Plan Review Details - Permit 01110451
Plan Review Stops For Permit 01110451
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-04 Cont ID  
Sent By rbrown Date 2002-01-04 Time 18:36 Rev Time 0.00
Received By rbrown Date 2002-01-04 Time 18:35 Sent To  
Notes
2002-01-03 00:00:00BUILDING PLAN REVIEW
 *******PROVISO******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
  
  
 --PROVISO-- SBC* 104.1.1A SEPARATE
 ROOFING PERMIT APPLICATION IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-19 Cont ID  
Sent By rbrown Date 2001-12-19 Time 11:56 Rev Time 0.00
Received By rbrown Date 2001-12-19 Time 11:56 Sent To  
Notes
2001-12-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE 12/4/01 BUILDING PLAN REVIEW.
  
 1) PROVISO. SBC* 104.1.1A SEPARATE
 ROOFING PERMIT APPLICATION IS REQUIRED.
 NOTE THAT A PRODUCT APPROVAL WILL BE
 REQUIRED FOR THE FIBERGLASS SHINGLES.
  
 3) PROVISO. FL ACC CODE 4.23.2AS
 PREVIOUSLY STATED THE BATHROOM DOOR
 SHALL HAVE A MINIMUM CLEAR OPENING OF
 29 INCHES. ADD DIMENSION TO PLAN.
  
 4) SBC* 1707.4 AND 2405.1.1THE PRODUCT
 APPROVAL FOR THE EXTERNAL DOOR REQUIRES
 THE USE OF IMPACT RESISTANT SHUTTERS.
 THE PRODUCT APPROVAL FOR THE WINDOWS IS
 MISSING SHEET 2 WHICH WILL BE ENTITLED
 'NOTICE OF ACCEPTANCE: SPECIFIC
 CONDITIONS' AND WILL STATE WHETHER
 IMPACT SHUTTERS ARE REQUIRED.EITHER
 PROVIDE IMPACT SHUTTERS OR DEMONSTRATE
 THAT THEY ARE NOT REQUIRED BY THE
 PRODUCT APPROVAL.
  
 5) SBC 2405.2.1(1),(2)&(4)THE GLAZING
 IN THE BATHROOM WINDOW, NEW EXTERNAL
 DOOR AND REPLACEMENT FRONT WINDOWS IS
 IN HAZARDOUS LOCATIONS AND SHALL PASS
 THE IMPACT AND OTHER REQUIREMENTS OF
 CPSC 16-CFR, PART 1201, AS PREVIOUSLY
 STATED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-04 Cont ID  
Sent By dpalmer Date 2001-12-04 Time 16:34 Rev Time 0.30
Received By rbrown Date 2001-12-04 Time 16:30 Sent To  
Notes
2001-12-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE (AMENDMENT
 S)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY EFFICIEN
 CY CODE FOR BUILDING CONSTRUCTION
  
 1) SBC* 104.2.1REAR AND SIDE
 ELEVATIONS SHALL BE SUBMITTED TO SHOW
 THE ROOF PROFILE AND DOOR AND WINDOW
 ARRANGEMENTS.
  
 2) FL ENERGY CODE 103.0CODE COMPLIANCE
 CERTIFICATION FORMS SHALL BE SUBMITTED
 UNLESS THE BUILDING IS NEITHER HEATED
 NOR COOLED BY MECHANICAL SYSTEMS, AND
 THEREFORE EXEMPT AS DESCRIBED IN PART
 VIII OF CHAPTER 553, FLORIDA STATUTES
 (SS. 553.902(1)(B) AND 553.903).
  
 3) FL ACC CODE 4.23.2THE BATHROOM DOOR
 SHALL HAVE A MINIMUM CLEAR OPENING OF
 29 INCHES.
  
 4) SBC* 1707.4PRODUCT APPROVAL
 DOCUMENTS FOR THE NEW EXTERNAL DOOR AND
 WINDOWS SHALL BE SUBMITTED.
  
 5) SBC 2405.2.1(2) AND (4)GLAZING IN
 HAZARDOUS LOCATIONS IS REQUIRED BY
 SBC 2405.1 TO PASS THE IMPACT AND OTHER
 LOAD TEST REQUIREMENTS OF CPSC (U.S.
 CONSUMER PRODUCT SAFETY COMMISSION)
 16-CFR, PART 1201.
  
 6) SBC 2308.1SPECIFY THE SPACING OF
 THE STUDS TO ENSURE COMPLIANCE WITH
 TABLE SBC 2308.1.
  
 7) TYPICAL SECTION.THE PROPOSED TRUSS
 ANCHOR "SIMPSON ETA 18" DOES NOT APPEAR
 TO BE A VALID SIMPSON OR USP REFERENCE.
 PRODUCT DETAILS OR CORRECT REFERENCE
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-03-21 Cont ID  
Sent By btrobaug Date 2005-03-21 Time 12:46 Rev Time 0.25
Received By btrobaug Date 2005-03-21 Time 12:43 Sent To  
Notes
2005-03-21 00:00:00 
 ADDED THIS STOP IN ERROR./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 16:21 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-04 Cont ID  
Sent By rbrown Date 2002-01-04 Time 19:15 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 20:18 Rev Time 0.33
Received By kstevens Date 2001-11-16 Time 20:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-14 Cont ID  
Sent By sgraham Date 2001-11-14 Time 10:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***