Plan Review Details - Permit 01110421
Plan Review Stops For Permit 01110421
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-28 Cont ID  
Sent By pkrauss Date 2002-02-19 Time 08:51 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-28 00:00:00PROVISO:
 SHEET A-9 INDICATES WALL SECTIONS HUNG
 FROM THE CEILING, RECEPTION AREA, INDICA
 TE FASTENERS& FREQUENCY OF FASTENING.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 21:18 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 21:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 18:11 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-25 Cont ID  
Sent By mcarsill Date 2002-01-25 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2002-01-25 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 07:13 Rev Time 0.30
Received By pkrauss Date 2002-02-07 Time 07:13 Sent To B
Notes
2002-02-07 00:00:00MECHANICAL PERMIT 02020462
  
 PROVISO:
  
 EXHAUST DUCT SHALL HAVE A FIRE DAMPER
 UNLESS IT MEETS ALL THE REQUIREMENTS OF
 1997 SMC 610.1.3 #3 - 1 THRU 4.
  
 1.DUCT SHALL NOT EXCEED 100 SQ INCHES
 2.THE DUCT SHALL BE OF 0.0217 MINIMUM
 STEEL
 3.THE DUCT SHALL CONTINUE WITH NO DUCT
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 THE RATED WALL.
 4.THE DUCT SHALL BE INSTALLED ABOVE
 THE CEILING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-29 Cont ID  
Sent By pkrauss Date 2001-11-29 Time 11:09 Rev Time 0.45
Received By pkrauss Date 2001-11-29 Time 11:03 Sent To  
Notes
2001-11-29 00:00:00*******************PROVISO**************
  
  
 PLAN SHEET M2.1, NOTE INDICATES 6"
 EXHAUST DUCT PENETRATING 1 HOUR FIRE
 RATED WALL A FIRE DAMPER IS NOT
 REQUIRED.
  
 AS PER 1997 SMC 510.1.2 #1, DUCTS
 PENETRATING WALLS OR PARTITIONS HAVING
 A FIRE RESISTANCE RATING OF 1 OR MORE
 HOURS.
  
 PLEASE CORRECT PLANS TO REFLECT FIRE
 DAMPERS.ALSO, O.A. DUCT INDICATES A
 DAMPER BUT DOES NOT SPECIFY A FIRE
 DAMPER OR A FIRE/SMOKE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096.
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 18:20 Rev Time 1.33
Received By kstevens Date 2002-01-31 Time 18:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-07 Cont ID  
Sent By kstevens Date 2002-01-07 Time 17:52 Rev Time 0.00
Received By kstevens Date 2002-01-08 Time 09:04 Sent To  
Notes
2002-01-08 00:00:00DENIED
 REFERENCES: SPC-94-FACBC-97
  
 1) MINIMUM FACILITIES CALL FOR 1 MALE
 AND 1 FEMALE RESTROOM. THE ONLY EXCEPT-
 ION IS FOOTNOTE #6 WHICH CALL FOR ONE
 UNISEX RESTROOM FOR A SPACE 1500 SQ FT
 OR LESS FOR RETAIL.
  
 2) MINIMUM FALILITIES ALSO CALLS FOR 1
 DRINKING FOUNTAIN WHICH IS NOT SHOWN.
 TABLE 407 SPC. IF SINGLE DRINKING FOUNT-
 AIN IS USED, PROVISIONS SHALL BE PROVID-
 ED FOR THOSE THAT HAVE DIFFICULTY BEND-
 ING OR STOOPING PER FACBC SEC 4.1.3(10)
 (A).
  
 3) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 HANDICAP FIXTURES. FACBC SEC 4.15.5,
 4.16.2, 4.19.3, 4.22.3, & 4.24.5.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 17:20 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 17:20 Sent To  
Notes
2001-11-21 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) CALCULATIONS FOR MINIMUM FACILITIES
 INDICAT THAT 1 MALE AND 2 FEMALE W/C'S
 AND LAV ARE REQUIRED FOR THE SQUARE
 FOOTAGE INDICATED ON PAGE T-1.
  
 2) PAGES A-2/A-12 KITCHEN ROOM 104. SINK
 TO COMPLY WITH FACBC SEC 4.24 (1) THRU
 (8). PLEASE SUBMIT DETAILS OF COMPLIANCE
  
 REVEIW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 13:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***