| Plan Review Stops For Permit 01110412 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-03-25 |
Time |
16:09 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2003-03-25 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2003-03-25 00:00:00 | STORM SHUTTERS, KEY PLAN ANCHOR SCHEDULE | | | AND PROTEST TESTING REPORTS REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-21 |
Time |
16:13 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-10-03 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2002-10-03 00:00:00 | 10/3/02 REVISION: BREEZEWAY REDUCTION IN | | | LENGTH. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-09-02 |
Time |
13:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-09-02 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2002-09-02 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 01110412 | | | ADD:EPOCH/PORTOFINO/MASTER TYPE III | | | CONT: EPOCH | | | TEL: (561)683-1052 | | | STD BLD CD= 1997 STANDARD BUILDING CODE | | | | | | ******PROVISO***** | | | | | | 1) WEDGE-ALL ANCHORS DETAILS, SINCE THE | | | LOADING IS NOT GIVEN FOR TENSION OR | | | SHEAR LOAD APPLICATIONS HAS THE EDGE FAC | | | TOR (REDUCTION) BEEN FACTORED INTO THE | | | SPACING? | | | A) DETAIL "D" S_D1.1 EXTERIOR CONDITION | | | @ LOFT 2X6 WALL SITTING ON TOP OF A 5" | | | CONCRETE WALL? NO INFORMATION IS GIVEN, | | | CONTACT SIMPSON ENG TO SEE IF A DOUBLE | | | REDUCTION WOULD BE REQUIRED SINCE YOU | | | WOULD BE 2 1/2" AWAY FROM BOTH SIDES? | | | B) DETAIL# 3, 2X6 WALL AT THE EDGE OF | | | SLAB, WHAT REDUCTION HAS BEEN TAKEN? HOW | | | FAR AWAY FROM THE EDGE OF THE SLAB WILL | | | THE ANCHOR BE LOCATED? | | | | | | ADDITIONAL INFORMATION SHALL BE OBTAINED | | | TO CLARIFY THE CONDITIONS LISTED ABOVE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-30 |
Time |
07:12 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2002-04-30 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | *******BUILDING PROVISO****** | | | | | | MASTER TYPE III | | | | | | SOILS TEST REPORT INDICATES FURTHER | | | INVESTIGATION BEFORE THE PERMIT CAN BE | | | ISSUED. SHOW HOW DENSIFICATION OF SOIL | | | WILL OCCUR. | | | | | | HYDROLIC CALCS MISSING FROM PLAN. | | | | | | DESIDENT INSPECTOR TO REGISTER WITH DON | | | NEELY BEFORE PERMITS MAY BE ISSUED. | | | | | | BUILDING PLANS TO BE SUBMITTED TO P.B. | | | COUNTY FOR IMPACT FEE ASSESSMENT | | | | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-26 |
Time |
17:44 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110412 | | | BRIGER TRACT | | | BUILDING TYPE III | | | THIRD REVIEW | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | SAME COMMENTS AS TYPE I BUILDING SEE | | | 01110409. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-21 |
Time |
13:02 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-21 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK # 01110412 | | | BRIGER TRACT "D" | | | BUILDING PLAN III | | | | | | SEE COMMENTS ON01110409 | | | | | | J.WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-14 |
Time |
13:53 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-12-14 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2001-12-14 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110412 | | | BRIGER TRACT "D" | | | BUILDINGTYPE III | | | | | | FLOOR AREA: | | | 1ST FL9,523 SQ FT | | | 2ND FL9,392 SQ FT | | | 3RD FL9,392 SQ FT | | | LOFT 2,556 SQ FT | | | TOTAL30,863 SQ FT | | | | | | | | | | | | SEE PLAN REVIEW 01110409 FOR NOTES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-29 |
Time |
13:08 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-04-29 |
Time |
12:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-29 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-14 |
Time |
17:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-19 |
Time |
19:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-19 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2002-06-19 00:00:00 | ************* NOTE ******************* | | | REDLINED ON PLANS, PERMITS APPLIED FOR | | | AFTER JAN 1ST 2002, REQ`D ARC FAULT | | | PROTECTIONPER 210-12. 99 NEC. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-13 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-13 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2002-06-13 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE SAME NOTES AS BEFORE | | | . |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-05-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-09 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-09 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2002-05-09 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT E-SHEETS DO | | | NOT HAVE AN ORIGINAL SIGNATURE FROM | | | THE ARCH/ENGINEER OF RECORD. PLEASE | | | NOTE THAT PER FS/FAC MUST BE AN ORIG | | | SIGNATURE. 471.025/481.221. | | | | | | 2)NOTE: PLEASE NOTE, OUTLET SPACING FOR | | | BALCONY/LOFT UNITS, STILL DO NOT MEET | | | 210-52. PLEASE NOTE RAIL AREAS ARE STILL | | | CONSIDERED 'WALL SPACE'. 210-52 ALSO | | | INCLUDES COUNTERSPACE IN KITCHENS... | | | PLEASE SEE 210-52C-1. | | | PLEASE SEE 210-52A 1-2-3. | | | | | | | | | | | | | | | 3)NOTE: PLEASE NOTE THAT PLANS KEEP | | | GOING BACK AND FORTH FOR CONDUIT TYPE | | | FOR FEEDERS TO UNITS. EMT IS PERMITTED | | | ONLY IN EXPOSED ARES ABOVE GROUND. IF | | | ANY OF THESE FEEDERS ARE IN THE SLAB OR | | | POURED IN CONCRETE, DIRECT CONTACT WITH | | | EARTH ETC. 348-5 | | | PLEASE NOTE THAT PREVIOUS NOTE FOR THIS | | | ITEM WAS THAT PLANS SHOWED "RIGID" | | | CONDUIT AND ITS EXPENSE. PVC IS ALSO | | | PEMITTED FOR SLABS. | | | THIS WAS JUST A NOTE. | | | | | | 4)NOTE: PLEASE NOTE THAT PER FS/FAC | | | PLANS DENIED FOR THE SAME COMMENTS MORE | | | THAN 3 TIMES ARE SUBJECT TO 4X FEE FOR | | | PLAN REVIEW PORTION OF TOTAL PERMIT FEE. | | | PLAN REVIEW PORTION IS ABOUT 30% OF | | | ORIG PERMIT FEE. PLEASE HAVE COMMENTS | | | ADDRESSED. IF A MEETING IS NEEDED OR | | | OVER THE PHONE? PLEASE NOTE, AS TO DATE | | | NO ONE HAS CONTACTED ME FOR ANY QUESTION | | | -S OR CLARIFICATIONS IF NEEDED. | | | FS 553-80. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. ONCE AGAIN, IF THERE ARE ANY,,, | | | QUESTIONS, PLEASE CALL.... | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-18 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-18 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2002-03-18 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLET | | | SPACING TO MEET 210-52. 2' OF WALLS AND | | | 12' OF WALLS. ONE SET WAS REDLINED. | | | | | | 2)NOTE: PLEASE NOTE MISSING LT REQ`D FOR | | | MECH CLOSET.210-70 | | | | | | 3)NOTE: PLEASE NOTE THAT ON PREVIOUS | | | REVIEW IT WAS NOTED THAT EMT COULD NOT | | | BE USED FOR SERVICE ENTRANCE CONDUIT. | | | PLEASE NOTE THAT NOW THE APT FEEDER | | | CONDUITS WERE ALSO CHANGED. PLEASE NOTE | | | THAT THESE MAY BE EMT. IF RIGID IS SHOWN | | | ON PLANS THEN REGID WILL BE REQ`D TO BE | | | INSTALLED. PLEASE VERIFY, THIS IS JUST | | | NOTED DUE TO THE EXSPENSE OF RIGID BEING | | | INSTALLED FOR APT SUB FEEDS. | | | | | | 4)NOTE: PLEASE HAVE ALL OLD E-SHEETS | | | REMOVED FROM SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-05 |
Time |
21:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-05 |
Time |
21:11 |
Sent To |
|
|
| Notes |
