| Plan Review Stops For Permit 01110409 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-03-25 |
Time |
16:00 |
Rev Time |
1.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-03-25 00:00:00 | STORM SHUTTERS | | | | | | TYPE I BLDG01110409 | | | TYPE II BLDG01110411 | | | TYPE III BLDG 01110412 | | | | | | REVIEWED WITH KEY PLAN SHUTTER ANCHOR | | | SCHEDULE & TESTING REPORT | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:06 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-12-31 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 01110409 MODEL TYPE I | | | 01110411 MODEL TYPE II | | | 01110412 MODEL TYPE III | | | ADD: 4400 N MILITARY TRAIL | | | CONT: EPOCH PROPERTIES | | | TEL: (561)683-1072 | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | SUBMITTAL: STORM SHUTTERS | | | DENIED | | | | | | 1) PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | SBC 1606.1.4. | | | 2)1997 SBC SECTION 103.6, | | | 1606.1.4& 1707.4 | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING | | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | | SUBMITTED AT TIME OF PERMIT APPLICATION | | | TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | ATTACHED IS A COPY OF THE CITIES | | | STANDARD FOR THE IMPLEMENTATION OF | | | HURRICANE MISSLE IMPACT PROTECTION, | | | IN REGARDS TO PROCEDURES (1 & 2). ALSO | | | ATTACHED IS A COPY OF A SAMPLE SCHEDULE | | | FOR INSTALATION. | | | PLEASE INDICATE WHAT MODEL TYPE | | | BUILDING I,II, OR III. ALSO INDICATE ON | | | THE SCHEDULE WHAT FLOOR YOU ARE INDICAT- | | | ING. THE CITY STATED THAT ALL WINDOWS ON | | | THE 2ND & 3RD FLOOR ARE TO BE LARGE | | | MISSLE TESTED, INDICATE ON THE SCHEDULE. | | | THE CITY AGREED THAT THE SLIDING GLASS | | | DOORS ON THE 2ND & 3RD FLOOR COULD BE | | | SHUTTERED AS STATED IN YOUR LETTER DATED | | | JULY 22,02 WITH ADDITIONAL HELP FROM | | | A TEMP LABOR LETTER DATED AUG 15,02. | | | THE USE OF STORM PANELS FOR FIRST FLOOR | | | OK, AS STATED IN IMPACT STANDARD, WITH | | | THE SCHEDULE FOR INSTALLATION!!!! | | | PLEASE PROVIDE THE ADDITIONAL INFOR- | | | MATION REQUESTED SO WE MAY EXPEDITE THIS | | | MATTER, FOR FURTHER CLARIFICATION | | | CONTACT: | | | JIM WITMER | | | (561) 659-8096 X8412 | | | BUILDING PLAN REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-31 |
Time |
10:55 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-12-31 00:00:00 | SUBMITTAL 12-12-02,DENIED 12-13-02,ONLY | | | 2 SETS OF PLANS SUBMITTED, SPECIAL | | | INSPECTOR PROGRAM IN EFFECT, 3 SETS OF | | | ANY CORESPONDANCE REQUIRED: | | | 1) BUILDING DEPART OFFICE COPY | | | 2) SPECIAL INSPECTOR COPY | | | 3) FIELD SET OF APPROVED DRAWINGS | | | | | | 12/31/02 PLANS ARE BACK ONLY 2 SETS: | | | AGAIN DENIED!!!!!!!! |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-12 |
Time |
13:31 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-11-20 00:00:00 | PRODUCT APPROVALS FOR 2ND/ 3RD FLOOR | | | LARGE MISSLE IMPACT REVIEWED | | | PW6200 ALUM FIXED WIND | | | HS8700 ALUM HOR SLID | | | SH7700 ALUM SINGLE HUNG |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-11-20 |
