Plan Review Details - Permit 01110595
Plan Review Stops For Permit 01110595
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-05 Cont ID  
Sent By hpiskura Date 2002-03-05 Time 13:18 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-22 Cont ID  
Sent By jwitmer Date 2001-11-22 Time 09:13 Rev Time 0.50
Received By jwitmer Date 2001-11-22 Time 09:12 Sent To  
Notes
2001-11-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01110595
 375 S ROSEMARY AV
 CONT AIR SERVICE INC
 TEL: 842-9778
  
 1) STRUCTURAL PLAN S-2 INDICATES ADD-
 ITIONAL STRUCTURAL DETAILS ON S-3 & S-4.
 PAGES MISSING.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-9086 X8412

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 07:05 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 07:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 10:12 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 10:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 11:52 Sent To  
Notes
2002-03-15 00:00:00THE SCRUBBER UNIT IS REQUIRED TO HAVE
 ITS OWN INDEPENDENT FIRE SUPPRESSION
 SYSTEM. PLEASE PROVIDE NOTES ON PLAN
 AND PROVIDE A SEPARATE PLAN AND PERMIT
 FOR ITS INSTALLATION.
 NO DOWNGRADES WILL BE ALLOWED FOR THE
 EXHAUST DUCT BEYOND THE SCRUBBER UNIT.
 SOFFIT REVISIONS WERE ALSO PRESENT WITH
 PLANS.
 THE FAXED COPY WITH REGARDS TO THE
 SCRUBBER UNIT THAT WAS SENT TO
 CONSTRUCTION SERVICES WAS DIFFICULT TO
 READ.
 PLANS ARE STAMPED REVISIONS FOR THE
 HOOD SCRUBBER UNIT. SCRUBBER UNIT IS
 TO BE BY SEPARATE PLAN AND PERMIT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2002-03-15 Time 11:44 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 08:55 Sent To  
Notes
2001-11-21 00:00:001) PLEASE PROVIDE PRODUCT APPROVALS FOR
 FAN SCRUBBER UNIT. PLEASE PROVIDE ALL
 APPLICABLE DATA FOR SCRUBBER UNIT.
 2) NFPA 96 REQUIRES THAT NO DOWNGRADING
 OF EXHUAST DUCT IS TO OCCUR AFTER THE
 PROPOSED FAN SCRUBBER UNIT. ALSO THIS
 CODE REQUIRES A FIRE SUPPRESSION SYSTEM
 FOR THIS EQUIPMENT. PLEASE SEE NFPA 96
 FOR DETAILS. SEPARATE PLANS AND PERMITS
 WILL BE REQUIRED FOR THIS FIRE
 SUPPRESSION SYSTEM. IT APPEARS THAT F5
 HAS BEEN REMOVED FROM FAN SCHEDULE ON
 PAGE M-5.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-05-17 Cont ID  
Sent By pkrauss Date 2002-05-17 Time 09:47 Rev Time 0.40
Received By pkrauss Date 2002-05-17 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-03-15 Cont ID  
Sent By pkrauss Date 2002-03-15 Time 11:35 Rev Time 0.50
Received By pkrauss Date 2002-03-15 Time 11:35 Sent To FIRE
Notes
2002-03-15 00:00:00 
  
 1.THE MANUFACTURER SUBMITTAL THAT
 WAS FAXED IS HARD TO READ THE
 ENGINEERING DATA.
  
 2.FIRE SUPRESSION FOR THE SCRUBBER
 WAS NOT INCLUDED WITH SUBMITTAL.
  
 3.PLANS ARE STAMPED "REVISIONS"THIS
 PERMIT HAS NEVER BEEN ISSUED, THERE
 FORE CANNOT BE A "REVISION.
  
 4.IT SEEMS THAT OTHER PLANS NOT
 PERTAINING TO THE SCRUBBER WHERE
 SUBMITTED.PLEASE CLARIFY WHY THESE
 PLANS WHERE SUBMITTED.
  
 PLEASE NOTE, NO DOWNGRADES TO EXHAUST
 DUCT BEYOND SCRUBBER ALLOWED AS PER NFPA
 96.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-26 Cont ID  
Sent By pkrauss Date 2002-02-26 Time 14:47 Rev Time 1.00
Received By lsmith Date 2002-02-26 Time 14:11 Sent To  
Notes
2002-02-26 00:00:00 
 PLANS ARE INCONSISTENT... NO ELECTRICAL
 PLANS SUBMITTED FOR THE FIRST REVIEW.
 PLANS ARE STAMPED "REVISION"THIS
 PERMIT HAS NEVER BEEN ISSUED.
  
 SECOND REQUEST FOR MANUFACTURER
 SUBMITTAL DATA ON THE SCRUBBER.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-16 Time 08:58 Rev Time 0.35
Received By pkrauss Date 2001-11-16 Time 08:50 Sent To  
Notes
2001-11-21 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR HOOD SCRUBBER.
  
 PLAN SHEET M-2, GREASE HOOD DUCT WRAP
 SEE DETAIL ON DWG. M-3/13.NO SUCH
 PLAN SUBMITTED.
  
 AS PER 1997 SMC 505.5.1, CLEANOUT
 OPENINGS ARE REQUIRED FOR EACH CHANGE
 OF DIRECTION.PLEASE SHOW LOCATIONS OF
 ALL CLEANOUTS.
  
 NOTE - GREASE DUCT SHALL HAVE A MINIMUM
 SLOPE OF 1 INCH PER FOOT.
  
 SHOW COMPLIANCE WITH NFPA 96 SECTION 6-3
 AND 6-3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.