| 2002-02-05 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT AN ELECTRICAL | | | RISER DIAGRAM IS NOW BEING SUBMITTED FOR | | | REVIEW. PLEASE NOTE THAT TYPE OF CONDUIT | | | IS SHOWN AS EMT? PLEASE NOTE THIS IS | | | NOT ALLOWED. | | | 2)NOTE: PLEASE NOTE SIZING OF OCP FOR | | | UNITS NEED TO BE NOTED. | | | | | | 3)NOTE: PLEASE CLARIFY ON PLANS WHERE | | | THE REQ`MENTS FOR FAIR HOUSING HEIGHTS | | | ARE? FHAR/CFR24 100.205 | | | | | | | | | | | | | | | 4)NOTE: PLEASE NOTE THAT THERE WERE | | | STILL SOMEOUTLETS MISSING PER 210-52 | | | UNIT-B ETC, WALLS AND BALCONIES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 5)NOTE: SD`S REQD AT BOTTOM OF STAIRS. | | | \\NFPA-72 2-2.1.1.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-27 |
Time |
20:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-27 |
Time |
20:49 |
Sent To |
|
|
| Notes |
| 2001-11-27 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | PLEASE SHOW THE GROUNDING ELECTRODE | | | SYSTEM. | | | | | | 5)NOTE: PLEASE PROVIDE A ONE-LINE DIA- | | | GRAM SHOWING SERVICE. PLEASE SHOW THE | | | LOACTION OF SERVICE. | | | | | | 6)NOTE: PLEASE NOTE THAT ALL HOUSE | | | CONTINUOUS LOADS ARE TO BE SHOWN AT 125% | | | | | | 7)NOTE: PLEASE NOTE STORAGE ROOM TPYES | | | OF FIXTURES AND CLEARENCES PER 410-8. | | | | | | 8)NOTE: PLEASE SHOW EXIT LTS PER FIRE | | | REVIEW COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | | | | PLEASE NOTE THAT NOTES 22, PLEASE NOTE | | | PER LOCAL AMENDMENTS,SE, NMC CABLES ETC | | | ARE NOT PERMITTED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-05-29 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | N/A | | | 1. SEE PERMIT # 02050423 FOR CIVIL/SITE | | | WORKS REVIEW AND PERMITTING FOR PARCEL-D | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-13 |
Time |
11:08 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-11-13 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | FAILED : | | | 1. SEE PERMIT # 01110408 | | | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-21 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-21 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-20 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-20 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2002-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-23 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-23 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2002-05-23 00:00:00 | A MEETING APPEARS TO BE NEEDED TO | | | DISCUSS ISSUES REGARDING THE PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-27 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-27 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | A) CIVIL DRAWINGS INDICATING FIRE MAIN | | | LOCATIONS, SIZES AND FIRE HYDRANT | | | LOCATIONS NOT YET APPROVED. | | | B) REVISED MECHANICAL DRAWINGS NEED TO | | | BE FURTHER CLARIFIED WITH REGARDS TO | | | DRYER VENTS. | | | | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-12 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2002-02-12 00:00:00 | 1) CIVIL DRAWINGS ARE NEEDED FOR FIRE | | | MAINS, FIRE HYDRANTS, ETC. WET FIRE | | | HYDRANTS ARE REQUIRED PRIOR TO, DURING | | | AND AFTER CONSTRUCTION. | | | 2) ARCHITECTURAL SITE MATRIX DOES NOT | | | INDICATE ANY FIRE HYDRANT LOCATIONS. | | | ALSO IT APPEARS THAT SECURITY ARMS | | | OR GATES ARE BEING PROVIDED. WHAT | | | PROVISIONS ARE MADE FOR FIRE RESCUE | | | ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN | | | LOSS OF POWER OCCURS. ALL ROADS ARE TO | | | BE A MINIMUM OF TWENTY FEET IN CLEAR | | | WIDTH AND BE ABLE TO SUPPORT THE WEIGHT | | | OF FIRE APPARATUS. WHAT IS THE | | | DIFFERENCE BETWEEN PHASE ONE AND PHASE | | | TWO. | | | 3) BUILDING ADDRESSES REQUIRED. | | | 4) PRESCRIPTIVE CODE REQUIREMENTS FOR | | | ALL HANDRAILS AND GUARDRAILS SHOULD | | | BE PROVIDED. | | | 5) PENETRATIONS SHOWN THRU RATED WALLS. | | | DRYER VENTS INTO BREEZEWAYS. | | | 6) PLEASE INDICATE LOCATION OF THE | | | FIRE ALARM CONTROL PANEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-26 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-26 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | SEE PLAN REVIEW NOTES FROM BUILDING | | | TYPE I AND TYPE II. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-29 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-29 |