Time |
16:20 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-11-20 00:00:00 | SHOP DRAWINGS- STAIRSOK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-14 |
Time |
16:26 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-10-21 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2002-10-21 00:00:00 | SHOP DRAWINGS, HEAVY GAUGE EXT STUDS, | | | NO REVIEWED BY ENG OF RECORD G. TSUNG |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-10-03 |
Time |
08:17 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-10-03 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2002-10-03 00:00:00 | 10/03/02 REVISION: BREEZEWAY REDUCTION | | | IN LENGTH BY VARIANCE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-09-02 |
Time |
10:04 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2002-09-02 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2002-09-02 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 01110409 | | | ADD:EPOCH/PORTOFINO/MASTER TYPE I | | | CONT: EPOCH | | | TEL: (561)683-1052 | | | ST BLD CD =1997 STANDARD BUILDING CODE | | | | | | *****PROVISO***** | | | | | | 1) WEDGE-ALL ANCHOR DETAILS, SINCE THE | | | LOADING IS NOT GIVEN FOR TENSION OR | | | SHEAR LOAD APPLICATIONS HAS THE EDGE FAC | | | TOR ( REDUCTION) BEEN FACORED INTO THE | | | SPACING? | | | A) DETAIL "D" S-D1.1 EXTERIOR CONDITION | | | @ LOFT 2X6 WALL SITTING ON TOP OF A 5" | | | CONCRETE WALL? NO INFORMATION IS GIVEN, | | | CONTACT SIMPSON ENG. TO SEE IF A DOUBLE | | | REDUCTION WOULD BE REQUIRED SINCE YOU | | | WOULD BE 2 1/2" AWAY ON BOTH SIDES? | | | B) DETAIL# 3 2X6 WALL AT EDGE OF SLAB, | | | WHAT REDUCTION HAS BEEN TAKEN? HOW FAR | | | AWAY FROM THE EDGE OF THE SLAB SHALL THE | | | WEDGE ANCHOR BE LOCATED? | | | | | | ADDITIONAL INFORMATION SHALL BE OBTAINED | | | TO CLARIFY THE CONDITIONS LISTED ABOVE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-25 |
Time |
17:23 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2002-06-25 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-29 |
Time |
17:33 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2002-04-29 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2002-04-29 00:00:00 | *****BUILDING PROVISO****** | | | | | | MASTER TYPE I | | | | | | SOILS TEST REPORT INDICATES FURTHER | | | INVESTIGATION BEFORE THE PERMIT CAN BE | | | ISSUED. SHOW HOW DENSIFICATION OF SOIL | | | WILL OCCUR. | | | | | | HYDROLIC CALS MISSING FROM PLANS. | | | | | | RESIDENT INSPECTOR TO REGISTER WITH | | | ASSISTANT BUILDING OFFICIAL DON NEELY | | | | | | BUILDING PLANS TO BE SUBMITTED TO COUNTY | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-20 |
Time |
13:06 |
Rev Time |
5.00 |
| Received By |
jwitmer |
Date |
