Plan Review Details - Permit 01110409
Plan Review Stops For Permit 01110409
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2003-03-25 Cont ID  
Sent By jwitmer Date 2003-03-25 Time 16:00 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2003-03-25 00:00:00STORM SHUTTERS
  
 TYPE I BLDG01110409
 TYPE II BLDG01110411
 TYPE III BLDG 01110412
  
 REVIEWED WITH KEY PLAN SHUTTER ANCHOR
 SCHEDULE & TESTING REPORT
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2002-12-31 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:06 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-31 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01110409 MODEL TYPE I
 01110411 MODEL TYPE II
 01110412 MODEL TYPE III
 ADD: 4400 N MILITARY TRAIL
 CONT: EPOCH PROPERTIES
 TEL: (561)683-1072
 SBC= 1997 STANDARD BUILDING CODE
  
 SUBMITTAL: STORM SHUTTERS
 DENIED
  
 1) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 SBC 1606.1.4.
 2)1997 SBC SECTION 103.6,
 1606.1.4& 1707.4
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 ATTACHED IS A COPY OF THE CITIES
 STANDARD FOR THE IMPLEMENTATION OF
 HURRICANE MISSLE IMPACT PROTECTION,
 IN REGARDS TO PROCEDURES (1 & 2). ALSO
 ATTACHED IS A COPY OF A SAMPLE SCHEDULE
 FOR INSTALATION.
 PLEASE INDICATE WHAT MODEL TYPE
 BUILDING I,II, OR III. ALSO INDICATE ON
 THE SCHEDULE WHAT FLOOR YOU ARE INDICAT-
 ING. THE CITY STATED THAT ALL WINDOWS ON
 THE 2ND & 3RD FLOOR ARE TO BE LARGE
 MISSLE TESTED, INDICATE ON THE SCHEDULE.
 THE CITY AGREED THAT THE SLIDING GLASS
 DOORS ON THE 2ND & 3RD FLOOR COULD BE
 SHUTTERED AS STATED IN YOUR LETTER DATED
 JULY 22,02 WITH ADDITIONAL HELP FROM
 A TEMP LABOR LETTER DATED AUG 15,02.
 THE USE OF STORM PANELS FOR FIRST FLOOR
 OK, AS STATED IN IMPACT STANDARD, WITH
 THE SCHEDULE FOR INSTALLATION!!!!
 PLEASE PROVIDE THE ADDITIONAL INFOR-
 MATION REQUESTED SO WE MAY EXPEDITE THIS
 MATTER, FOR FURTHER CLARIFICATION
 CONTACT:
 JIM WITMER
 (561) 659-8096 X8412
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2002-12-31 Cont ID  
Sent By jwitmer Date 2002-12-31 Time 10:55 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-31 00:00:00SUBMITTAL 12-12-02,DENIED 12-13-02,ONLY
 2 SETS OF PLANS SUBMITTED, SPECIAL
 INSPECTOR PROGRAM IN EFFECT, 3 SETS OF
 ANY CORESPONDANCE REQUIRED:
 1) BUILDING DEPART OFFICE COPY
 2) SPECIAL INSPECTOR COPY
 3) FIELD SET OF APPROVED DRAWINGS
  
 12/31/02 PLANS ARE BACK ONLY 2 SETS:
 AGAIN DENIED!!!!!!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-12-12 Time 13:31 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-11-20 00:00:00PRODUCT APPROVALS FOR 2ND/ 3RD FLOOR
 LARGE MISSLE IMPACT REVIEWED
 PW6200 ALUM FIXED WIND
 HS8700 ALUM HOR SLID
 SH7700 ALUM SINGLE HUNG

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2002-11-20 Cont ID  
Sent By jwitmer Date 2002-11-20 Time 16:20 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
2002-11-20 00:00:00SHOP DRAWINGS- STAIRSOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-10-21 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:26 Rev Time 0.75
Received By jwitmer Date 2002-10-21 Time 14:18 Sent To  
Notes
2002-10-21 00:00:00SHOP DRAWINGS, HEAVY GAUGE EXT STUDS,
 NO REVIEWED BY ENG OF RECORD G. TSUNG

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-10-03 Cont ID  
Sent By jwitmer Date 2002-10-03 Time 08:17 Rev Time 1.00
Received By jwitmer Date 2002-10-03 Time 08:17 Sent To  
Notes
2002-10-03 00:00:0010/03/02 REVISION: BREEZEWAY REDUCTION
 IN LENGTH BY VARIANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-09-02 Cont ID  
Sent By jwitmer Date 2002-09-02 Time 10:04 Rev Time 2.00
Received By jwitmer Date 2002-09-02 Time 10:04 Sent To  
Notes
2002-09-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01110409
 ADD:EPOCH/PORTOFINO/MASTER TYPE I
 CONT: EPOCH
 TEL: (561)683-1052
 ST BLD CD =1997 STANDARD BUILDING CODE
  
 *****PROVISO*****
  
 1) WEDGE-ALL ANCHOR DETAILS, SINCE THE
 LOADING IS NOT GIVEN FOR TENSION OR
 SHEAR LOAD APPLICATIONS HAS THE EDGE FAC
 TOR ( REDUCTION) BEEN FACORED INTO THE
 SPACING?
 A) DETAIL "D" S-D1.1 EXTERIOR CONDITION
 @ LOFT 2X6 WALL SITTING ON TOP OF A 5"
 CONCRETE WALL? NO INFORMATION IS GIVEN,
 CONTACT SIMPSON ENG. TO SEE IF A DOUBLE
 REDUCTION WOULD BE REQUIRED SINCE YOU
 WOULD BE 2 1/2" AWAY ON BOTH SIDES?
 B) DETAIL# 3 2X6 WALL AT EDGE OF SLAB,
 WHAT REDUCTION HAS BEEN TAKEN? HOW FAR
 AWAY FROM THE EDGE OF THE SLAB SHALL THE
 WEDGE ANCHOR BE LOCATED?
  
