Plan Review Details - Permit 01110411
Plan Review Stops For Permit 01110411
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2003-03-25 Cont ID  
Sent By jwitmer Date 2003-03-25 Time 16:06 Rev Time 1.00
Received By jwitmer Date 2003-03-25 Time 16:06 Sent To  
Notes
2003-03-25 00:00:00STORM SHUTTER
 TYPE II BLDG
 STORM SHUTTERS, KEY PLAN AND ANCHOR
 SCHEDULE REVIEWED
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2002-10-03 Cont ID  
Sent By jwitmer Date 2002-10-03 Time 08:18 Rev Time 1.00
Received By jwitmer Date 2002-10-03 Time 08:18 Sent To  
Notes
2002-10-03 00:00:0010/3/03 REVISION: BREEZEWAY REDUCTION IN
 LENGTH BY VARIANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-09-02 Cont ID  
Sent By jwitmer Date 2002-09-02 Time 12:19 Rev Time 2.00
Received By jwitmer Date 2002-09-02 Time 11:20 Sent To  
Notes
2002-09-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01110411
 ADD:EPOCH/PORTOFINO/MASTER TYPE II
 CONT: EPOCH
 TEL: (561)683-1052
 ST BLD CD = 1997 STANDARD BUILDING CODE
  
 *****PROVISO******
  
 1) WEDGE-ALL ANCHOR DETAILS, SINCE THE
 LOADING IS NOT GIVEN FOR TENSION OR
 SHEAR LOAD APPLICATIONS, HAS THE EDGE
 FACTOR (REDUCTION) BEEN FACTORED INTO
 THE SPACING?
 A) DETAIL"D" S-D1.1 EXTERIOR CONDITION
 @ LOFT 2X6 WALL SITTING ON TOP OF A 5"
 CONCRETE WALL? NO INFORMATION IS GIVEN,
 CONTACT SIMPSON ENG. TO SEE IF A DOUBLE
 REDUCTION WOULD BE REQUIRED SINCE YOU
 WOULD BE 2 1/2" AWAY ON BOTH SIDES?
 B) DETAIL# 3 2X6 WALL AT EDGE OF SLAB,
 WHAT REDUCTION HAS BEEN TAKEN? HOW FAR
 AWAY FROM THE EDGE OF THE SLAB SHALL THE
 WEDGE ANCHOR BE LOCATED?
  
 ADDITIONAL INFORMATION SHALL BE OBTAINED
 TO CLARIFY THE CONDITIONS LISTED ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-06-25 Cont ID  
Sent By jwitmer Date 2002-06-25 Time 17:26 Rev Time 3.00
Received By jwitmer Date 2002-06-25 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-04-30 Cont ID  
Sent By jwitmer Date 2002-04-30 Time 06:41 Rev Time 1.25
Received By jwitmer Date 2002-04-30 Time 06:41 Sent To  
Notes
2002-04-30 00:00:00*******BUILDING PROVISO********
  
 MASTER TYPE II
  
 SOILS TEST REPORT INDICATES FURTHER
 INVESTIGATION BEFORE THE PERMIT CAN BE
 ISSUED. SHOW HOW DENSIFICATION OF SOIL
 WILL OCCUR.
  
 HYDROLIC CALCS MISSING FROM PLAN.
 RESIDENT INSPECTOR
 TO REGISTER WITH DON NEELY
  
 BUILDING PLANS TO BE SUBMITTED TO
 COUNTY FOR IMPACT FEES
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-03-26 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 17:41 Rev Time 0.00
Received By jwitmer Date 2002-04-30 Time 06:41 Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110411
 BRIGER TRACT "D"
 BUILDING TYPE II
 THIRD REVIEW
  
 SBC= 1997 STANDARD BUILDING CODE
  
 SAME COMMENTS AS TYPE I BUILDING SEE
 01110409

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-21 Cont ID  
Sent By jwitmer Date 2002-02-21 Time 12:56 Rev Time 2.00
Received By jwitmer Date 2002-02-21 Time 12:56 Sent To  
Notes
2002-02-21 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK # 01110411
 BRIGER TRACT "D"
 BUILDING TYPE II
 SEE COMMENTS ON 01110409
  
