| Plan Review Stops For Permit 01110542 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-06 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-06 00:00:00 | PROVISO:PERMIT AND NOTICE OF | | | ACCEPTANCE REPORT IS REQUIRED FOR | | | SHUTTERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-02-19 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | THE NOTICE OF ACCEPTANCE #00-0602.04 FOR | | | THE EASTERN METALS SUPPLY IS INCOMPLETE | | | AND MOSTLY ILLEGIBLE.PLEASE PROVIDE | | | COMPLETE, CLEAR INFORMATION. | | | | | | THE "CITY PLACE" MANAGEMENT REQUIRES A | | | REVIW FOR THEIR REQUIREMENTS AND | | | STANDARDS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-20 |
Time |
15:09 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-11-20 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2001-11-20 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01110542 | | | 477 S ROSEMARY/175 | | | CONT:INSIDE OUTFITTERS | | | TEL: (954) 561-5262 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS STANDARD BUILDING CODE | | | FL ACCES CODE= FLORIDA ACCESSIBILITY | | | CODE | | | | | | 1)- FL ENERGY CALS. SECTION 400 | | | 2)- SBC 1606.4.1*/ 1707.4.1* ALL GLAZED | | | OPENINGS WILL REQUIRE PRODUCT TESTING | | | REPORTS FOR LARGE MISSLE IMPACT RESIS- | | | TANCE. (2) COPIES OF EITHER SBCCI OR | | | DADE COUNTY PRODUCT TESTING REPORTS ARE | | | ACCEPTED. | | | 3)- PLANS DO NOT INDICATE ELEVATIONS- | | | CUT SECTIONS THROUGH TENANT SEPERATION | | | WALLS. | | | 4)- PLANS DO NOT INDICATE SOFFITS NOR | | | CEILING DROPS, FASTENING SCHEDULE NOR | | | FRAMING SPACING. | | | 5)- PLANS DO NOT GIVE THE MINIMUM BUILD- | | | ING TYPE, IF FIRE SPRINKLERED? | | | 6)- THE FINISH WALL SCHEDULE IS MISSING, | | | SBC TABLE 803.3 MINIMUM INTERIOR FINISH | | | SCHEDULE. | | | 7)- PUBLIC RESTROOMS 1204.2 REQUIRE A | | | NON-ABSORBANT MATERIAL ON FLOORAND 4'-0" | | | HIGH ON THE SIDE WALLS. | | | 8)- FL ACCES CODE 4.5 FLOOR SURFACES | | | ALONG ACCESIBLE ROUTES AND IN ACCESIBLE | | | ROOMS AND SPACES INCLUDING FLOORS, WALKS | | | AND RAMPS SHALL BE STABLE, FIRM AND | | | SLIP-RESISTANT. ADDAAG A-5 A STATIC | | | COEFFICIENT OF FRICTION 0.6 ON ACCESIBLE | | | ROUTES AND 0.8 ON RAMPS. | | | | | | PLANS ARE INADEQUITE TO DO A THOROUGH PL | | | AN REVIEW WITH. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-12 |
Time |
19:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-12 |
Time |
19:56 |
Sent To |
|
|
| Notes |
| 2002-06-12 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE SCHEDULE FOR PANEL | | | "B" NEEDS TO HAVE LOAD/OCP/WIRE SIZE | | | CORRELATE. PLEASE NOTE 20KW SHOWN FOR | | | #12 W/20A OCP. | | | PLEASE ALSO CLARIFY LOAD SHOWN FOR | | | XFMR AS #4? MISPRINT? | | | | | | 2)NOTE: PLEASE SHOW CONTINOUS LOADS AT | | | 125%. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE COND UNIT | | | IS FED FROM. 480V PANEL SHOWS AHU BUT | | | NOT COND UNIT?? | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | PLEASE NOTE, THIS IS THE FIRST TIME A | | | RISER DIAGRAM HAS BEEN SUBMITTED FOR | | | REVIEW. PLEASE SUBMIT ASAP FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-29 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-29 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ANY CHANGES TO | | | PLANS THAT ORIG DONE BY AN ARCH/ENGINEER | | | OF RECORD, NEEDS TO HAVE REVISIONS DONE | | | BY THAT PERSON(S). | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-19 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-19 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-19 |
Time |
21:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-19 |
Time |
21:46 |