 ADDITIONAL INFORMATION SHALL BE OBTAINED
 TO CLARIFY THE CONDITIONS LISTED ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-06-25 Cont ID  
Sent By jwitmer Date 2002-06-25 Time 17:23 Rev Time 3.00
Received By jwitmer Date 2002-06-25 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-04-29 Cont ID  
Sent By jwitmer Date 2002-04-29 Time 17:33 Rev Time 2.00
Received By jwitmer Date 2002-04-29 Time 17:32 Sent To  
Notes
2002-04-29 00:00:00*****BUILDING PROVISO******
  
 MASTER TYPE I
  
 SOILS TEST REPORT INDICATES FURTHER
 INVESTIGATION BEFORE THE PERMIT CAN BE
 ISSUED. SHOW HOW DENSIFICATION OF SOIL
 WILL OCCUR.
  
 HYDROLIC CALS MISSING FROM PLANS.
  
 RESIDENT INSPECTOR TO REGISTER WITH
 ASSISTANT BUILDING OFFICIAL DON NEELY
  
 BUILDING PLANS TO BE SUBMITTED TO COUNTY
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-20 Cont ID  
Sent By jwitmer Date 2002-02-20 Time 13:06 Rev Time 5.00
Received By jwitmer Date 2002-02-20 Time 13:06 Sent To  
Notes
2002-02-20 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110409
 BRIGER TRACT "D"
 BUILDINGTYPE I
 SECOND REVIEW
  
 SBC=1997 STANDARD BUILDING CODE
  
 1)- SBC503.3.1 GENERAL AREA MODIFICATION
 SHALL BE APPLIED TO TYPE I BUILDING,
 UNPROTECTED, SPRINKLERED WITH THE USE OF
 NFPA 13R, THIS COMPLIES WITH FL STATE
 STATUTE 553.895 (2).
 2)- NO SITE SURVEY/ PLOT PLAN "RESPONCE"
 SEE CIVIL PACKAGE, WHERE, WE HAVE NOT RE
 CEIVED ANY CIVIL DRAWING AS OF TO DATE.
 THIS IS A MAJOR CONCERN, WHEN WE DRAFTED
 THE ADDRESS LIST A TELEPHONE CALL TO
 EPOCH WAS MADE REVEALING THIS CONCERN!
 DISCREPANCY, THE FIRST PLAN REVIEW F0.11
 REVEALS A SITE LAYOUT DIFFERENT FROM THE
 SITE LAYOUT DEPICTED ON"TYPE I"S0.10.
 2/19/01 TEL. MIKE SPELLMAN AS TO THE
 DISCREPANCY. MR. SPELLMAN INDICATED THAT
 THE FIRST DRAWING IS WHAT WAS APPROVED.
 THE PLANS NEED TO BE CORRECTED, TO
 FACILITATE PLAN REVIEW A REVIEW OF TABLE
 600 REVEILS A PROBLEM BETWEEN BUILDING
 NUMBER 4 & 16. THERE IS NO DIMENSIONS
 BETWEEN BUILDINGS TO INDICATE DISTACNES
 BETWEEN BUILDINGS.
 3)- ADDRESSING PER PREVIOUS CONVERSATION
 THE SITE SHALL HAVE A STREET NAME OF
 "PORTOFINO WAY". BEFORE PERMITS CAN BE
 ISSUED A PLAT SHALL BE RECORDED WITH
 PALM BEACH COUNTY, THE PROPOSED STREET
 NAME SHOULD APPEAR ON THE PLAT.AGAIN
 WE HAVE NOT RECEIVED CIVIL DRAWINGS.
 4)- EXTERIOR STAIRS, THE FLOOR PLAN
 DOES INDICATE THAT CODE SECTION 1004.1.4
 HAS BEEN MET AS FAR AS 1/2 THE DIAGONAL
 DISTANCE BETWEEN STAIRS.
  
 1997 SBC 1006.2.1. DOES ALLOW FOR THE
 USE OF EXTERIOR STAIRS AS AN MEANS OF
 EGRESS IN BUILDINGS NOT EXCEEDING SIX
 STORIES, WITHOUT ENCLOSURE REQUIREMENTS.
 THE EXTERIOR EXITWAY STAIR ARRANGEMENT
 SHALL CONTAIN 3 PRIMARY FEATURES TO
 ASSURE THE LEVEL OF PROTECTION NECESS-
 ARY FOE THE BUILDING OCCUPANTS.
  
 FIRST EACH TENANT MUST HAVE ACCESS TO A
 CHOICE OF EGRESS PATHS LEADING TO INDE-
 PENDANT AND REMOTELY LOCATED EXTERIOR
 STAIRS. THE PLANS HAVE BEEN REVISED TO
 INDICATE SUCH ON LS1.11.
  
 THE SECOND PROTECTION FEATURE INVOLES
 THE DISSIPATION OF SMOKE AND COMBUSTION
 PRODUCTS, WHILE THE CODE DOES NOT CUR-
 RENTLY ATTEMPT TO DEFINE THE DEGREE OF
 OPENNESS THAT MUST BE MAINTAINED.
  
 THE THIRD ELEMENT OF EXTERIOR EXIT
 STAIRS MUST BE FROM DIRECT FIRE EXPOSURE
 EITHER A 10 FT SEPERATION OF THE STAIR
 AND BALCONY (BREEZEWAY) FROM THE PROPER-
 TY LINE AND OTHER BUILDINGS ON THE SAME
 LOT OR 3/4 HR OPENING PROTECTIVES TO PRO
 TECT AGAINST EXTERIOR FIRE EXPOSURE.THIS
 ALSO HAS BEEN ACHIEVED THROUGH THE
 CURRENT DESIGN.
 SECTION 1006.2.4 PROVIDES PROTECTION
 AGAINST INTERIOR EXPOSURE. THIS HAS NOT
 BEEN ACHIEVED, THE OPENINGS ON EACH SIDE
 OF THE STAIRWAY SHALL HAVE 45 MINUTE
 OPENING PROTECTION. THIS PROTECTION
 SHALL EXTEND FROM THE GROUND TO A POINT
 10 FT ABOVE THE TOP MOST LANDING OR THE
 ROOFLINE AND HORIZONTALLY 10 FT FROM
 EACH SIDE OF THE STAIRWAY. THIS WOULD
 PERTAIN TO THE WINDOWS OF EACH UNIT AD-
 JACENT A STAIRWAY AND THE GARAGE DOORS
 ADJACENT TO THE STAIRWAY.
 5)- WINDERS REVISED OK
 6)- GENERAL AREA INCREASE TAAKEN FOR
 TYPE I BUILDING, NFPA 13-R OK.
 7)- SHEET M2.31/ M2.32 INDICATES A RATED
 CHASE, RESPONCE TO SEAL AT SLABS.
 SBC 705.6 INDICATES THAT ALL PENETRA-
 TIONS OF HORIZONTAL SLABS SHALL BE PRO-
 TECTED BY A SHAFT ENCLOSURE. 705.6.1
 DOES GIVE EXCEPTION TO PENETRATIONS THAT
 PENETRATE A SINGLE FIRE RATED FLOOR OR
 FLOOR/ CEILING ASSEMBLY, OTHERWISE A
 RATED SHAFT SHALL BE REQUIRED, PLEASE
 PROVIDE A UL OR GYPSUM ASSEMBLY NUMBER.
 8)- MEZZANINE OK
 9)- COMMENT ON DRAFT STOPPING OK
 BLOCK WALLS EXTENDING ABOVE FLOOR
 TRUSSES VS ENTRY HALL AND STORE ROOM
 NEED TO CLARIFY WHERE THIS REVISION
 IS SHOWN?
 10)- FASTENING SUBSTITUTION FASTENING
 SCHEDULE, NOW MISSING FROM STRUCTURAL
 SHEETS.
 11)- PLANS INDICATE THE USAGE OF 5"X5"
 STEEL COLUMNS ON THE COLUMN SCHEDULE,
 DETAIL A/S-D11 MISSING?
 12)- ROOF SHEATHING SCHEDULE MISSING ,
 ENGINEER TO INDICATE NAILING SCHEDULE
 ABOVE 35'.
 13)- TRUSS PLAN TO INDICATE THE LOADS
 TO BE RESISTED AND THE FASTENERS
 REQUIRED FOR EACH AREA. SEMCO HAS NOT
 BEEN IN BUSINESS FOR OVER 2 YEARS!
 14)- COMPONENTS & CLADDING SBC1606.2.6.2
 (3 COPIES) OF PRODUCT TESTING REPORTS
 FOR EACH BUILDING TYPE.SBCCI OR DADE
 COUNTY REPORTS ARE ACCEPTED. NORANDEX
 WINDOWS REQUIRE SITE SPECIFIC REPORT, IF
 USED (THEY ONLY HAVE BROWARD APPROVAL).
 WINDOWS,SLIDING GLASS DOORS, EXTERIOR
 SWING DOORS GARAGE DOORS ASWELL AS
 ROOFING. SEE CITY INTERPETTATION FOR
 LARGE MISSLE IMPACT TESTING.
 15)- RESIDENT INSPECTOR REQUIRED, SEE
 DON NEELY FOR INFORMATION.
 16)- COUNTY IMPACT FEES TO BE PAID
 BEFORE ISSUANCE OF BUILDING PERMIT.
 17)- CONTRACTOR TO PAY RADON FEES
 AT TIME OF ISSUANCE.
 18)- PLANS TO REFLECT WIND PRESSURE
 ZONES, FOR WINDOWS AND DOORS, THIS
 IS COMPLETED.
  
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-14 Cont ID  
Sent By jwitmer Date 2001-12-14 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2001-12-14 Time 13:20 Sent To  
Notes
2001-12-14 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110409
 BRIGER TRACT "D"
 BUILDING TYPE I
  
 FLOOR AREA:
 1ST FL 15,569 SQ FT
 2ND FL 15,470 SQ FT
 3RD FL9,813 SQ FT
 LOFT 3,834 SQ FT
 TOTAL44,686 SQ FT
  
 NO SITE SURVEY / PLOT PLAN TO BE ABLE TO
 CHECK TABLE 600 ISSUES, HORIZONTAL
 SEPERATION, NOR ADDRESSING. WHAT IS
 FILED UNDER FIRE IS UNREADABLE AS TO
 WHAT TYPE OF BUILDINGS OR SITE FEATURES.
  
 WILL SITE ADDRESSING TAKE A WINDSOR WAY
 ADDRESS? OR WILL THERE BE A PRIVATE
 STREET NAME BE SUBMITTED? WILL TRACT"D"
 AND TRACT "C" HAVE THE SAME DEVELOPMENT
 NAME? SINCE THE PROPERTIES ARE ON (2)
 SEPERATE PROPERTIES THEY WILL REQUIRE
 2 ADDRESSES OR WILL THERE BE A UNITY OF
 TITLE?
  
 1006.2.1 EXTERIOR STAIRS: THE STAIRWAYS
 DEPCTED DO NOT COMPLY WITH THE DEFINI-
 TION OF EXTERIOR STAIRS. BREEZEWAY: A
 COVERED PASSAGEWAY AS BETWEEN A HOUSE/
 GARAGE, OFTEN ENCLOSED ON BOTH SIDES, W/
 OPEN ENDS AND A ROOF.
 BALCONY: A PLATFORM PROJECTING FROM THE
 BUILDING WITH A RAILING.
 PORCH: A COVERED ENTRANCE
 A SAMPLE PAGE OF OPEN EXTERIOR STAIRS
 FROM THE CODE COMMENTARY IS ATTACHED.
 SBC 1006.2.2 THE STAIR ARANGEMENTS DO
 NOT MEET THE CRITERIA OF THIS SECTION,
 THEY DO NOT MEET THE 1/2 THE DIAGONAL,
 PLUS MEETING THE 10' OPENING PROTECTIVES
 REQUIRED IN SBC 1006.2.4.OPENING WITHIN
 THE 10' HORIZONTALLY FROM EACH SIDE OF
 THE STAIRWAY SHALL BE EQUIPPED WITH FIX-
 ED 3/4 HR ASSEMBLIES.
 SBC TABLE 1007.1 CODE COMMENTARY INDICAT
 ES FOR TYPE V BUILDINGS RESIDENTIAL USE
 STAIRS 3 STORIES & GREATER REQUIRE NON-
 COMBUSTIBLE MATERIAL, SHOW COMPLIANCE
 WITH WOOD TRUSS FLOOR SYSTEM, STRUCTURAL
 DRAWINGS DO NOT INDICATE THE INTERMEDI-
 ATE FLOOR LANDINGS.
 IF STAIR & BREEZEWAY WERE ACCEPTED, THE
 1 HR SEPERATION SHALL BE MAINTAINED,
 M2.1 /M2.32 INDICATE THE BATH EXHAUST
 THRU TO BREEZEWAY.1006.2.4.
  
 SHEET A.3.31-A3.34 ILLEGAL WINDER SEE
 SECTION 1007.8.1.
  
 SHEET A3.34/F2.12 TYPE V FULLY SPRINKLER
 ED BUILDING. PLANS DO NOT SHOW FIRE
 SPRINKLERS IN GARAGE OR BREEZEWAY INTERM
 EDIATE LANDINGS OR ROOF TRUSSES.
 CS1.01 CODE SUMMARY(E) CONSTRUCTION TYPE
 RESIDENTIAL FULLY SPRINKLERED.PLANS
 INDICATE NFPA(13R) THIS SYSTEM WILL NOT
 ALLOW FOR THE HEIGTH MODIFICATION IN
 TABLE 500,FOOTNOTE "H".903.2 REQUIREMENT
 CITY OF RALIEGH, PLEASE CORRECT.
  
 SHEET M2.31/ M2.32 NOTE#5 INDICATES A
 RATED CHASE FOR REFRIGARANT LINES & CON-
 DENSATE LINES? SEC 705.2.2 SHAFT ENCLOS-
 URES, GIVE UL OR GYPSUM ASSEMBLY NUMBER.
  
 MEZZANINE SECTION 503.2.3:
 TYPE I BUILD : OK
 TYPE II BUILD:
 BALCONY SQ FT OVER
 SOLARIUM SQ FT OVER
 TYPE III BUILD:
 BALCONY SQ FT OVER
 SOLARIUM SQ FT OVER
  
 SHEET A-5.33 DRAFTSTOPPING REQ. 2305.2.2
 (2) FL/CEIL ASSEMBLY GARAGE / 2ND FL.
 A3.3.4 BLOCK DOES NOT EXTEND ABOVE THE
 FLOOR TRUSSES AT ENTRY HALL? STOREROOMS?
  
 SHEET S1.11 FASTENING SUBSTITUTION FAST-
 ENING SCHEDULE: STATES THAT THE NAILING
 FASTENERS PATERNS FOR SUBSTITUTE FASTEN-
 ERS SHALL USE THE SAME SCHEDULE CONVER-
 SION CHART FOR "ALLOWABLE LOADS ADJUST-
 MENT FACTORS" NOT THE SAME TENSION LOADS
 SEE MANUFACTURES LOAD CHARTS.
  
 SHEET S3.13 DETAIL #12 INDICATES USE OF
 COLUMN TO WOOD POST, WHERE IS THIS TO BE
 USED?
  
 ROOF SHEATHING SCHEDULE SBC TABLE 2306.1
 (COUNTY AMENDMENTS) ARE GOOD TO A HEIGTH
 OF 35'. ENGINEER SHALL INDICATE NAILING
 SCHEDULE FOR ABOVE 35'.
  
 SHEET S2.35 ROOF FRAMING PLAN INDICATE
 THE MAGNITUDE OF LOADS TO BE RESISTED,
 VERTICAL, HORIZONTAL & GRAVITY AND THE
 TYPE OF FASTENER REQUIRED FOR EACH AREA.
  
 SBC 1606.2.6.2 COMPONENTS & CLADDING
 DOOR & WINDOW BUCK ATTACHMENTS : NOT
 FOUND IN STRUCTURAL SHEETS.
 GLAZED OPENINGS REQUIRE LARGE MISSLE
 IMPACT RESISTANCE TESTING: SEE CITY
 POLICY AS TO REQUIREMENTS FOR LARGE
 COMPLEXES, COPY ATTACHED. (3 COPIES
 OF PRODUCT APPROVAL SHALL BE REQUIRED
 FOR EACH TYPE OF OPENING)
 ROOFING : ROOFING ASSEMBLIES SHALL ALSO
 REQURIE PRODUCT TESTING REPORTS FOR
 WIND ZONE 110.
 MULLIONS SHALL REQUIRE PRODUCT TESTING
 IF GLAZED UNIT WASN'T TESTED W/ MULLION
 DADE COUNTY OR SBCCI REPORTS ARE
 ACCEPTED.
  
 THIS PROJECT SHALL QUALIFY FOR A
 RESIDENT INSPECTOR. THE INSPETOR SHALL
 MEET WITH ASSISTANT BUILD DON NEELY
 TO REGISTER BEFOR ISSUANCE OF PERMIT.
  
 COUNTY IMPACT FEES SHALL BE PAID BY THE
 CONTRACTOR, CONTRACTOR SHALL SUBMIT
 PLANS TO THE COUNTY FOR IMPACT FEE
 ASSESSMENT.
  
 AT TIME OF ISSUANCE CONTRACTOR WILL PAY
 RADON FEES.
  
 PLANS ARE TO STATE CLEARLY ON ELEVATIONS
 THE APPROPRIATE WIND PRESSURES FOR
 DOORS AND WINDOWS,INCLUDING END ZONES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2003-04-29 Cont ID  
Sent By btrobaug Date 2003-04-29 Time 11:43 Rev Time 1.00
Received By btrobaug Date 2003-04-29 Time 11:43 Sent To  
Notes
2003-04-29 00:00:00THIS REV,CORRECTLY INCREASES THE SERVICE
 CONDUCTOR FOR 1200 AMPS (ALUMINUM) AND
 CORRECTS THE VOLTAGE TO 240 FROM 208.
 COPPER CONDUCTORS WERE SPEC'D.SAME SIZE
 AL WERE INSTALLED INCORRECTLY./WRT.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-11-13 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:44 Rev Time 1.50
Received By btrobaug Date 2002-11-13 Time 10:11 Sent To  
Notes
2002-11-13 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT ALL COUNTERTOP
 RECEPTACLES MUST COMPLY WITH
 210-8(A)(6).SHEETS 3.11 THROUGH 3.15
 HAVE SOME "GFI" NOTATIONS REMOVED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 20:32 Sent To  
Notes
2002-06-20 00:00:00STAMPED 6/20/02
 DV PALMER.
2002-06-19 00:00:00****************** NOTE ***************
  
