| Plan Review Stops For Permit 01110753 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-20 |
Time |
10:03 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-20 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2001-11-20 00:00:00 | ******************PROVISO*************** | | | | | | PLEASE NOTE LOCATION OF NEW AHU - ACCESS | | | FOR SERVICE SHALL COMPLY WITH 1997 SMC | | | 304.4.1,ACCESS OPENING SHALL BE NO | | | LESS THAN 22" X 36" CONTINUOUS FROM THE | | | OPENING TO THE EQUIPMENT AND ITS | | | CONTROLS. | | | | | | A LIGHT ON THE SERVICE SIDE CONTROLLED | | | BY A SWITCH AT THE ACCESS OPENING SHALL | | | BE PROVIDED.AN ACCESSIBLE DISCONNECT | | | SWITCH AND A 110-120 VOLT A/C GROUNDING | | | TYPE CONVENIENCE OUTLET CONVENIENT TO | | | THE GENERAL EQUIPMENT AREA WILL ALSO BE | | | REQUIRED AS PER 1997 SMC 304.4.2 | | | COUNTYWIDE AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|