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | OUTLETS PER 210-62 LOAD PER 220-12A. | | | | | | 2)NOTE: PLEASE NOTE MISSING EXITS/EM LTS | | | PLEASE SHOW. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PER 220-3/220-11/220-13 ETC. | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125% 230-42/215-3 | | | | | | 4)NOTE: PLEASE CLARIFY 100A OCP FOR | | | #6 AWG ON A/C UNIT. AT 20KW LOAD? | | | | | | 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUND BETWEEN MAIN DISCONNECT AND | | | PANEL. PLEASE SIZE CONDCUTOR PER 250-122 | | | | | | 6)NOTE: PLEASE CLARIFY SWITCHING FOR | | | LIGHTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | ***NOTE*** | | | | | | NEED TO PROVIDE CONTRACT FOR COMPLETE | | | SCOPE OF WORK TO INCLUDE ALL LABOR AND | | | MATERIALS. NEED TO VERIFY VALUE ON THE | | | APPLICATION. 104.7.5 OF PALM BEACH | | | COUNTY AND CITY WIDE ADMIN. CODE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-05 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-05 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-19 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-19 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | 1) SINCE EXIT ACCESS IS PROVIDED THRU | | | THE STOCKROOM, PLEASE INDICATE HOW | | | THE REQUIRED 44" AISLE IS GOING TO | | | BE MAINTAINED TO REACH THE REAR EXIT. | | | 2) PLEASE INDICATE HOW THE STOCKROOM | | | IS GOING TO BE MAINTAINED IN AN | | | UNOBSTRUCTED CONDITION FOR THE PATH | | | OF TRAVEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-21 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-21 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | 1) INSUFFICIENT INFORMATION TO PERFORM | | | PLAN REVIEW. ALL OF THE REQUIRED FIRE | | | AND LIFE SAFETY EQUIPMENT NOT DEPICTED | | | ON THE PLANS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-05 |
Time |
12:54 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-03-05 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2002-03-05 00:00:00 | | | | PROVISO: | | | | | | OUTSIDE AIR SHALL BE IN CLOSE PROXIMITY | | | TO THE RETURN AIR TO ENSURE PROPER | | | CIRCULATION OF THE OUTSIDE AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-20 |
Time |
09:30 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-20 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | ********************DENIED************** | | | | | | | | | 1.PROVIDE INFORMATION ON THE RETURN | | | AIR GRILLE IN THE DOOR.IS THIS FOR | | | AIR TRANSFER & DOES THE STORAGE ROOM | | | ALSO HAVE A RETURN AIR GRILLE IN THE | | | CEILING?AS PER 1997 SMC 609.1, A | | | ROOM SHALL NOT BE USED AS AN | | | INTEGRAL PART OF A DUCT SYSTEM OR | | | PLENUM.SUCH CHAMBERS SHALL NOT BE | | | USED FOR STORAGE OR OCCUPATIONAL | | | PURPOSES. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096, | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-21 |
Time |
16:36 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-11-21 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE PROVIDE PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-25 |
Time |
13:09 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-02-25 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2002-02-25 00:00:00 | PASSED/PROVISO | | | | | | IF DRINKING FOUNTAIN IS NOT A HI/LOW, | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-19 |
Time |
17:01 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-11-19 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 1, MINIMUM FIXTURES REQUIRED. | | | 1 MENS RESTROOM AND 1 WOMENS RESTROOM | | | REQUIRED PER SPC TABLE 407. | | | 2) PAGE 1 MINIMUM FIXTURES REQUIRED. | | | 1 DRINKING FOUNTAIN REQUIRED PER SPC | | | TABLE 407. DRINKING FOUNTAIN TO COMPLY | | | WITH FACBC SEC 4.15. SHOW CLEAR FLOOR | | | SPACE, SPOUT HEIGHT EXT. IF SINGLE D.F. | | | PROVISIONS SHALL BE PROVIDED FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | 3) PER FACBC SEC 4.1.3(1) RESTROOMS | | | SHALL BE ON AN ACCESSIBLE ROUTE. CASED | | | OPENING REQUIRED. PLEASE REMOVE DOOR SO | | | RESTROOMS ARE ACCESSIBLE FOR PUBLIC USE. | | | 4) PER FACBC SEC 4.1.3(16)(A)(B) SIGNAGE | | | SHALL BE PROVIDED. | | | 5) DRESSING ROOM BENCH TO COMPLY WITH | | | FACBC SEC 4.35.4. PLEASE SHOW DETAILS | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|