 J. WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-14 Cont ID  
Sent By jwitmer Date 2001-12-14 Time 13:33 Rev Time 4.50
Received By jwitmer Date 2001-12-14 Time 13:33 Sent To  
Notes
2001-12-14 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110411
 BRIGER TRACT "D"
 BUILDING TYPE II
  
 FLOOR AREA:
 1ST FL 9,365 SQ FT
 2ND FL 9,413 SQ FT
 3RD FL 9,413 SQ FT
 LOFT2,556 SQ FT
 TOTAL 30,747 SQ FT
  
  
 SEE COMMENTS LISTED UNDER REVIEW:
 01110409JW

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2003-04-29 Cont ID  
Sent By btrobaug Date 2003-04-29 Time 12:41 Rev Time 1.00
Received By btrobaug Date 2003-04-29 Time 12:41 Sent To  
Notes
2003-04-29 00:00:00 
 THIS REV CHANGES FROM CU TO AL FEEDERS@
 240 FROM 208V./WRT.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-11-14 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:42 Rev Time 0.00
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 20:06 Sent To  
Notes
2002-06-19 00:00:00************** NOTE *************
  
 PLANS REDLINED, PERMIT APPLIED FOR AFTER
 JAN 1ST 2002, REQ`D TO MEET 210-12 "99"
 NEC.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-06-13 Cont ID  
Sent By dpalmer Date 2002-06-13 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2002-06-13 Time 10:59 Sent To  
Notes
2002-06-13 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE SAME NOTES/COMMENTS
 FROM OTHER REVIEWS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-05-10 Cont ID  
Sent By dpalmer Date 2002-05-10 Time 06:21 Rev Time 0.00
Received By dpalmer Date 2002-05-10 Time 06:21 Sent To  
Notes
2002-05-10 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS HAVE
 ORIGINAL WET SIGNATURE PER FS/FAC
 FOR ARCH/ ENGINEERS. 471.025/481.221
  
 2)NOTE: PLEASE NOTE PLANS STILL DO NOT
 MEET 210-52. PLEASE NOTE 210-52A 1,2,3
 FOR WALL SPACE. 210-52C-1 FOR KITCHEN
 WALL SPACE.
 RAIL AREAS ARE CONSIDERED WALL SPACE.
  
 3)NOTE: PLEASE NOTE THAT PER FS/FAC
 DESIGNE PROFESSIONALS ARE SUBJECT TO
 4XFEE FOR PLANS HAVING THE SAME
 COMMENTS FOR MORETHAN 3 TIMES.
 553-80 2BPORTION OF PLAN REVIEW FEE.
  
 4)NOTE: PLEASE NOTE PLANS HAVE GONE BACK
 AND FORTH IN REF TO RIGID AND EMT
 BEING INSTALLED. PLEASE NOTE THAT PER
 LOCAL AMEDMENTS 348-5, ENT SHALL NOT
 BE USED POURED IN CONCRETE, SLAB/DIRECT
 CONTACT WITH EARTH ETC. PLEASE NOTE THAT
 PREVIOUS NOTE WAS JUST A NOTE. PLEASE
 NOTE THAT RIGID, PVC AND IMC MAY BE
 USED. PLEASE SEE LOCAL AMENDMENTS.
  
 PLEASE NOTE IF A MEETING IS REQ`D OR
 A CONFERENCE CALL TO OVER ANY QUESTIONS,
 OR TO CLARFIY ANYTHING, PLEASE CALL.
 AS TO DATE, NO ONE HAS CALLED TO CLARIFY
 ANYTHNG.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-03-18 Cont ID  
Sent By dpalmer Date 2002-03-18 Time 06:08 Rev Time 0.00
Received By dpalmer Date 2002-03-18 Time 06:08 Sent To  
Notes
2002-03-18 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 STILL NEEDS TO MEET 210-52. MISSING IN
 BEDROOMS OF 2' OF WALL. MISSING ON
 LOFT/BALCONY AREAS, 12' OF WALL SPACE.
  
