Plan Review Details - Permit 01110542
Plan Review Stops For Permit 01110542
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-06 Cont ID  
Sent By hpiskura Date 2002-03-06 Time 10:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-06 00:00:00PROVISO:PERMIT AND NOTICE OF
 ACCEPTANCE REPORT IS REQUIRED FOR
 SHUTTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-19 Cont ID  
Sent By hpiskura Date 2002-02-19 Time 14:18 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-19 00:00:00THE NOTICE OF ACCEPTANCE #00-0602.04 FOR
 THE EASTERN METALS SUPPLY IS INCOMPLETE
 AND MOSTLY ILLEGIBLE.PLEASE PROVIDE
 COMPLETE, CLEAR INFORMATION.
  
 THE "CITY PLACE" MANAGEMENT REQUIRES A
 REVIW FOR THEIR REQUIREMENTS AND
 STANDARDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-20 Cont ID  
Sent By jwitmer Date 2001-11-20 Time 15:09 Rev Time 1.50
Received By jwitmer Date 2001-11-20 Time 14:04 Sent To  
Notes
2001-11-20 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110542
 477 S ROSEMARY/175
 CONT:INSIDE OUTFITTERS
 TEL: (954) 561-5262
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACCES CODE= FLORIDA ACCESSIBILITY
 CODE
  
 1)- FL ENERGY CALS. SECTION 400
 2)- SBC 1606.4.1*/ 1707.4.1* ALL GLAZED
 OPENINGS WILL REQUIRE PRODUCT TESTING
 REPORTS FOR LARGE MISSLE IMPACT RESIS-
 TANCE. (2) COPIES OF EITHER SBCCI OR
 DADE COUNTY PRODUCT TESTING REPORTS ARE
 ACCEPTED.
 3)- PLANS DO NOT INDICATE ELEVATIONS-
 CUT SECTIONS THROUGH TENANT SEPERATION
 WALLS.
 4)- PLANS DO NOT INDICATE SOFFITS NOR
 CEILING DROPS, FASTENING SCHEDULE NOR
 FRAMING SPACING.
 5)- PLANS DO NOT GIVE THE MINIMUM BUILD-
 ING TYPE, IF FIRE SPRINKLERED?
 6)- THE FINISH WALL SCHEDULE IS MISSING,
 SBC TABLE 803.3 MINIMUM INTERIOR FINISH
 SCHEDULE.
 7)- PUBLIC RESTROOMS 1204.2 REQUIRE A
 NON-ABSORBANT MATERIAL ON FLOORAND 4'-0"
 HIGH ON THE SIDE WALLS.
 8)- FL ACCES CODE 4.5 FLOOR SURFACES
 ALONG ACCESIBLE ROUTES AND IN ACCESIBLE
 ROOMS AND SPACES INCLUDING FLOORS, WALKS
 AND RAMPS SHALL BE STABLE, FIRM AND
 SLIP-RESISTANT. ADDAAG A-5 A STATIC
 COEFFICIENT OF FRICTION 0.6 ON ACCESIBLE
 ROUTES AND 0.8 ON RAMPS.
  
 PLANS ARE INADEQUITE TO DO A THOROUGH PL
 AN REVIEW WITH.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-06-12 Cont ID  
Sent By dpalmer Date 2002-06-12 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2002-06-12 Time 19:56 Sent To  
Notes
2002-06-12 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE SCHEDULE FOR PANEL
 "B" NEEDS TO HAVE LOAD/OCP/WIRE SIZE
 CORRELATE. PLEASE NOTE 20KW SHOWN FOR
 #12 W/20A OCP.
 PLEASE ALSO CLARIFY LOAD SHOWN FOR
 XFMR AS #4? MISPRINT?
  
 2)NOTE: PLEASE SHOW CONTINOUS LOADS AT
 125%.
  
 3)NOTE: PLEASE CLARIFY WHERE COND UNIT
 IS FED FROM. 480V PANEL SHOWS AHU BUT
 NOT COND UNIT??
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE, THIS IS THE FIRST TIME A
 RISER DIAGRAM HAS BEEN SUBMITTED FOR
 REVIEW. PLEASE SUBMIT ASAP FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 14:26 Sent To  
Notes
2002-05-29 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ANY CHANGES TO
 PLANS THAT ORIG DONE BY AN ARCH/ENGINEER
 OF RECORD, NEEDS TO HAVE REVISIONS DONE
 BY THAT PERSON(S).
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-19 Cont ID  
Sent By dpalmer Date 2002-02-19 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2002-02-19 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 21:46 Sent To  
Notes
2001-11-19 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62 LOAD PER 220-12A.
  
 2)NOTE: PLEASE NOTE MISSING EXITS/EM LTS
 PLEASE SHOW.
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220-3/220-11/220-13 ETC.
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% 230-42/215-3
  
 4)NOTE: PLEASE CLARIFY 100A OCP FOR
 #6 AWG ON A/C UNIT. AT 20KW LOAD?
  
 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUND BETWEEN MAIN DISCONNECT AND
 PANEL. PLEASE SIZE CONDCUTOR PER 250-122
  
 6)NOTE: PLEASE CLARIFY SWITCHING FOR
 LIGHTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 ***NOTE***
  
 NEED TO PROVIDE CONTRACT FOR COMPLETE
 SCOPE OF WORK TO INCLUDE ALL LABOR AND
 MATERIALS. NEED TO VERIFY VALUE ON THE
 APPLICATION. 104.7.5 OF PALM BEACH
 COUNTY AND CITY WIDE ADMIN. CODE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-03-05 Cont ID  
Sent By mcarsill Date 2002-03-05 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2002-03-05 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-02-19 Cont ID  
Sent By mcarsill Date 2002-02-19 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2002-02-19 Time 11:15 Sent To  
Notes
2002-02-19 00:00:001) SINCE EXIT ACCESS IS PROVIDED THRU
 THE STOCKROOM, PLEASE INDICATE HOW
 THE REQUIRED 44" AISLE IS GOING TO
 BE MAINTAINED TO REACH THE REAR EXIT.
 2) PLEASE INDICATE HOW THE STOCKROOM
 IS GOING TO BE MAINTAINED IN AN
 UNOBSTRUCTED CONDITION FOR THE PATH
 OF TRAVEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 13:23 Sent To  
Notes
2001-11-21 00:00:001) INSUFFICIENT INFORMATION TO PERFORM
 PLAN REVIEW. ALL OF THE REQUIRED FIRE
 AND LIFE SAFETY EQUIPMENT NOT DEPICTED
 ON THE PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-03-05 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 12:54 Rev Time 0.45
Received By pkrauss Date 2002-03-05 Time 12:19 Sent To  
Notes
2002-03-05 00:00:00 
 PROVISO:
  
 OUTSIDE AIR SHALL BE IN CLOSE PROXIMITY
 TO THE RETURN AIR TO ENSURE PROPER
 CIRCULATION OF THE OUTSIDE AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-20 Cont ID  
Sent By pkrauss Date 2002-02-20 Time 09:30 Rev Time 0.45
Received By pkrauss Date 2002-02-20 Time 09:30 Sent To  
Notes
2002-02-20 00:00:00********************DENIED**************
  
  
 1.PROVIDE INFORMATION ON THE RETURN
 AIR GRILLE IN THE DOOR.IS THIS FOR
 AIR TRANSFER & DOES THE STORAGE ROOM
 ALSO HAVE A RETURN AIR GRILLE IN THE
 CEILING?AS PER 1997 SMC 609.1, A
 ROOM SHALL NOT BE USED AS AN
 INTEGRAL PART OF A DUCT SYSTEM OR
 PLENUM.SUCH CHAMBERS SHALL NOT BE
 USED FOR STORAGE OR OCCUPATIONAL
 PURPOSES.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096,
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 16:36 Rev Time 0.35
Received By pkrauss Date 2001-11-21 Time 16:36 Sent To  
Notes
2001-11-21 00:00:00 
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 13:09 Rev Time 0.75
Received By kstevens Date 2002-02-25 Time 13:08 Sent To  
Notes
2002-02-25 00:00:00PASSED/PROVISO
  
 IF DRINKING FOUNTAIN IS NOT A HI/LOW,
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By kstevens Date 2001-11-19 Time 17:01 Rev Time 1.00
Received By kstevens Date 2001-11-19 Time 17:01 Sent To  
Notes
2001-11-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 1, MINIMUM FIXTURES REQUIRED.
 1 MENS RESTROOM AND 1 WOMENS RESTROOM
 REQUIRED PER SPC TABLE 407.
 2) PAGE 1 MINIMUM FIXTURES REQUIRED.
 1 DRINKING FOUNTAIN REQUIRED PER SPC
 TABLE 407. DRINKING FOUNTAIN TO COMPLY
 WITH FACBC SEC 4.15. SHOW CLEAR FLOOR
 SPACE, SPOUT HEIGHT EXT. IF SINGLE D.F.
 PROVISIONS SHALL BE PROVIDED FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 3) PER FACBC SEC 4.1.3(1) RESTROOMS
 SHALL BE ON AN ACCESSIBLE ROUTE. CASED
 OPENING REQUIRED. PLEASE REMOVE DOOR SO
 RESTROOMS ARE ACCESSIBLE FOR PUBLIC USE.
 4) PER FACBC SEC 4.1.3(16)(A)(B) SIGNAGE
 SHALL BE PROVIDED.
 5) DRESSING ROOM BENCH TO COMPLY WITH
 FACBC SEC 4.35.4. PLEASE SHOW DETAILS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377