 NOTE REDLINED ON PLANS, PERMITS APPLIED
 FOR AFTER JAN 1,2002 ARE REQ`D TO HAVE
 ARC FAULT PROTECTION PER 210-12 "99" NEC
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-06-13 Cont ID  
Sent By dpalmer Date 2002-06-13 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2002-06-13 Time 11:38 Sent To  
Notes
2002-06-13 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE NOTE SAME NOTES AS BEFORE
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-05-09 Cont ID  
Sent By dpalmer Date 2002-05-09 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2002-05-09 Time 07:48 Sent To  
Notes
2002-05-09 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT E- SHEETS DO
 NOT HAVE ORIGINAL SIGNATURE FROM THE
 ARCH/ENGINEER OF RECORD WHICH IS REQ`D
 UNDER FS/FAC 471.025/481.221
 MUST BE AN ORIG SIGNATURE.
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACINGS
 STILL NEED TO MEET 210-52. PLEASE SEE
 210-52C-1AND 210-52A 123
 PLEASE ALSO NOTE THAT RAIL SPACE IS
 CONSIDERED TO BE WALL SPACE.
  
 3)NOTE: PLEASE NOTE THAT PLANS HAVE
 GONE BACK AND FORTH IN REF TO RIGID AND
 EMT. PLEASE NOTE THAT PER LOCAL AMEND.
 EMT SHALL NOT BE USED , IN DIRECT
 CONTACT WITH EARTH, POURED ETC . PLEASE
 NOTE IT WAS JUST A NOTE, RIGID MAY BE
 USED AND ALSO PVC, IMC. PLEASE SEE
 348-5 LOCAL AMENDMENTS.
  
 4)NOTE:PLEASE NOTE THAT PER FS/ FAC
 553-80, PLANS THAT ARE DENIED MORETHAN
 3 TIMES FOR THE SAME COMMENTS ARE
 SUBJECT TO 4X FEE FOR THE PORTION SET
 ASIDE FOR PLAN REVIEW OF THE TOTAL
 PERMIT FEE. (30%)
  
 PLEASE NOTE THAT IF A MEETING IS REQ`D
 OR A CONFERENCE CALL TO CLARIFY ANYTHING
 AS TO DATE, NO ONE HAS CONTACTED ME
 WITH ANY QUESTIONS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-03-18 Cont ID  
Sent By dpalmer Date 2002-03-18 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2002-03-18 Time 06:50 Sent To  
Notes
2002-03-18 00:00:00********************* UNSAT ************
  
 1)NOTE: PLEASE NOTE MISSING LT REQ`D FOR
 MECH ROOM UPSTAIRS PER 210-70.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING STILL
 NEEDS TO MEET 210-52. BALCONY/LOFT WALL.
 BEDROOM WALLS. 2' OF WALL.
  
 3)NOTE: PLEASE NOTE, IT IS NOTED THAT
 THE FEEDER CONDUITS TO APT UNITS WERE
 ALSO CHANGED TO "RIGID" CONDUIT. THE
 COMMENT FROM THE PREVIOS REVIEW WAS FOR
 SERVICE ENTRANCE CONDUIT ONLY COMING
 FROM FPL. PLEASE NOTE IF RIGID IS SHOWN
 THE IT WILL BE REQ`D TO BE INSTALLED.
 PLEASE VERIFY IF CHANGING APT FEEDER
 CONDUIT STILL STANDS. RIGID STANDS TO
 BE MUCH MORE OF AN EXSPENSE.
  
 4)NOTE: PLEASE REMOVE ALL OLD E-SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 18:08 Rev Time 0.00
Received By dpalmer Date 2002-02-06 Time 18:08 Sent To  
Notes
2002-02-06 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52. BALCONY AND WALLS IN BEDROOMS.
  
 2)NOTE: MISSING REQ`D SD`S AT BOTTOM OF
 STAIRS. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE CLARIFY EMT AS TYPE OF
 CONDUIT FOR SERVICE? EMT IS NOT ALLOWED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372
  
 4)NOTE: PLEASE NOTE THAT OCP NEEDS TO
 BE SHOWN FOR UNITS. CAN BE TYPICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-27 Cont ID  
Sent By dpalmer Date 2001-11-27 Time 19:46 Rev Time 0.00
Received By dpalmer Date 2001-11-27 Time 19:46 Sent To  
Notes
2001-11-27 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE PROVIDE A ONE-LINE
 DIAGRAM FOR SERVICE RISER.
 215-5
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM.250-50
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 6)NOTE: PLEASE PROVIDE THE INFORMATION
 FOR THE FAIR HOUSING ACT 24CFR 100.205
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 7)NOTE: PLEASE PROVIDE EXIT LTS PER
 FIRE DEPT COMMENTS.
  