 2)NOTE: PLEASE NOTE THAT COMMENT WAS
 MADE ON PREVIOUS COMMETS OF USING EMT
 AS SERVICE ENTRANCE CONDUIT. IT HAS BEEN
 NOTED THAT ALL FEEDER CONDUITS FROM
 METER CENTER HAVE NOW BEEN CHANGED TO
 RIGID ALONG WITH SEC`S. PLEASE NOTE THAT
 IF PLANS SHOW RIGID FOR FEEDER, THEN
 RIGID WILL BE REQ`D TO BE INSTALLED.
 THIS IS JUST A NOTE TO VERFIY EXSPENSE?
  
 3)NOTE: PLEASE HAVE ALL OLD E-SHEETS
 REMOVED FROM PLANS BEFORE RESUBMITTING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 4)NOTE: PLEASE NOTE UPSTAIRS MECH ROOM
 AND MISSING LT REQ`D PER 210-70.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 21:30 Sent To  
Notes
2002-02-06 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET 210-52. PLEASE NOTE LOCATION STILL
 MISSING. BALCONY/BEDROOM ENTRANCE WALLS
  
 2)NOTE: PLEASE NOTE THAT NOW A RISER
 DIAGRAM IS SUBMITTED FOR REVIEW, PLEASE
 NOTE THAT SERVICE ENTRANCE CONDUIT IS
 SHOWN AS EMT? THIS IS NOT PERMITTED.
  
 3)NOTE: PLEASE CLARIFY WHERE THE FHAR
 ARE SHOWN ON THE PLANS.24 CFR 100.205
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 4)NOTE: PLEASE NOTE SD`S REQ`D AT BOTTOM
 OF STAIRS. NFPA-72 2-2.1.1.1
  
  
 5)NOTE: PLEASE NOTE THAT OCP NEEDS TO
 BE SHOWN FOR EACH UNIT. CAN BE TYPICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 13:43 Sent To  
Notes
2001-11-28 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MISSING EXITS LTS.
 PER FIRE REVIEW.
  
 2)NOTE: PLEASE CLARIFY FIXTURES/CLEAR-
 -ENCES PER 410-8 FOR STORAGE ROOM LTS.
  
 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% FOR HOUSE
 PANELS.215-2,-3, 230-42
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 SIZE PER 250-66
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW THE REQ`MENTS FOR FHAR,24CFR
 100.205.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE THE PER LOCAL AMENDMENTS
 SE,NMC ETC IN NOTES (22) MAYNOT
 BE USED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2002-05-29 Cont ID  
Sent By mamini Date 2002-05-29 Time 10:32 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
2002-05-29 00:00:00N/A
 1. SEE PERMIT # 02050423 FOR CIVIL/SITE
 WORKS REVIEW AND PERMITTING FOR PARCEL-D
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mamini Date 2001-11-13 Time 11:04 Rev Time 1.00
Received By mamini Date 2001-11-13 Time 11:03 Sent To  
Notes
2001-11-13 00:00:00FAILED :
 1. SEE PERMIT # 01110408
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-10-21 Cont ID  
Sent By mcarsill Date 2002-10-21 Time 11:51 Rev Time 0.00
Received By mcarsill Date 2002-10-21 Time 11:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-06-20 Cont ID  
Sent By mcarsill Date 2002-06-20 Time 11:41 Rev Time 0.00
Received By mcarsill Date 2002-06-20 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-03-27 Cont ID  
Sent By mcarsill Date 2002-03-27 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2002-03-27 Time 10:40 Sent To  
Notes
2002-03-27 00:00:00A) CIVIL DRAWINGS INDICATING FIRE MAIN
 LOCATIONS, SIZES AND FIRE HYDRANT
 LOCATIONS HAVE NOT YET BEEN APPROVED.
 B) MORE DETAILS REQUIRED ON DRYER VENT
 TERMINATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 16:54 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 16:54 Sent To  
Notes
2002-02-12 00:00:001) CIVIL DRAWINGS ARE NEEDED FOR FIRE
 MAINS AND FIRE HYDRANTS. WET FIRE
 HYDRANTS ARE REQUIRED PRIOR TO, DURING
 AND AFTER CONSTRUCTION.
 2) ARCHITECTURAL SITE MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS OR
 GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE
 TO BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH AND BE ABLE TO SUPPORT FIRE
 APPARATUS. WHAT IS THE DIFFERENCE
 BETWEEN PHASE ONE AND PHASE TWO.
 3) BUIDLING ADDRESSES REQUIRED.
 4) DOORS APPEAR TO OPPOSE EACH OTHER
 NEAR THE GARAGE.
 5) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GAURDRAILS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 10:20 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 10:20 Sent To  
Notes
2001-11-26 00:00:001) IT DEPENDS WHEN THE BUILDING IS
 OFFICIALLY SUBMITTED FOR PERMITS AS
 TO WHAT FIRE CODE THE BUILDING WILL
 BE REVIEWED UNDER. JANUARY 1, 2002, THE
 FIRE PREVENTION CODE WILL BE APPLICABLE
 WHICH INVOKES THE 2000 LIFE SAFETY CODE.
 2) BUILDING ADDRESS REQUIRED.
 3) SITE PLAN FOR FIRE PROTECTION
 DRAWINGS DOES NOT INDICATE STREET NAMES.
 4) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER PLANS.
 5) ILLUMINATED EXIT SIGNS NOT SHOWN ON
 ELECTRICAL DRAWINGS, FLOOR PLANS.
 6) FIRE DEPARTMENT CONNECTIONS TO BE
 LOCATED NE FARTHER THAN 150 FEET TO
 FIRE HYDRANTS.
 7) THE CITY OF RALEIGH NOTED ON PAGE
 F1.11.
 8) TRAVEL DISTANCE UNDER THE 1985
 EDITION OF THE LIFE SAFETY CODE ALLOWS
 ONLY 150 FEET IN SPRINKLERED APARTMENT
 BUILDINGS.
 9) PLEASE EXPLAIN USE OF LOFTS.
 10) GARAGE DOORS SHOWN ON PAGE A2.11
 APPEAR TO INTERSECT WITH ONE ANOTHER.
 11) WHAT FIRE RATING IS PRESENT FOR THE
 ALCOVES FROM THE GARAGE AND STORAGE
 AREAS.
 12) IS THERE ANY FIRE SEPARATION FOR
 THE STORAGE ROOMS.
 13) PLEASE INDICATE HEADROOM CLEARANCES
 FOR THE MEANS OF EGRESS AREAS.
 14) NO DIAGONAL DISTANCES SHOWN ON
 LS1.21.
 15) DRYER EXHAUST VENTS APPEAR TO
 PENETRATE EXIT CORRIDORS AND ONE HOUR
 WALLS.
 16) NO RATINGS PRESENT ON DOOR SCHEDULE
 FOR GARAGE DOORS WHICH APPEAR TO BE
 PART OF EXIT ACCESS AND COMMUNICATES
 WITH EXIT.
 17) FIRE PROTECTION APPEARS TO RUN
 UNDERNEATH THE BUILDING LIKE TYPE 1.
 THIS ARRANGEMENT IS NOT PERMITTED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:42 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 08:42 Sent To E
Notes
2003-04-29 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-11-14 Cont ID  
Sent By pkrauss Date 2002-11-14 Time 12:50 Rev Time 0.45
Received By pkrauss Date 2002-11-14 Time 12:49 Sent To  
Notes
2002-11-14 00:00:00REVISIONS DENIED - SPOKE WITH TOM
 DESSOYE (EPCOH), REQUEST A SUBMITTAL LTR
 FROM THE ENG STATING WHY A DROP IN THE
 WALK-IN CLOSET IS NEEDED & REDUCTION OF
 TONNAGE IN THE A/C UNITS.DUCT MATERIAL
 & LAYOUT ARE TO BE INSTALLED AS PER THE
 APPROVED PLANS ON THE MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-30 Time 08:37 Rev Time 1.00
Received By pkrauss Date   Time   Sent To  
Notes
2002-09-30 00:00:00PLAN SHEET M3.21, M3.22, M3.23, & M3.24
 REVISION TO DUCT LAYOUT.PLAN SHEET
 M5.23 CORRECTED REVISION NOTES - PRIOR
 SUBMITTAL HAD (2) REV #4.
  
