Plan Review Details - Permit 01110753
Plan Review Stops For Permit 01110753
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-20 Cont ID  
Sent By pkrauss Date 2001-11-20 Time 10:03 Rev Time 0.40
Received By pkrauss Date 2001-11-20 Time 10:03 Sent To  
Notes
2001-11-20 00:00:00******************PROVISO***************
  
 PLEASE NOTE LOCATION OF NEW AHU - ACCESS
 FOR SERVICE SHALL COMPLY WITH 1997 SMC
 304.4.1,ACCESS OPENING SHALL BE NO
 LESS THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT AND ITS
 CONTROLS.
  
 A LIGHT ON THE SERVICE SIDE CONTROLLED
 BY A SWITCH AT THE ACCESS OPENING SHALL
 BE PROVIDED.AN ACCESSIBLE DISCONNECT
 SWITCH AND A 110-120 VOLT A/C GROUNDING
 TYPE CONVENIENCE OUTLET CONVENIENT TO
 THE GENERAL EQUIPMENT AREA WILL ALSO BE
 REQUIRED AS PER 1997 SMC 304.4.2
 COUNTYWIDE AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.