 8)NOTE: PLEASE NOTE THAT CLEARENCE FOR
 STORAGE ROOM LIGHTING FIXTURES.410-8
  
 9)NOTE: PLEASE NOTE THAT PER LOCAL CODE
 ALL METHODS IN NOTES FOR SE,NMC MAY NOT
 BE USED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2002-05-29 Cont ID  
Sent By mamini Date 2002-05-29 Time 10:28 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
2002-05-29 00:00:00N/A
 1. SEE PERMIT # 02050423 FOR CIVIL/SITE
 WORKS REVIEW AND PERMITTING FOR PARCEL-D
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mamini Date 2001-11-13 Time 11:00 Rev Time 1.00
Received By mamini Date 2001-11-13 Time 11:00 Sent To  
Notes
2001-11-13 00:00:00FAILED :
 1. SEE PERMIT # 01110408
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-10-21 Cont ID  
Sent By mcarsill Date 2002-10-21 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2002-10-21 Time 11:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-06-20 Cont ID  
Sent By mcarsill Date 2002-06-20 Time 11:40 Rev Time 0.00
Received By mcarsill Date 2002-06-20 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 09:10 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 09:10 Sent To  
Notes
2002-04-04 00:00:00A) CIVIL DRAWINGS INDICATING FIRE MAIN
 LOCATIONS, SIZES AND FIRE HYDRANT
 LOCATIONS NOT YET APPROVED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 11:20 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 11:20 Sent To  
Notes
2002-02-12 00:00:001) CIVIL DRAWINGS ARE REQUIRED SO A
 REVIEW CAN OCCUR FOR FIRE MAIN, FIRE
 HYDRANTS, ETC. WET FIRE HYDRANTS ARE
 REQUIRED PRIOR TO,DURING AND AFTER
 CONSTRUCTION.
 2) DOORS INTERSECT WITH ONE ANOTHER
 ON THE FIRST FLOOR PLAN.
 3) ARCHITECTURAL MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS
 OR GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE TO
 BE A MINIMUM OF AT LEAST 20 FEET IN
 CLEAR WIDTH AND ABLE TO SUPPORT FIRE
 APPARATUS. WHAT IS THE DIFFERENCE
 BETWEEN PHASE ONE AND PHASE TWO.
 4) BUILDING ADDRESSES REQUIRED.
 5) PLEASE SEE PREVIOUS FIRE PLAN
 REVIEW NOTES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 09:38 Sent To  
Notes
2001-11-26 00:00:001) IT DEPENDS WHEN THE BUILDING IS
 OFFICIALLY SUBMITTED FOR PERMIT AS TO
 WHAT FIRE CODE THE BUILDING WILL BE
 REVIEWED UNDER. JANUARY 1, 2002, THE
 FIRE PREVENTION CODE WILL BE APPLICABLE
 WHICH INVOKES THE 2000 LIFE SAFETY CODE.
 2) BUILDING ADDRESS REQUIRED.
 3) SITE PLAN FOR FIRE PROTECTION
 DRAWINGS DOES NOT INDICATES STREET
 NAMES.
 4) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER PLANS.
 5) ILLUMINATED EXIT SIGNS NOT SHOWN
 ON ELECTRICAL DRAWINGS, FLOOR PLANS.
 6) FIRE DEPARTMENT CONNECTIONS TO BE
 LOCATED NO FARTHER 150 FEET TO FIRE
 HYDRANTS.
 7) THE CITY OF RALEIGH NOTED ON PAGE
 F1.11
 8) TRAVEL DISTANCE UNDER THE 1985
 EDITION OF THE LIFE SAFETY CODE ALLOWS
 ONLY 150 FEET IN SPRINKLERED APARTMENT
 BUILDINGS.
 9) PLEASE EXPLAIN USE OF LOFTS.
 10) THIRD FLOOR PLAN ON LS1.12, FIRE
 RATING APPEARS TO RUN IN MIDDLE OF
 CORRIDOR.
 11) GARAGE DOORS SHWON ON PAGE A2.11
 APPEAR TO INTERSECT WITH ONE ANOTHER.
 12) WHAT FIRE RATING IS PRESENT FOR THE
 ALCOVES FROM THE GARAGE AND STORAGE
 AREAS.
 13) IS THERE ANY FIRE SEPARATION FOR
 THE STORAGE ROOMS.
 14) PLEASE INDICATE HEADROOM CLEARANCES
 FOR THE MEANS OF EGRESS AREAS.
 15) WHAT ARE THE ROOMS ADJACENT TO THE
 STOREROOMS USED FOR.
 16) PLEASE VERIFY SEPARATION DISTANCES
 OF STAIRS. DIMENSIONS ON PAGE A2.11 DO
 NOT MEET DISTANCES ON PAGE LS1.11.
 17) FIRE SPRINKLER PROTECTION NOT SHOWN
 FOR UNITS A,B, AND C A3.11,A3.12,AND
 A3.13.
 18) DRYER EXHAUST VENTS APPEAR TO
 PENETRATE EXIT CORRIDORS AND ONE HOUR
 WALLS.
 19) GARAGE DOORS LABELED IN CORRECTLY
 ON PAGE A5.11.
 20) NO RATINGS PRESENT ON DOOR SCHEDULE
 FOR GARAGE DOORS WHICH APPEAR TO BE
 PART OF EXIT ACCESS AND COMMUNICATES
 WITH EXIT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 08:23 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 08:23 Sent To E
Notes
2003-04-29 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:06 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:06 Sent To B
Notes
2003-03-14 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-12 Time 13:31 Rev Time 0.00
Received By btrobaug Date 2002-12-12 Time 13:31 Sent To B
Notes
2002-12-12 00:00:00JIM W./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-14 Time 16:25 Rev Time 0.00
Received By btrobaug Date 2002-11-14 Time 16:23 Sent To B
Notes
2002-11-14 00:00:00TO JIM W./WRT
 TO JIM W./WRT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2002-11-14 Cont ID  
Sent By pkrauss Date 2002-11-06 Time 12:35 Rev Time 0.50
Received By pkrauss Date 2002-11-06 Time 12:34 Sent To  
Notes
2002-11-06 00:00:00REVISIONS DENIED - SPOKE WITH TOM
 DESSOYE (EPOCH), REQUEST A SUMITTAL LTR
 FROM THE ENG STATING WHY A DROP IN THE
 WALK-IN CLOSET IS NEED & REDUCTION OF
 TONNAGE IN THE A/C UNITS.DUCT MATERIAL
 & LAYOUT ARE TO GO ACCORDING TO THE
 APPROVED PLANS ON THE MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-30 Time 11:21 Rev Time 1.00
Received By pkrauss Date 2002-09-30 Time 10:01 Sent To  
Notes
2002-09-30 00:00:00REVISED PLAN SHEETS M3.11, M3.12, M3.13,
 M3.14, M3.15, M3.16 - REVISED DUCT LAY
 OUT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-21 Cont ID  
Sent By pkrauss Date 2002-06-21 Time 10:01 Rev Time 0.40
Received By pkrauss Date 2002-06-21 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-05-14 Cont ID  
Sent By pkrauss Date 2002-05-14 Time 10:03 Rev Time 1.00
Received By pkrauss Date 2002-05-14 Time 10:03 Sent To  
Notes
2002-05-14 00:00:00PLEASE NOTE SOME OF THE MECHANICAL
 PAGES HAVE A "STAMPED" SIGNATURE FOR THE
 ENGINEER INSTEAD OF A SIGNATURE.UNDER
 THE PROVISIONS OF CHAPTER 471 OF THE
 FLORIDA STATUES, ALL PAGES SHALL HAVE
 AN ORIGINAL SIGNATURE NOT A STAMP.
  
 BUILDING PERMIT 01110409
  
 PROVIDE RATING OF UL425 FOR THE DRYER
 CHASE (1 HR, 2 HR?).
  
 SPECIFICATION FOR SPECIFIC DRYER ALSO
 SUBMITTED INDICATING THE ALLOWABLE
 LENGTH OF DUCT EXCEEDING THE CODE
 REQUIREMENT.PLEASE NOTE DRYERS SHALL
 BE INSTALLED FOR FINAL INSPECTION.
  
 DETAIL FOR THE RESTROOM EXHAUST VENTING
 ON PLAN SHEET M5.33, PLEASE NOTE SHOULD
 THE ALTERNATE DISCHARGE THROUGH THE ROOF
 BE USED IT SHALL COMPLY WITH 1997 SMC
 610.4. (DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-03-13 Cont ID  
Sent By pkrauss Date 2002-03-13 Time 09:27 Rev Time 2.00
Received By pkrauss Date 2002-03-12 Time 16:50 Sent To  
Notes
2002-03-13 00:00:00 
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #84"
 METAL DRYER EXHAUST VENT ROUTED UP IN
 CHASE & THROUGH THE ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE".DUCTS
 EXTENDINGTHROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROM DRYER LOCATION TO
 WALL OR ROOF CAP.THERE SHALL BE A 5
 FT DEDUCTION FOR EACH 90 DEGREE BEND &
 2 1/2 FT DEDUCTION FOR EACH 45 DEGREE
 BEND.THE WALL OR ROOF CAP SHALL BE
 NONSCREENED WITH BACK DRAFT DAMPER.
 1997 SMC 509.3
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPER AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 07:59 Rev Time 0.45
Received By pkrauss Date 2002-02-07 Time 07:59 Sent To  
Notes
2002-02-07 00:00:00 
  
 BUILDING TYPE I - PERMIT 01110409
  
 AS PER 2000 LIFE SAFETY CODE CHAPTER 7 -
 7.1.3.1 EXIT ACCESS CORRIDORS
  
 (E) PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ASSEMBLY
 SHALL BE PROHIBITED EXCEPT FOR THE
 FOLLOWING.
  
 (1) ELECTRICAL CONDUIT SERVING THE
 STAIRWAY
 (2) REQUIRED EXIT DOORS
 (3) DUCTWORK & EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION
 (4) WATER OR STEAM PIPING NECESSARY
 FOR THE HEATING OR COOLING OF THE
 EXIT ENCLOSURE
 (5) SPRINKLER PIPING
 (6) STANDPIPES
  
 ALSO AS PER 1997 SMC 610.1.2, FIRE
 DAMPERS REQUIRED WHERE DUCTS PENETRATE
 WALLS OR PARTITIONS HAVING A FIRE
 RESISTANCE RATING OF 1 OR MORE HOURS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 11 Status P Date 2002-12-12 Cont ID  
Sent By kstevens Date 2002-12-12 Time 14:10 Rev Time 0.25
Received By kstevens Date 2002-12-12 Time 14:09 Sent To  
Notes
2002-12-12 00:00:00RESTAMP

Review Stop P PLUMBING
Rev No 10 Status F Date 2002-12-09 Cont ID  
Sent By kstevens Date 2002-12-06 Time 18:45 Rev Time 0.50
Received By kstevens Date 2002-12-06 Time 18:45 Sent To  
Notes
2002-12-06 00:00:00REVISION OK - CHANGED VENT THRU ROOF TO
 C/2 STACKS
  
 REVIEW CHANGED TO FAILED - NO CHANGES TO
 MASTER - ALL REVISIONS TO BE SUBMITTED
 FOR EACH PERMIT NUMBER.

Review Stop P PLUMBING
Rev No 9 Status P Date 2002-09-06 Cont ID  
Sent By kstevens Date 2002-09-06 Time 10:35 Rev Time 0.00
Received By kstevens Date 2002-09-06 Time 10:35 Sent To  
Notes
2002-09-06 00:00:00REVISION OK - SHT P5.11 SANT RISERS

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-08-28 Cont ID  
Sent By kstevens Date 2002-08-28 Time 09:55 Rev Time 0.00
Received By kstevens Date 2002-08-28 Time 09:55 Sent To  
Notes
2002-08-28 00:00:00REVISION OK - SHT P2.11

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 17:29 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 17:29 Sent To  
Notes
2002-07-22 00:00:00REVISION DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SANITARY RISERS A1, A2, B1, & B2-
 NO KITCHEN SINK OR WASHING MACHINE TRAP
 SHALL BE PLACED ON A 2" COMBINED WASTE
 AND VENT. 3" WASTE AND VENT STACK REQD.
 SECT. 911.4-SHT P5.11
  
 2) NO VENT THRU ROOF SHOWN ON ANY STACK.
 PLEASE INDICATE WICH STACK/STACKS WILL
 VENT THRU ROOF.SHT P5.11
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-07-11 Cont ID  
Sent By kstevens Date 2002-07-11 Time 16:56 Rev Time 0.00
Received By kstevens Date 2002-07-11 Time 16:56 Sent To  
Notes
2002-07-11 00:00:00REVISION OK - CHANGED BLDG DRAIN TO ONE
 LINE.

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-05-14 Cont ID  
Sent By kstevens Date 2002-05-14 Time 10:47 Rev Time 0.00
Received By kstevens Date 2002-05-14 Time 10:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-14 Cont ID  
Sent By kstevens Date 2002-05-14 Time 09:36 Rev Time 0.00
Received By kstevens Date 2002-05-14 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-03-08 Cont ID  
Sent By kstevens Date 2002-03-08 Time 18:08 Rev Time 1.50
Received By kstevens Date 2002-03-08 Time 18:07 Sent To  
Notes
2002-03-08 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN
 MANUAL
  