 ALL OTHER PAGES SUBMITTED HAD NO CHANGES
 TOM DESSOYE WILL PULL ALL PAGES WITH NO
 CHANGES.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-25 Cont ID  
Sent By jwitmer Date 2002-06-25 Time 17:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-25 00:00:00MASTER SAME REVIEW TYPE I BLDG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-05-14 Cont ID  
Sent By pkrauss Date 2002-05-14 Time 10:43 Rev Time 1.00
Received By pkrauss Date 2002-05-14 Time 10:40 Sent To  
Notes
2002-05-14 00:00:00PLEASE NOTE SOME OF THE MECHANICAL PAGES
 HAVE A "STAMPED" SIGNATURE FOR THE
 ENGINEER INSTEAD OF A SIGNATURE.UNDER
 THE PROVISIONS OF CHAPTER 471 OF THE
 FLORIDA STATUES, ALL PAGES SHALL HAVE
 AN ORIGINAL SIGNATURE NOT A STAMP.
  
 LETTER OF RESPONSE - MECHANICAL ITEM #1
  
 "CHASE IS A FIRE RATED SHAFT COMPLYING
 WITH SMC 610.4.SEE REVISED DRAWING
 A512."
  
 PLAN SHEET A5.12 IS NOT IN THE TYPE II
 SUBMITTAL.HOWEVER ON PLAN SHEET A5.22
 PLAN VIEW OF DRYER VENT DUCT THROUGH
 FLOORS TO ROOF.SEE PLAN SHEET A.522
 FOR REVISED DRAWING (ATTACHED).PLEASE
 PROVIDE THE RATING OF THE "CHASE" (1HR,
 2HR?).
  
 PLAN SHEET M5.23 NOTE #6 (DRYER VENT)
 REFERENCES A SBCC 610.1.3.3.NO SUCH
 CODE.PLEASE CORRECT.
  
 SPECIFICATION FOR SPECIFIC DRYER SALO
 SUBMITTED INDICATING ALLOWABLE LENGTH
 OF DUCT EXCEEDING THE CODE REUQIREMENT.
 PLEASE NOTE DRYERS SHALL BE INSTALLED
 FOR FINAL INPSPECTION.
  
 DETAIL FOR THE RESTROOM EXHASUT VENTING
 ON PLAN SHEET M5.33, PLEASE NOTE SHOULD
 THE ALTERNATE DISCHARGE THROUGH THE ROOF
 BE USED IT SHALL COMPLY WITH 1997 SMC
 610.4 (DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-03-13 Cont ID  
Sent By pkrauss Date 2002-03-13 Time 16:42 Rev Time 2.00
Received By pkrauss Date 2002-03-13 Time 16:42 Sent To  
Notes
2002-03-13 00:00:00 
 TYPE II
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #8 4"
 METAL DRYER EXHAUST VENT ROUTED UP IN
 CHASE & THROUGH TH ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE". DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROM DRYER LOCATION TO
 WALL OR ROOF CAP. THERE SHALL BE A 5 FT
 DEDUCTIONS FOR EACH 90 DEGREE BEND & 2
 1/2 FT FOR A 45 DEGREE BEND.THE WALL
 OR ROOF CAP SHALL BE NONSCREENED WITH
 BACK DRAFT DAMPER. 1997 SMC 509.3.
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPERS AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By pkrauss Date 2002-02-06 Time 16:29 Rev Time 0.00
Received By pkrauss Date 2002-02-06 Time 16:29 Sent To  
Notes
2002-02-06 00:00:00 
 BUILDING TYPE II - PERMIT 01110411
  
 AS PER 2000 LIFE SAFETY CODE CHAPTER 7 -
 7.1.3.1 EXIT ACCESS CORRIDORS
  
 (E) PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ASSEMBLY
 SHALL BE PROHIBITED EXCEPT FOR THE
 FOLLOWING.
  
