Plan Review Details - Permit 01110412
Plan Review Stops For Permit 01110412
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-03-25 Cont ID  
Sent By jwitmer Date 2003-03-25 Time 16:09 Rev Time 1.00
Received By jwitmer Date 2003-03-25 Time 16:09 Sent To  
Notes
2003-03-25 00:00:00STORM SHUTTERS, KEY PLAN ANCHOR SCHEDULE
 AND PROTEST TESTING REPORTS REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-10-03 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 16:13 Rev Time 1.00
Received By jwitmer Date 2002-10-03 Time 08:20 Sent To  
Notes
2002-10-03 00:00:0010/3/02 REVISION: BREEZEWAY REDUCTION IN
 LENGTH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-09-02 Cont ID  
Sent By jwitmer Date 2002-09-02 Time 13:30 Rev Time 1.50
Received By jwitmer Date 2002-09-02 Time 13:30 Sent To  
Notes
2002-09-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01110412
 ADD:EPOCH/PORTOFINO/MASTER TYPE III
 CONT: EPOCH
 TEL: (561)683-1052
 STD BLD CD= 1997 STANDARD BUILDING CODE
  
 ******PROVISO*****
  
 1) WEDGE-ALL ANCHORS DETAILS, SINCE THE
 LOADING IS NOT GIVEN FOR TENSION OR
 SHEAR LOAD APPLICATIONS HAS THE EDGE FAC
 TOR (REDUCTION) BEEN FACTORED INTO THE
 SPACING?
 A) DETAIL "D" S_D1.1 EXTERIOR CONDITION
 @ LOFT 2X6 WALL SITTING ON TOP OF A 5"
 CONCRETE WALL? NO INFORMATION IS GIVEN,
 CONTACT SIMPSON ENG TO SEE IF A DOUBLE
 REDUCTION WOULD BE REQUIRED SINCE YOU
 WOULD BE 2 1/2" AWAY FROM BOTH SIDES?
 B) DETAIL# 3, 2X6 WALL AT THE EDGE OF
 SLAB, WHAT REDUCTION HAS BEEN TAKEN? HOW
 FAR AWAY FROM THE EDGE OF THE SLAB WILL
 THE ANCHOR BE LOCATED?
  
 ADDITIONAL INFORMATION SHALL BE OBTAINED
 TO CLARIFY THE CONDITIONS LISTED ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-04-30 Cont ID  
Sent By jwitmer Date 2002-04-30 Time 07:12 Rev Time 1.25
Received By jwitmer Date 2002-04-30 Time 07:12 Sent To  
Notes
2002-04-30 00:00:00*******BUILDING PROVISO******
  
 MASTER TYPE III
  
 SOILS TEST REPORT INDICATES FURTHER
 INVESTIGATION BEFORE THE PERMIT CAN BE
 ISSUED. SHOW HOW DENSIFICATION OF SOIL
 WILL OCCUR.
  
 HYDROLIC CALCS MISSING FROM PLAN.
  
 DESIDENT INSPECTOR TO REGISTER WITH DON
 NEELY BEFORE PERMITS MAY BE ISSUED.
  
 BUILDING PLANS TO BE SUBMITTED TO P.B.
 COUNTY FOR IMPACT FEE ASSESSMENT
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-03-26 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 17:44 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110412
 BRIGER TRACT
 BUILDING TYPE III
 THIRD REVIEW
 SBC= 1997 STANDARD BUILDING CODE
  
 SAME COMMENTS AS TYPE I BUILDING SEE
 01110409.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-21 Cont ID  
Sent By jwitmer Date 2002-02-21 Time 13:02 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-21 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK # 01110412
 BRIGER TRACT "D"
 BUILDING PLAN III
  
 SEE COMMENTS ON01110409
  
 J.WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-14 Cont ID  
Sent By jwitmer Date 2001-12-14 Time 13:53 Rev Time 4.00
Received By jwitmer Date 2001-12-14 Time 13:53 Sent To  
Notes
2001-12-14 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110412
 BRIGER TRACT "D"
 BUILDINGTYPE III
  
 FLOOR AREA:
 1ST FL9,523 SQ FT
 2ND FL9,392 SQ FT
 3RD FL9,392 SQ FT
 LOFT 2,556 SQ FT
 TOTAL30,863 SQ FT
  
  
  
 SEE PLAN REVIEW 01110409 FOR NOTES.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2003-04-29 Cont ID  
Sent By btrobaug Date 2003-04-29 Time 13:08 Rev Time 0.75
Received By btrobaug Date 2003-04-29 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-11-14 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:40 Rev Time 0.00
Received By btrobaug Date 2002-11-14 Time 17:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 19:42 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 19:42 Sent To  
Notes
2002-06-19 00:00:00************* NOTE *******************
 REDLINED ON PLANS, PERMITS APPLIED FOR
 AFTER JAN 1ST 2002, REQ`D ARC FAULT
 PROTECTIONPER 210-12. 99 NEC.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-06-13 Cont ID  
Sent By dpalmer Date 2002-06-13 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2002-06-13 Time 10:15 Sent To  
Notes
2002-06-13 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE SAME NOTES AS BEFORE
 .

