| 2001-12-04 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC* = STANDARD BUILDING CODE (AMENDMENT |
| | S) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | FL ENERGY CODE = FLORIDA ENERGY EFFICIEN |
| | CY CODE FOR BUILDING CONSTRUCTION |
| | |
| | 1) SBC* 104.2.1REAR AND SIDE |
| | ELEVATIONS SHALL BE SUBMITTED TO SHOW |
| | THE ROOF PROFILE AND DOOR AND WINDOW |
| | ARRANGEMENTS. |
| | |
| | 2) FL ENERGY CODE 103.0CODE COMPLIANCE |
| | CERTIFICATION FORMS SHALL BE SUBMITTED |
| | UNLESS THE BUILDING IS NEITHER HEATED |
| | NOR COOLED BY MECHANICAL SYSTEMS, AND |
| | THEREFORE EXEMPT AS DESCRIBED IN PART |
| | VIII OF CHAPTER 553, FLORIDA STATUTES |
| | (SS. 553.902(1)(B) AND 553.903). |
| | |
| | 3) FL ACC CODE 4.23.2THE BATHROOM DOOR |
| | SHALL HAVE A MINIMUM CLEAR OPENING OF |
| | 29 INCHES. |
| | |
| | 4) SBC* 1707.4PRODUCT APPROVAL |
| | DOCUMENTS FOR THE NEW EXTERNAL DOOR AND |
| | WINDOWS SHALL BE SUBMITTED. |
| | |
| | 5) SBC 2405.2.1(2) AND (4)GLAZING IN |
| | HAZARDOUS LOCATIONS IS REQUIRED BY |
| | SBC 2405.1 TO PASS THE IMPACT AND OTHER |
| | LOAD TEST REQUIREMENTS OF CPSC (U.S. |
| | CONSUMER PRODUCT SAFETY COMMISSION) |
| | 16-CFR, PART 1201. |
| | |
| | 6) SBC 2308.1SPECIFY THE SPACING OF |
| | THE STUDS TO ENSURE COMPLIANCE WITH |
| | TABLE SBC 2308.1. |
| | |
| | 7) TYPICAL SECTION.THE PROPOSED TRUSS |
| | ANCHOR "SIMPSON ETA 18" DOES NOT APPEAR |
| | TO BE A VALID SIMPSON OR USP REFERENCE. |
| | PRODUCT DETAILS OR CORRECT REFERENCE |
| | REQUIRED. |