 (1) ELECTRICAL CONDUIT SERVING THE
 STAIRWAY
 (2) REQUIRED EXIT DOORS
 (3) DUCTWORK & EQUIPMENT NECESSARY FOR
 INDEPENDNET STAIR PRESSURIZATION
 (4) WATER OR STEAM PIPING NECESSARY
 FOR THE HEATING OR COOLING OF THE
 EXIT ENCLOSURE
 (5) SPRINKLER PIPING
 (6) STANDPIPES
  
 ALSO AS PER 1997 SMC 610.1.2, FIRE
 DAMPERS REQUIRED WHERE DUCTS PENETRATE
 WALLS OR PARTITIONS HAVING A FIRE
 RESISTANCE RATING OF 1 OR MORE HOURS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 10 Status P Date 2002-12-12 Cont ID  
Sent By kstevens Date 2002-12-12 Time 14:11 Rev Time 0.25
Received By kstevens Date 2002-12-12 Time 14:11 Sent To  
Notes
2002-12-12 00:00:00RESTAMP

Review Stop P PLUMBING
Rev No 9 Status F Date 2002-12-09 Cont ID  
Sent By kstevens Date 2002-12-06 Time 18:23 Rev Time 0.50
Received By kstevens Date 2002-12-06 Time 18:22 Sent To  
Notes
2002-12-06 00:00:00REVISION OK - VTR CHANGED TO D/2 RISERS
  
 REVIEW CHANGED TO FAILED - NO CHANGES TO
 MASTER - ALL REVISIONS TO BE SUBMITTED
 FOR EACH PERMIT NUMBER.

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-09-06 Cont ID  
Sent By kstevens Date 2002-09-06 Time 10:43 Rev Time 0.00
Received By kstevens Date 2002-09-06 Time 10:43 Sent To  
Notes
2002-09-06 00:00:00REVISION OK - SHEET P5.21 RISERS

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-08-28 Cont ID  
Sent By kstevens Date 2002-08-28 Time 11:14 Rev Time 0.00
Received By kstevens Date 2002-08-28 Time 11:14 Sent To  
Notes
2002-08-28 00:00:00REVISION OK - BLDG DRAIN

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 17:00 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 17:00 Sent To  
Notes
2002-07-22 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SANITARY RISERS A1, A2, B1, & B2 -
 NO KITCHEN SINK OR WASHING MACHINE TRAP
 SHALL BE PLACED ON A 2" COMBINED WASTE
 AND VENT. 3" WASTE AND VENT STACK REQD.
 SECT. 911.4-SHT P5.21
  
 2) NO VENT THRU ROOF SHOWN ON ANY STACK
 PLEASE INDICATE WHICH STACK/STACKS WILL
 VENT THRU ROOF. SHT P5.21
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-07-11 Cont ID  
Sent By kstevens Date 2002-07-11 Time 16:58 Rev Time 0.00
Received By kstevens Date 2002-07-11 Time 16:58 Sent To  
Notes
2002-07-11 00:00:00REVISION OK - CHANGED BLDG DRAIN TO ONE
 LINE

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-14 Cont ID  
Sent By kstevens Date 2002-05-14 Time 10:16 Rev Time 0.00
Received By kstevens Date 2002-05-14 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-03-14 Cont ID  
Sent By kstevens Date 2002-03-14 Time 08:40 Rev Time 1.00
Received By kstevens Date 2002-03-14 Time 08:40 Sent To  
Notes
2002-03-14 00:00:00DENIED
 REFERENCE: SPC-94-FHA AMEND-98
 DESIGN MANUAL
  
 1) SEE REVIEW COMMENTS FROM PERMIT
 #01110409
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 19:28 Rev Time 0.50
Received By kstevens Date 2002-02-08 Time 19:28 Sent To  
Notes
2002-02-08 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) EXCEPT FOR #6 WHICH IS OK ON TYPE II
 BLDG SEE COMMENTS FROM PERMIT #01110409
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By kstevens Date 2001-11-30 Time 15:07 Rev Time 2.00
Received By kstevens Date 2001-11-30 Time 15:07 Sent To  
Notes
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94-FHA-98 DESIGN MAN
  
 SEE COMMENTS PERMIT #01110409