Plan Review Details - Permit 01110620
| Plan Review Stops For Permit 01110620 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-20 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-20 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-05 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-05 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | IF THE PARKING GARAGE IS THREE STORIES | | | AND FIFTY FEET IN HEIGHT A STANDPIPE | | | SYSTEM WILL BE REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
N |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-20 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
ydavis |
Date |
2001-11-20 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2001-11-20 00:00:00 | 1) NO CUT-SHEETS PROVIDED FOR FIRE | | | SPRINKLER HEADS PLANNED FOR USE. PLEASE | | | PROVIDE CUT-SHEETS. | | | 2) PROVIDE DETAILS FOR FIRE SPRINKLER | | | INSTALLATIONS FOR DUMBWAITER AND TRASH | | | CHUTE(S). | | | 3) PLEASE INDICATE IF THE ONE FIRE | | | DEPARTMENT CONNECTION WILL SERVICE ALL | | | OF THE BUILDINGS LOCATED ON THE CAMPUS. | | | 4) NO FIRE SPRINKLER PROTECTION PROVIDED | | | FOR IT EQUIPMENT ROOM. FM 200 SYSTEM | | | IS NOTED BUT CANNOT BE USED IN LIEU OF | | | REQUIRED FIRE SPRINKLER PROTECTION. | | | 5) HOW WILL PIPE PENETRATIONS BE SEALED | | | THRU RATED FIRE WALLS, ETC. WHO'S | | | RESPONSIBLE FOR IT. | | | 6) PLEASE CLEARLY INDICATE WHY NO | | | FIRE STANDPIPE SYSTEM IS PRESENT IN THE | | | GARAGE. IF THE GARAGE IS THREE STORIES | | | AND MORE THAN FIFTY FEET IN HEIGHT A | | | STANDPIPE SYSTEM WOULD BE REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-05 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-05 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
|