 1) FROM PREVIOUS REVIEW - SHT A0.11 UNIT
 TYPE A, B, & C NOW, INDICATE SPECIFICAT-
 A OR B, ONE OR THE OTHER. BOTH A OR B
 IS NOT AN OPTION.
 2) FROM PREVIOUS REVIEW - SHT A0.11 SEE
 REVIEW NOTE #1. SEE FHA DESIGN MANUAL
 FOR DIFFERENCE BETWEEN SPECIFICATION A
 OR B ON FLOOR LAY OUT.
 3) FROM PREVIOUS REVIEW - CLEAR FLOOR
 SPACE FOR LAVS NOT SHOWN. CLEAR FLOOR
 SPACE FOR SHOWERS NOT SHOWN.
 4) FROM PREVIOUS REVIEW - ALL DIMENTIONS
 FOR ALL W/'S NOT SHOWN. SEE BATHROOMS
 #B307 & #C110.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 18:50 Rev Time 0.00
Received By kstevens Date 2002-02-08 Time 18:50 Sent To  
Notes
2002-02-08 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SHT A0.11 UNIT TYPE A, INDICATE SPEC-
 IFICATION A OR B FOR BATHROOM AS REQUES-
 TED IN PREVIOUS PLAN REVIEW.
 2) SHT A0.11 HAS SPECIFICATION B LAY OUT
 AND SPEC. A CALLED OUT. TYPICAL FOR RM
 #'S B201, A101, AND C101. PLEASE CLAIRFY
 3) SHT A0.11 CLEAR FLOOR SPACE NOT SHOWN
 ON KITCHEN FIXTURES AND/OR APPLIANCES AS
 REQUIRED IN FHA DESIGN MANUAL.
 4) SHT A0.11 SHOW CLEAR FLOOR SPACE FOR
 ALL LAVS WHICH SHALL BE CENTERED ON
 CLEAR FLOOR SPACE, AND SHOW CLEAR FLOOR
 SPACE PROPERLY AT ALL TUBS AND SHOWERS.
 SEE FHA DESIGN MANUAL FOR EXAMPLES.
 5) SHT A0.11 ALL DIMENSIONS FOR WATER
 CLOSETS NOT SHOWN. SEE B-307 AN C-110.
 SHOWN IS 15" TO CENTER FROM ONE SIDE BUT
 NO MEASUREMENT FROM OTHER SIDE. 33" MIN.
 REQUIRED.
 6) SHT 2.12 SHOW ALL CLEANOUTS ON RISER
 DIAGRAM,
 7) SHT P5.11 SANITARY RISER (B-2) STILL
 REDUCES FROM 3" TO 2" ON RISER. 3" SHALL
 RUN UNDIMINISHED FROM CONNECTION TO BLDG
 DRAIN TO CONNECTION TO STACK VENT.
 SPC SEC 714.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By kstevens Date 2001-11-30 Time 14:24 Rev Time 2.50
Received By kstevens Date 2001-11-30 Time 14:24 Sent To  
Notes
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94- FHA AMEND-98
 DESIGN MANUAL
  
 1) SHT A0.31 FAIR HOUSING PLANS. FHA-98
 DESIGN MANUAL, PLEASE COMPLY WITH REQ-
 UIREMENTS 1 THRU 7. REQ 7 PART B, PLEASE
 INDICATE SPECIFICATION A OR B FOR EACH
 FIRST FLOOR UNIT.
 2) SHT A0.31, PLEASE SHOW CLEAR FLOOR
 SPACE FOR ALL REQUIRED FIXTURES. (SEE
 PAGE 7.43)
 3) TYPICAL DOUBLE LAV - OFFSET BASIN AT
 DOUBLE LAVS, (SEE PAGE 7.48), FOR COUNT-
 ER AT LEAST 60" LONG. FOR SHORTER COUNT-
 ERS FORWARD APPROACH IS REQUIRED AND THE
 VANITY WILL HAVE TO BE REMOVABLE. (SEE
 PAGE 7.49) GIVE A DETAIL IN PLANS
 4) SHOW DEMENSIONS FOR ALL 1ST FLOOR W/C
 OPENINGS THAT HAVE NO DEMEMTIONS.
 5) SHT P2.31 2-WAY CLEAN OUTS ARE REQUI-
 RED AT EACH BREEZWAY. SPC SEC 710.2.4
 MAXIMUM 80' BETWEEN C/O'S.
 6) TYPICAL OF ALL UNITS, MAXIMUM 6' FOR
 2" TRAP FROM VENT. SPC TABLE 908.1. TUBS
 SCALE OUT TO BE FARTHER THAN ALLOWED.
 7) PROVIDE SANITARY RISER DIAGRAM FOR
 FIRST FLOOR HORIZONTAL BLDG DRAIN. SHOW
 ALL PIPE SIZES AND DRAINAGE FIXTURE
 UNITS EACH SECTION OF PIPE DRAINS. SHOW
 NUMBER OF FIXTURE UNITS DRAINING FROM
 EACH SANITARY RISER. (STACK)
 8) SHT P4.31 WATER HEATER DETAIL. DI-
 ELECTRIC UNIONS NOT APPROVED.
 9) SHT P4.31 DETAILS 6D & 7D WATER METER
 NOT APPROVED PER CITY CODE SEC 31-29
 SEE ATTACHED SHEET.
 10) SHT PR.31 WATER HEATER DETAIL. SAFE-
 TY PAN SHALL BE OF SUFFICIENT SIZE AND
 SHAPE TO RECIEVE ALL DRIPPINGS OR CON-
 DENSATE FROM TANK OR HEATER - DRAIN
 VALVE MUST BE INSIDE PAN. SEC 507.8.2
 11) SHT P4.31 ELECT. WATER HEATER SCHED.
 PER SPC TABLE 504 B-UNITS SHALL HAVE 40
 GAL W/HEATERS. C-UNITS SHALL HAVE 50 GAL
 W/HEATERS. ONLY 30 & 40 ARE SHOWN.
 12) SHT P5.31 SANITARY RISERS B1 & B2
 SHALL NOT REDUCE TO 2", BUT SHALL RUN
 UNDIMINISHED IN SIZE FROM ITS CONNECTION
 TO THE BLDG DRAIN TO ITS CONNECTION TO
 THE STACK VENT. SPC SEC 714.2
 13) AN APPROVED CIVIL DRAWING IS REQUIR-
 ED FOR FINAL APPROVAL OF PLUMBING PLANS.
 14) RPZ BACKFLOW REQUIRED FOR EACH BLDG.
 TYPE I, 2, & 3.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377