Plan Review Details - Permit 01110762
Plan Review Stops For Permit 01110762
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 10:51 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-12-10 Cont ID  
Sent By hpiskura Date 2001-12-10 Time 16:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 14:41 Rev Time 0.00
Received By btrobaug Date 2002-05-15 Time 14:22 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 19:21 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 19:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 12:11 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-05 Cont ID  
Sent By ndenmark Date 2002-07-05 Time 14:46 Rev Time 0.33
Received By ndenmark Date 2002-07-05 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 10:38 Rev Time 0.40
Received By pkrauss Date 2002-01-05 Time 10:31 Sent To  
Notes
2002-01-05 00:00:00MECH PERMIT 01110783

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 11:06 Rev Time 0.45
Received By pkrauss Date 2001-12-08 Time 11:04 Sent To  
Notes
2001-12-08 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 2.DETAIL OF CONDENSER UNIT STAND.
 AS PER COUNTY WIDE AMENDMENT 1997
 SMC 304.2.5, A MINIMUM OF 18"
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS.
 (1997 SMC 406.1 & NFPA 90A 4-4.4.3)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 16:39 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 16:39 Sent To  
Notes
2002-05-18 00:00:00REVISION OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-26 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 14:41 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-26 00:00:00REVISION,OK PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-12 Cont ID  
Sent By kstevens Date 2002-01-12 Time 18:14 Rev Time 1.25
Received By kstevens Date 2002-01-12 Time 18:14 Sent To  
Notes
2002-01-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-2, SANITARY RISER DIAGRAM NOT
 TO CODE. FLOOR DRAIN NOT VENTED PROPERLY
 AND DRINKING FOUNTAINS NOT VENTED AT ALL
 PLEASE SUBMIT RISER DIAGRAM THAT MEETS
 CODE REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-12-03 Cont ID  
Sent By kstevens Date 2001-12-03 Time 16:44 Rev Time 1.50
Received By kstevens Date 2001-12-03 Time 16:44 Sent To  
Notes
2001-12-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) MORE INFORMATION REQUIRED. INDICATE
 USAGE FOR SPACE SO THE PROPER MINIMUM
 FIXTURE REQUIREMENTS CAN BE DETERMINED.
 2) DRINKING FOUNTAIN IS REQUIRED PER SPC
 TABLE 407.
 3) SHT A-1, TOILET ACCESS. NOTES #5. TOP
 OF SEAT TO BE 17" TO 19", NOT 19" TO 20"
 AS SHOWN.
 4) SHT A-1, TOILET DETAIL. FLUSH HANDLE
 TO BE ON CLEAR SIDE OF TANK PER FACBC
 SEC 4.16.5.
 5) SHT A-2, HDCP TOILET FLOOR PLAN,
 FLOOR DRAIN NOT VENTED PROPERLY. FLOOR
 DRAIN SHALL COME OFF LAV DRAIN LINE.
 6) SHT A-2, FLOOR DRAIN SHALL BE A MINI-
 MUM OF 3" AND HAVE A TRAP PRIMER PER SPC
 SEC 409.4.1.1.
 7) SHT A-2, W/C SHALL HAVE A 3" DRAIN,
 NOT 2" AS SHOWN. ALSO A MINIMUM OF 3"
 VENT THRU ROOM IS REQUIRED PER SPC SEC
 904.3.1
 8) PLEASE PROVIDE A SANITARY AND A WATER
 RISER DIAGRAM. SHOW ALL PIPE SIZES. SHOW
 WATER HAMMER ARRESTORS PLACED CLOSE TO
 FIXTURES IN AN EFFECTIVE RANGE.
 9) DEMO INSPECTION REQUIRED FOR ALL FIX-
 TURES THAT ARE ELIMINATED.
  
 REVIEW BY KEN STEVENS