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-05-09 Cont ID  
Sent By dpalmer Date 2002-05-09 Time 06:57 Rev Time 0.00
Received By dpalmer Date 2002-05-09 Time 06:57 Sent To  
Notes
2002-05-09 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT E-SHEETS DO
 NOT HAVE AN ORIGINAL SIGNATURE FROM
 THE ARCH/ENGINEER OF RECORD. PLEASE
 NOTE THAT PER FS/FAC MUST BE AN ORIG
 SIGNATURE. 471.025/481.221.
  
 2)NOTE: PLEASE NOTE, OUTLET SPACING FOR
 BALCONY/LOFT UNITS, STILL DO NOT MEET
 210-52. PLEASE NOTE RAIL AREAS ARE STILL
 CONSIDERED 'WALL SPACE'. 210-52 ALSO
 INCLUDES COUNTERSPACE IN KITCHENS...
 PLEASE SEE 210-52C-1.
 PLEASE SEE 210-52A 1-2-3.
  
  
  
  
 3)NOTE: PLEASE NOTE THAT PLANS KEEP
 GOING BACK AND FORTH FOR CONDUIT TYPE
 FOR FEEDERS TO UNITS. EMT IS PERMITTED
 ONLY IN EXPOSED ARES ABOVE GROUND. IF
 ANY OF THESE FEEDERS ARE IN THE SLAB OR
 POURED IN CONCRETE, DIRECT CONTACT WITH
 EARTH ETC. 348-5
 PLEASE NOTE THAT PREVIOUS NOTE FOR THIS
 ITEM WAS THAT PLANS SHOWED "RIGID"
 CONDUIT AND ITS EXPENSE. PVC IS ALSO
 PEMITTED FOR SLABS.
 THIS WAS JUST A NOTE.
  
 4)NOTE: PLEASE NOTE THAT PER FS/FAC
 PLANS DENIED FOR THE SAME COMMENTS MORE
 THAN 3 TIMES ARE SUBJECT TO 4X FEE FOR
 PLAN REVIEW PORTION OF TOTAL PERMIT FEE.
 PLAN REVIEW PORTION IS ABOUT 30% OF
 ORIG PERMIT FEE. PLEASE HAVE COMMENTS
 ADDRESSED. IF A MEETING IS NEEDED OR
 OVER THE PHONE? PLEASE NOTE, AS TO DATE
 NO ONE HAS CONTACTED ME FOR ANY QUESTION
 -S OR CLARIFICATIONS IF NEEDED.
 FS 553-80.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY,,,
 QUESTIONS, PLEASE CALL....
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-03-18 Cont ID  
Sent By dpalmer Date 2002-03-18 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2002-03-18 Time 07:46 Sent To  
Notes
2002-03-18 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING OUTLET
 SPACING TO MEET 210-52. 2' OF WALLS AND
 12' OF WALLS. ONE SET WAS REDLINED.
  
 2)NOTE: PLEASE NOTE MISSING LT REQ`D FOR
 MECH CLOSET.210-70
  
 3)NOTE: PLEASE NOTE THAT ON PREVIOUS
 REVIEW IT WAS NOTED THAT EMT COULD NOT
 BE USED FOR SERVICE ENTRANCE CONDUIT.
 PLEASE NOTE THAT NOW THE APT FEEDER
 CONDUITS WERE ALSO CHANGED. PLEASE NOTE
 THAT THESE MAY BE EMT. IF RIGID IS SHOWN
 ON PLANS THEN REGID WILL BE REQ`D TO BE
 INSTALLED. PLEASE VERIFY, THIS IS JUST
 NOTED DUE TO THE EXSPENSE OF RIGID BEING
 INSTALLED FOR APT SUB FEEDS.
  
 4)NOTE: PLEASE HAVE ALL OLD E-SHEETS
 REMOVED FROM SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 21:11 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 21:11 Sent To  
Notes
2002-02-05 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT AN ELECTRICAL
 RISER DIAGRAM IS NOW BEING SUBMITTED FOR
 REVIEW. PLEASE NOTE THAT TYPE OF CONDUIT
 IS SHOWN AS EMT? PLEASE NOTE THIS IS
 NOT ALLOWED.
 2)NOTE: PLEASE NOTE SIZING OF OCP FOR
 UNITS NEED TO BE NOTED.
  
 3)NOTE: PLEASE CLARIFY ON PLANS WHERE
 THE REQ`MENTS FOR FAIR HOUSING HEIGHTS
 ARE? FHAR/CFR24 100.205
  
  
  
  
 4)NOTE: PLEASE NOTE THAT THERE WERE
 STILL SOMEOUTLETS MISSING PER 210-52
 UNIT-B ETC, WALLS AND BALCONIES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 5)NOTE: SD`S REQD AT BOTTOM OF STAIRS.
 \\NFPA-72 2-2.1.1.1.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-27 Cont ID  
Sent By dpalmer Date 2001-11-27 Time 20:49 Rev Time 0.00
Received By dpalmer Date 2001-11-27 Time 20:49 Sent To  
Notes
2001-11-27 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 PLEASE SHOW THE GROUNDING ELECTRODE
 SYSTEM.
  
 5)NOTE: PLEASE PROVIDE A ONE-LINE DIA-
 GRAM SHOWING SERVICE. PLEASE SHOW THE
 LOACTION OF SERVICE.
  
 6)NOTE: PLEASE NOTE THAT ALL HOUSE
 CONTINUOUS LOADS ARE TO BE SHOWN AT 125%
  
 7)NOTE: PLEASE NOTE STORAGE ROOM TPYES
 OF FIXTURES AND CLEARENCES PER 410-8.
  
 8)NOTE: PLEASE SHOW EXIT LTS PER FIRE
 REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
  
 PLEASE NOTE THAT NOTES 22, PLEASE NOTE
 PER LOCAL AMENDMENTS,SE, NMC CABLES ETC
 ARE NOT PERMITTED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2002-05-29 Cont ID  
Sent By mamini Date 2002-05-29 Time 10:35 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
2002-05-29 00:00:00N/A
 1. SEE PERMIT # 02050423 FOR CIVIL/SITE
 WORKS REVIEW AND PERMITTING FOR PARCEL-D
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mamini Date 2001-11-13 Time 11:08 Rev Time 1.00
Received By mamini Date 2001-11-13 Time 11:08 Sent To  
Notes
2001-11-13 00:00:00FAILED :
 1. SEE PERMIT # 01110408
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2002-10-21 Cont ID  
Sent By mcarsill Date 2002-10-21 Time 11:55 Rev Time 0.00
Received By mcarsill Date 2002-10-21 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-06-20 Cont ID  
Sent By mcarsill Date 2002-06-20 Time 11:41 Rev Time 0.00
Received By mcarsill Date 2002-06-20 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2002-05-23 Cont ID  
Sent By mcarsill Date 2002-05-23 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2002-05-23 Time 16:00 Sent To  
Notes
2002-05-23 00:00:00A MEETING APPEARS TO BE NEEDED TO
 DISCUSS ISSUES REGARDING THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-03-27 Cont ID  
Sent By mcarsill Date 2002-03-27 Time 09:59 Rev Time 0.00
Received By mcarsill Date 2002-03-27 Time 09:58 Sent To  
Notes
2002-03-27 00:00:00A) CIVIL DRAWINGS INDICATING FIRE MAIN
 LOCATIONS, SIZES AND FIRE HYDRANT
 LOCATIONS NOT YET APPROVED.
 B) REVISED MECHANICAL DRAWINGS NEED TO
 BE FURTHER CLARIFIED WITH REGARDS TO
 DRYER VENTS.
  
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 15:47 Sent To  
Notes
2002-02-12 00:00:001) CIVIL DRAWINGS ARE NEEDED FOR FIRE
 MAINS, FIRE HYDRANTS, ETC. WET FIRE
 HYDRANTS ARE REQUIRED PRIOR TO, DURING
 AND AFTER CONSTRUCTION.
 2) ARCHITECTURAL SITE MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS
 OR GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE TO
 BE A MINIMUM OF TWENTY FEET IN CLEAR
 WIDTH AND BE ABLE TO SUPPORT THE WEIGHT
 OF FIRE APPARATUS. WHAT IS THE
 DIFFERENCE BETWEEN PHASE ONE AND PHASE
 TWO.
 3) BUILDING ADDRESSES REQUIRED.
 4) PRESCRIPTIVE CODE REQUIREMENTS FOR
 ALL HANDRAILS AND GUARDRAILS SHOULD
 BE PROVIDED.
 5) PENETRATIONS SHOWN THRU RATED WALLS.
 DRYER VENTS INTO BREEZEWAYS.
 6) PLEASE INDICATE LOCATION OF THE
 FIRE ALARM CONTROL PANEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 10:37 Sent To  
Notes
2001-11-26 00:00:00SEE PLAN REVIEW NOTES FROM BUILDING
 TYPE I AND TYPE II.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:40 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 08:40 Sent To E
Notes
2003-04-29 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 16:13 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 16:13 Sent To B
Notes
2002-11-21 00:00:00TO JIM./WRT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-11-14 Cont ID  
Sent By pkrauss Date 2002-11-14 Time 12:53 Rev Time 0.45
Received By pkrauss Date 2002-11-14 Time 12:53 Sent To  
Notes
2002-11-14 00:00:00REVISIONS DENIED - SPOKEWITH TOM
 DESSOYE (EPOCH), REQUEST A SUBMITTAL LTR
 FROM THE ENG STATING WHY A DROP IN THE
 WALK-IN CLOSET IS NEEDED & REDUCTION OF
 TONNAGE IN THE A/C UNITS.DUCT MATERIAL
 & LAYOUT ARE TO BE INSTALLED AS PER THE
 APPROVED PLANS ON THE MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-11-14 Cont ID  
Sent By pkrauss Date 2002-11-14 Time 12:39 Rev Time 0.50
Received By pkrauss Date 2002-09-30 Time 11:56 Sent To  
Notes
2002-09-30 00:00:00SHEETS M3.31, M3.32, M3.33, M3.24, DUCT
 LAYOUT REVISED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-20 Cont ID  
Sent By pkrauss Date 2002-06-20 Time 16:49 Rev Time 1.00
Received By pkrauss Date 2002-06-20 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-05-14 Cont ID  
Sent By pkrauss Date 2002-05-08 Time 14:08 Rev Time 1.30
Received By pkrauss Date 2002-05-08 Time 12:36 Sent To  
Notes
2002-05-08 00:00:00PLEASE NOTE SOME OF THE MECHANICAL
 PAGES HAVE A "STAMPED" SIGNATURE FOR THE
 ENGENEER INSTEAD OF A SIGNATURE. UNDER
 THE PROVISIONS OF CHAPTER 471 OF THE
 FLORIDA STATUES ALL PAGES SHALL HAVE AN
 ORIGINAL SIGNATURE NOT A STAMP.
  
 LETTER OF RESPONSE -
  
 MECHANICAL ITEM #1
  
 "CHASE IS A FIRE RATED SHAFT COMPLYING
 WITH SMC 610.4.SEE REVISED DRAWING
 A5.12."
  
 PLAN SHEET A5.12 IS NOT IN THE TYPE III
 SUBMITTAL.HOWEVER ON PLAN SHEET A5.32
 PLAN VIEW OF DRYER VENT DUCT THROUGH
 FLOORS TO ROOF.SEE PLAN SHEET A5.32
 FOR REVISED DRAWING (ATTACHED). PLEASE
 PROVIDE WHAT RATING (1 HR, 2 HR ?).
  
 SPECIFICATION FOR SPECIFIC DRYER ALSO
 SUBMITTED INDICATING ALLOWABLE LENGTH OF
 DUCT EXCEEDING THE CODE REQUIREMENT.
 PLEASE NOTE DRYERS SHALL BE INSTALLED
 FOR FINAL INSPECTION.
  
 DETAIL FOR THE RESTROOM EXHAUST VENTING
 ON PLAN SHEET M5.33, PLEASE NOTE SHOULD
 THE ALTERNATE DISCHARGE THROUGH THE ROOF
 BE USED IT SHALL COMPLY WITH 1997 SMC
 610.4. (DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-03-13 Cont ID  
Sent By pkrauss Date 2002-03-13 Time 15:21 Rev Time 2.00
Received By pkrauss Date 2002-03-13 Time 15:21 Sent To  
Notes
2002-03-13 00:00:00 
 TYPE III
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #8 4"
 METAL DRYER EXHASUT VENT ROUTED UP IN
 CHASE & THROUGH THE ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE".DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROMDRYER LOCATION
 TO WALL OR ROOF CAP.THERE SHALL BE A
 5 FT DEDUCTION FOR EACH 90 DEGREE BEND &
 2 1/2 FT FOR EACH 45 DEGREE BEND. THE
 WALL OR ROOF CAP SHALL BE NONSCREENED
 WITH A BACK DRAFT DAMPER. 1997 SMC 610.6
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPERS AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By pkrauss Date 2002-02-06 Time 15:14 Rev Time 3.00
Received By pkrauss Date 2002-02-06 Time 12:24 Sent To  
Notes
2002-02-06 00:00:00 
 BUILDING TYPE III - PERMIT 01110412
  
  
 AS PER 2000 LIFE SAFETY CODE CHAPTER 7 -
 7.1.3.1 EXIT ACCESS CORRIDORS
  
 (E) PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ASSEMBLY
 SHALL BE PROHIBITED EXECPT FOR THE
 FOLLOWING.
  
 (1) ELECTICAL CONDUIT SERVING THE
 STAIRWAY
 (2) REQUIRED EXIT DOORS
 (3) DUCTWORK & EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION
 (4) WATER OR STEAM PIPING NECESSARY
 FOR THE HEATING OR COOLING OF THE
 EXIT ENCLOSURE
 (5) SPRINKLER PIPING
 (6) STANDPIPES
  
 ALSO AS PER 1997 SMC 610.1.2, FIRE
 DAMPERS REQUIRED WHERE DUCTS PENETRATE
 WALLS OR PARTITIONS HAVING A FIRE
 RESISTANCE RATING OF 1 OR MORE HOURS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT 8388.

Review Stop P PLUMBING
Rev No 10 Status P Date 2002-12-12 Cont ID  
Sent By kstevens Date 2002-12-12 Time 14:12 Rev Time 0.25
Received By kstevens Date 2002-12-12 Time 14:12 Sent To  
Notes
2002-12-12 00:00:00RESTAMP

Review Stop P PLUMBING
Rev No 9 Status F Date 2002-12-09 Cont ID  
Sent By kstevens Date 2002-12-07 Time 05:18 Rev Time 0.50
Received By kstevens Date 2002-12-07 Time 05:18 Sent To  
Notes
2002-12-07 00:00:00REVISION OK - CHANGED VENT THRU ROOF
 STACKS
  
 REVIEW CHANGED TO FAILED - NO CHANGES TO
 MASTER - ALL REVISIONS TO BE SUBMITTED
 FOR EACH PERMIT NUMBER.

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-09-06 Cont ID  
Sent By kstevens Date 2002-09-06 Time 10:51 Rev Time 0.00
Received By kstevens Date 2002-09-06 Time 10:51 Sent To  
Notes
2002-09-06 00:00:00REVISION OK - SHEET P5.31 SANT RISERS

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-08-28 Cont ID  
Sent By kstevens Date 2002-08-28 Time 10:03 Rev Time 0.00
Received By kstevens Date 2002-08-28 Time 10:03 Sent To  
Notes
2002-08-28 00:00:00REVISION OK - SHT P2.31 VTR

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 17:34 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 17:34 Sent To  
Notes
2002-07-22 00:00:00REVISION DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SANITARY RISERS A1, A2, B1, & B2.
 NO KITCHEN SINK OR WASH MACHINE TRAP
 SHALL BE PLACED ON A 2" COMBINED WASTE
 AND VENT. 3" WASTE AND VENT REQD.
 SECT. 911.4-SHT P5.31
  
 2) NO VENT THRU ROOF SHOWN ON ANY STACK.
 PLEASE INDICATE WHICH STACK/STACKS WILL
 VENT THRU ROOF. SHT P5.31
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-07-11 Cont ID  
Sent By kstevens Date 2002-07-11 Time 16:59 Rev Time 0.00
Received By kstevens Date 2002-07-11 Time 16:59 Sent To  
Notes
2002-07-11 00:00:00REVISION OK - CHANGED BLDG DRAIN TO ONE
 LINE.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-26 Cont ID  
Sent By kstevens Date 2002-06-26 Time 16:53 Rev Time 0.00
Received By kstevens Date 2002-06-26 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-03-13 Cont ID  
Sent By kstevens Date 2002-03-13 Time 16:43 Rev Time 0.50
Received By kstevens Date 2002-03-13 Time 16:43 Sent To  
Notes
2002-03-13 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SEE COMMENTS FROM PERMIT #01110409
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 19:39 Rev Time 0.50
Received By kstevens Date 2002-02-08 Time 19:38 Sent To  
Notes
2002-02-08 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) EXCEPT FOR COMMENT #6 WHICH IS OK ON
 TYPE III BLDG SEE COMMENTS FROM PERMIT
 #01110409.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By kstevens Date 2001-11-30 Time 15:14 Rev Time 2.00
Received By kstevens Date 2001-11-30 Time 15:14 Sent To  
Notes
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94-FHA-98 DESIGN MAN.
  
 SEE COMMENTS PERMIT #01110409


Account Summary | Usage Policy | Privacy Policy