Time |
08:40 |
Sent To |
E |
|
| Notes |
| 2003-04-29 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-21 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-21 |
Time |
16:13 |
Sent To |
B |
|
| Notes |
| 2002-11-21 00:00:00 | TO JIM./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-14 |
Time |
12:53 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-11-14 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2002-11-14 00:00:00 | REVISIONS DENIED - SPOKEWITH TOM | | | DESSOYE (EPOCH), REQUEST A SUBMITTAL LTR | | | FROM THE ENG STATING WHY A DROP IN THE | | | WALK-IN CLOSET IS NEEDED & REDUCTION OF | | | TONNAGE IN THE A/C UNITS.DUCT MATERIAL | | | & LAYOUT ARE TO BE INSTALLED AS PER THE | | | APPROVED PLANS ON THE MASTER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-14 |
Time |
12:39 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-09-30 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2002-09-30 00:00:00 | SHEETS M3.31, M3.32, M3.33, M3.24, DUCT | | | LAYOUT REVISED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-20 |
Time |
16:49 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-06-20 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-08 |
Time |
14:08 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2002-05-08 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2002-05-08 00:00:00 | PLEASE NOTE SOME OF THE MECHANICAL | | | PAGES HAVE A "STAMPED" SIGNATURE FOR THE | | | ENGENEER INSTEAD OF A SIGNATURE. UNDER | | | THE PROVISIONS OF CHAPTER 471 OF THE | | | FLORIDA STATUES ALL PAGES SHALL HAVE AN | | | ORIGINAL SIGNATURE NOT A STAMP. | | | | | | LETTER OF RESPONSE - | | | | | | MECHANICAL ITEM #1 | | | | | | "CHASE IS A FIRE RATED SHAFT COMPLYING | | | WITH SMC 610.4.SEE REVISED DRAWING | | | A5.12." | | | | | | PLAN SHEET A5.12 IS NOT IN THE TYPE III | | | SUBMITTAL.HOWEVER ON PLAN SHEET A5.32 | | | PLAN VIEW OF DRYER VENT DUCT THROUGH | | | FLOORS TO ROOF.SEE PLAN SHEET A5.32 | | | FOR REVISED DRAWING (ATTACHED). PLEASE | | | PROVIDE WHAT RATING (1 HR, 2 HR ?). | | | | | | SPECIFICATION FOR SPECIFIC DRYER ALSO | | | SUBMITTED INDICATING ALLOWABLE LENGTH OF | | | DUCT EXCEEDING THE CODE REQUIREMENT. | | | PLEASE NOTE DRYERS SHALL BE INSTALLED | | | FOR FINAL INSPECTION. | | | | | | DETAIL FOR THE RESTROOM EXHAUST VENTING | | | ON PLAN SHEET M5.33, PLEASE NOTE SHOULD | | | THE ALTERNATE DISCHARGE THROUGH THE ROOF | | | BE USED IT SHALL COMPLY WITH 1997 SMC | | | 610.4. (DUCTS PENETRATING MORE THAN 1 | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-13 |
Time |
15:21 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2002-03-13 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2002-03-13 00:00:00 | | | | TYPE III | | | | | | DRYER EXHAUST FOR THE INTERIOR | | | APARTMENTS - HVAC SHEET NOTES - #8 4" | | | METAL DRYER EXHASUT VENT ROUTED UP IN | | | CHASE & THROUGH THE ROOF.PLEASE | | | PROVIDE DETAIL OF "CHASE".DUCTS | | | EXTENDING THROUGH MORE THAN ONE FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4. | | | | | | PLEASE NOTE, THE MAXIMUM LENGTH SHALL | | | NOT EXCEED 25 FT FROMDRYER LOCATION | | | TO WALL OR ROOF CAP.THERE SHALL BE A | | | 5 FT DEDUCTION FOR EACH 90 DEGREE BEND & | | | 2 1/2 FT FOR EACH 45 DEGREE BEND. THE | | | WALL OR ROOF CAP SHALL BE NONSCREENED | | | WITH A BACK DRAFT DAMPER. 1997 SMC 610.6 | | | | | | BATHROOM EXHAUST - WALL CAP SHALL BE | | | SCREENED.PLEASE INDICATE ACCESS FOR | | | THE FIRE DAMPERS AS PER 1997 SMC 610.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-06 |
Time |
15:14 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2002-02-06 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | | | | BUILDING TYPE III - PERMIT 01110412 | | | | | | | | | AS PER 2000 LIFE SAFETY CODE CHAPTER 7 - | | | 7.1.3.1 EXIT ACCESS CORRIDORS | | | | | | (E) PENETRATIONS INTO AND OPENINGS | | | THROUGH AN EXIT ENCLOSURE ASSEMBLY | | | SHALL BE PROHIBITED EXECPT FOR THE | | | FOLLOWING. | | | | | | (1) ELECTICAL CONDUIT SERVING THE | | | STAIRWAY | | | (2) REQUIRED EXIT DOORS | | | (3) DUCTWORK & EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION | | | (4) WATER OR STEAM PIPING NECESSARY | | | FOR THE HEATING OR COOLING OF THE | | | EXIT ENCLOSURE | | | (5) SPRINKLER PIPING | | | (6) STANDPIPES | | | | | | ALSO AS PER 1997 SMC 610.1.2, FIRE | | | DAMPERS REQUIRED WHERE DUCTS PENETRATE | | | WALLS OR PARTITIONS HAVING A FIRE | | | RESISTANCE RATING OF 1 OR MORE HOURS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-12 |
Time |
14:12 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-12 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | RESTAMP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-07 |
Time |
05:18 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-12-07 |
Time |
05:18 |
Sent To |
|
|
| Notes |
| 2002-12-07 00:00:00 | REVISION OK - CHANGED VENT THRU ROOF | | | STACKS | | | | | | REVIEW CHANGED TO FAILED - NO CHANGES TO | | | MASTER - ALL REVISIONS TO BE SUBMITTED | | | FOR EACH PERMIT NUMBER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-06 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-06 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2002-09-06 00:00:00 | REVISION OK - SHEET P5.31 SANT RISERS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2002-08-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-28 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-28 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2002-08-28 00:00:00 | REVISION OK - SHT P2.31 VTR |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2002-07-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-22 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-22 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2002-07-22 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SANITARY RISERS A1, A2, B1, & B2. | | | NO KITCHEN SINK OR WASH MACHINE TRAP | | | SHALL BE PLACED ON A 2" COMBINED WASTE | | | AND VENT. 3" WASTE AND VENT REQD. | | | SECT. 911.4-SHT P5.31 | | | | | | 2) NO VENT THRU ROOF SHOWN ON ANY STACK. | | | PLEASE INDICATE WHICH STACK/STACKS WILL | | | VENT THRU ROOF. SHT P5.31 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-07-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-11 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-11 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2002-07-11 00:00:00 | REVISION OK - CHANGED BLDG DRAIN TO ONE | | | LINE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-06-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-26 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-26 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-13 |
Time |
16:43 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-03-13 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2002-03-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA AMEND-98 DESIGN | | | MANUAL | | | | | | 1) SEE COMMENTS FROM PERMIT #01110409 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
19:39 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
19:38 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA AMEND-98 DESIGN | | | MANUAL | | | | | | 1) EXCEPT FOR COMMENT #6 WHICH IS OK ON | | | TYPE III BLDG SEE COMMENTS FROM PERMIT | | | #01110409. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-30 |
Time |
15:14 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2001-11-30 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2001-11-30 00:00:00 | DENIED | | | REFERENCE: SPC-94-FHA-98 DESIGN MAN. | | | | | | SEE COMMENTS PERMIT #01110409 |
|
|