRED FOR
 PLUMBING,GAS,MECHANICAL AND ELECTRICAL.
 ADDITIONAL DRAWINGS AND INFORMATION IS
 REQUIRED TO BE SUBMITTED WITH PLUMBING,
 GAS AND MECHANICAL PERMIT APPLICATIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-12-24 Cont ID  
Sent By rmcdouga Date 2001-12-24 Time 10:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-24 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE OVERFLOW SCUPPERS PER 97SBC
 SEC. 1517.6.4.
  
 3) INDICATE THE EXTERIOR WINDOW AND DOOR
 SIZES AND TYPES ON THE PLANS.
  
 4) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED FIXED GLASS WINDOWS
 - STRUCTURAL MULLIONS
 - SINGLE FRENCH DOOR (THE APPROVAL THAT
 WAS SUBMITTED IS FOR SINGLE UNIT
 APPLICATION OF A PAIR OF DOORS AND A
 SINGLE DOOR WITH SIDELITE ONLY)
 THE FRENCH DOOR PRODUCT APPROVALS WERE
 ALSO MISSING THE APPROVED DRAWINGS.
  
 5) PROVIDE A BATHROOM WITH A DOOR HAVING
 A 29" CLEAR OPENING PER FL ACCESSIBILITY
 CODE.
  
 6) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 7) PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS UNDER A SEPARATE PERMIT.
  
 8) INDICATE HOW THE FOYER WALLS WILL BE
 ATTACHED TO THE EXISTING STRUCTURE AND
 NEW BLOCK STRUCTURE.
  
 9) INDICATE THE TRUSS TO DOUBLE PLATE
 AND DOUBLE PLATE TO (3) 2X 10 BEAM
 CONNECTIONS REQUIRED FOR A CONTINOUS
 LOAD PATH.
  
 10) THE ROOF SHEATHING NAILING SPECIFIED
 ON SHEET 4 IS INCORRECT. THE CITY OF WPB
 AMENDMENTS TO THE 97SBC SEC. 2306
 REQUIRE 6"O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE IN ROOF ZONES 1 & 2.
  
 11) INDICATE COMPLIANCE WITH CITY OF WPB
 AMENDMENTS TO 97 SBC SEC. 2304.2.5.
 WHERE LATH AND STUCCO FINISH IS APPLIED
 OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION, AN APPROVED WEEP SCREED
 (STUCCO STOP) PLACED NOT LESS THAN 6"
 ABOVE FINISHED GRADE SHALL BE USED TO
 TERMINATE THE STUCCO AT THE BASE OF THE
 WALL.
  
 12)PROVIDE FIRE BLOCKING AT INTERSECTION
 OF WALL AND CEILING PER 97SBC SEC.2305.1
  
 13) PROVIDE FIRECUTS WHERE TRUSSES
 TERMINATE IN MASONRY WALLS PER 97 SBC
 SEC. 2305.4.
  
 14) INDICATE WALL FURRING MATERIAL THAT
 WILL BE USED ON WALL SECTION.
  
 15) INDICATE ATTIC VENTILATION AS
 REQUIRED BY 97 SBC SEC. 2309.7.
  
 16) PROVIDE ARCHITECT'S TITLE BLOCK ON
 SHEETS 2 AND 3 OF PLANS.
  
 17) PROVIDE A DESIGN CERTIFICATION FORM
 OR PROVIDE ALL THE REQUIRED INFORMATION
 ON THE PLANS (MEAN ROOF HEIGHT, DESIGN
 PRESSURE, IMPORTANCE FACTOR, ETC.). SEE
 ATTACHED.
  
 18) STORM PANELS WILL BE REQUIRED ON ALL
 GLAZING THAT IS NOT IMPACT RESISTANT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-07 Cont ID  
Sent By sgraham Date 2001-12-07 Time 16:41 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***