Plan Review Details - Permit 01110485
Plan Review Stops For Permit 01110485
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-12-20 Cont ID  
Sent By mamini Date 2001-12-20 Time 09:22 Rev Time 2.00
Received By mamini Date 2001-12-20 Time 09:12 Sent To  
Notes
2001-12-20 00:00:00PASSED :
 1. RESPONSES TO THE PREVIUOS REVIEW
 COMMENTS DATED 11-19-01 SATISFACTORY AND
 IMPLEMENTED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By mamini Date 2001-11-19 Time 13:37 Rev Time 1.00
Received By mamini Date 2001-11-19 Time 13:37 Sent To  
Notes
2001-11-19 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER PIPE
 CALCULATIONS.
 2. PLEASE PROVIDE DETAILS FOR ALL THE
 STORM WATER STRUCTURES USED ON THIS SITE
 3. PLEASE PROVIDE DETAILS FOR CULVERT
 CONNECTIONS TO LAKES.
 4. REFER TO PLAN SHEET FOR COMMENTS AND
 CORRECT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI