Plan Review Details - Permit 01110574
Plan Review Stops For Permit 01110574
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-14 Cont ID  
Sent By lmartine Date 2001-12-14 Time 12:11 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-23 Cont ID  
Sent By jwitmer Date 2001-11-23 Time 11:46 Rev Time 0.55
Received By jwitmer Date 2001-11-23 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 20:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 19:29 Sent To  
Notes
2001-11-19 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SHOW LOAD CALCUALTIONS,
 PER 220-3/220-13/220-11
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. (LIGHTING) ETC.
  
 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62 LOADS PER 220-12A
  
 3)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5.
  
 PLEASE USBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-23 Cont ID  
Sent By jwitmer Date 2001-11-23 Time 11:40 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-23 00:00:00SEE PLAN MEC APPROVAL 11/19/01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 11:19 Rev Time 0.35
Received By pkrauss Date 2001-12-08 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-29 Cont ID  
Sent By pkrauss Date 2001-11-29 Time 14:25 Rev Time 0.45
Received By pkrauss Date 2001-11-29 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-12-17 Cont ID  
Sent By kstevens Date 2001-12-17 Time 10:16 Rev Time 0.00
Received By kstevens Date 2001-12-17 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-04 Cont ID  
Sent By kstevens Date 2001-12-04 Time 16:47 Rev Time 0.50
Received By kstevens Date 2001-12-04 Time 16:47 Sent To  
Notes
2001-12-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) COMMENT RESPONSE FOR DRINKING FOUNT-
 AIN NOT APPROVED. DRINKING FOUNTAIN RE-
 QUIRED PER SPC TABLE 407. PLEASE COMPLY
 AND SHOW DETAILS.
  
 2) WILL AIR CHAMBERS BE USED? IF SO ACC-
 ESS PANELS SHALL BE REQUIRED. AIR CHAM-
 BERS ALSO NEED TO BE RECHARGEABLE AND
 REQUIRE SHUT OFF VALVES - DRAIN DOWN
 VALVES AND PETCOCK ON TOP. IF WATER
 HAMMER ARRESTORS ARE USED PLEASE IN-
 DICATE SO ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-20 Cont ID  
Sent By kstevens Date 2001-11-20 Time 09:42 Rev Time 0.50
Received By kstevens Date 2001-11-20 Time 09:39 Sent To  
Notes
2001-11-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SPC SEC 407.2.2 REQUIRED FACILITIES
 SHALL BE DIRECTLY ACCESSIBLE TO THE PUB-
 LIC THROUGH DIRECT OPENINGS OR CORRIDORS
 FROM THE AREA OR AREAS THEY ARE INTENDED
 TO SERVE. DOOR OPENING NOT ACCEPTABLE.
 PAGE A-1
  
 2) PAGE A-1, OFFICE DOORS TO OFFICE
 SHALL NOT OPEN INTO CLEAR FLOOR SPACE OF
 SINK PER FACBC SEC 4.22.2
  
 3) PAGE A-1, PER SPC TABLE 407 1 DRINK-
 ING FOUNTAIN IS REQUIRED. D.F SHALL COM-
 PLY WITH FACBC SEC 4.15. IF A SINGLE D.
 F. IS USED PROVISIONS SHALL BE MADE FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING PER FACBC SEC 4.1.3(10).
  
 4) PAGE M-1, WATER PIPING DIAGRAM. IF
 W/HEATER HAS EMERGENCY PAN, IT SHALL
 HAVE A 1" DRAIN LINE. AIR CHAMBERS ARE
 QUICK FIX AND REQUIRE ACCESS PANELS AND
 SHALL BE RECHARGEABLE PER SPC SEC 607.8.
 3. WATER HAMMER ARRESTORS CAN BE INSTALL
 ED WITH OUT ACCESS PANELS.
  
 REVIEW BY KENSTEVENS
 (561) 659-8096 EXT 8377