2002-02-20 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110409 | | | BRIGER TRACT "D" | | | BUILDINGTYPE I | | | SECOND REVIEW | | | | | | SBC=1997 STANDARD BUILDING CODE | | | | | | 1)- SBC503.3.1 GENERAL AREA MODIFICATION | | | SHALL BE APPLIED TO TYPE I BUILDING, | | | UNPROTECTED, SPRINKLERED WITH THE USE OF | | | NFPA 13R, THIS COMPLIES WITH FL STATE | | | STATUTE 553.895 (2). | | | 2)- NO SITE SURVEY/ PLOT PLAN "RESPONCE" | | | SEE CIVIL PACKAGE, WHERE, WE HAVE NOT RE | | | CEIVED ANY CIVIL DRAWING AS OF TO DATE. | | | THIS IS A MAJOR CONCERN, WHEN WE DRAFTED | | | THE ADDRESS LIST A TELEPHONE CALL TO | | | EPOCH WAS MADE REVEALING THIS CONCERN! | | | DISCREPANCY, THE FIRST PLAN REVIEW F0.11 | | | REVEALS A SITE LAYOUT DIFFERENT FROM THE | | | SITE LAYOUT DEPICTED ON"TYPE I"S0.10. | | | 2/19/01 TEL. MIKE SPELLMAN AS TO THE | | | DISCREPANCY. MR. SPELLMAN INDICATED THAT | | | THE FIRST DRAWING IS WHAT WAS APPROVED. | | | THE PLANS NEED TO BE CORRECTED, TO | | | FACILITATE PLAN REVIEW A REVIEW OF TABLE | | | 600 REVEILS A PROBLEM BETWEEN BUILDING | | | NUMBER 4 & 16. THERE IS NO DIMENSIONS | | | BETWEEN BUILDINGS TO INDICATE DISTACNES | | | BETWEEN BUILDINGS. | | | 3)- ADDRESSING PER PREVIOUS CONVERSATION | | | THE SITE SHALL HAVE A STREET NAME OF | | | "PORTOFINO WAY". BEFORE PERMITS CAN BE | | | ISSUED A PLAT SHALL BE RECORDED WITH | | | PALM BEACH COUNTY, THE PROPOSED STREET | | | NAME SHOULD APPEAR ON THE PLAT.AGAIN | | | WE HAVE NOT RECEIVED CIVIL DRAWINGS. | | | 4)- EXTERIOR STAIRS, THE FLOOR PLAN | | | DOES INDICATE THAT CODE SECTION 1004.1.4 | | | HAS BEEN MET AS FAR AS 1/2 THE DIAGONAL | | | DISTANCE BETWEEN STAIRS. | | | | | | 1997 SBC 1006.2.1. DOES ALLOW FOR THE | | | USE OF EXTERIOR STAIRS AS AN MEANS OF | | | EGRESS IN BUILDINGS NOT EXCEEDING SIX | | | STORIES, WITHOUT ENCLOSURE REQUIREMENTS. | | | THE EXTERIOR EXITWAY STAIR ARRANGEMENT | | | SHALL CONTAIN 3 PRIMARY FEATURES TO | | | ASSURE THE LEVEL OF PROTECTION NECESS- | | | ARY FOE THE BUILDING OCCUPANTS. | | | | | | FIRST EACH TENANT MUST HAVE ACCESS TO A | | | CHOICE OF EGRESS PATHS LEADING TO INDE- | | | PENDANT AND REMOTELY LOCATED EXTERIOR | | | STAIRS. THE PLANS HAVE BEEN REVISED TO | | | INDICATE SUCH ON LS1.11. | | | | | | THE SECOND PROTECTION FEATURE INVOLES | | | THE DISSIPATION OF SMOKE AND COMBUSTION | | | PRODUCTS, WHILE THE CODE DOES NOT CUR- | | | RENTLY ATTEMPT TO DEFINE THE DEGREE OF | | | OPENNESS THAT MUST BE MAINTAINED. | | | | | | THE THIRD ELEMENT OF EXTERIOR EXIT | | | STAIRS MUST BE FROM DIRECT FIRE EXPOSURE | | | EITHER A 10 FT SEPERATION OF THE STAIR | | | AND BALCONY (BREEZEWAY) FROM THE PROPER- | | | TY LINE AND OTHER BUILDINGS ON THE SAME | | | LOT OR 3/4 HR OPENING PROTECTIVES TO PRO | | | TECT AGAINST EXTERIOR FIRE EXPOSURE.THIS | | | ALSO HAS BEEN ACHIEVED THROUGH THE | | | CURRENT DESIGN. | | | SECTION 1006.2.4 PROVIDES PROTECTION | | | AGAINST INTERIOR EXPOSURE. THIS HAS NOT | | | BEEN ACHIEVED, THE OPENINGS ON EACH SIDE | | | OF THE STAIRWAY SHALL HAVE 45 MINUTE | | | OPENING PROTECTION. THIS PROTECTION | | | SHALL EXTEND FROM THE GROUND TO A POINT | | | 10 FT ABOVE THE TOP MOST LANDING OR THE | | | ROOFLINE AND HORIZONTALLY 10 FT FROM | | | EACH SIDE OF THE STAIRWAY. THIS WOULD | | | PERTAIN TO THE WINDOWS OF EACH UNIT AD- | | | JACENT A STAIRWAY AND THE GARAGE DOORS | | | ADJACENT TO THE STAIRWAY. | | | 5)- WINDERS REVISED OK | | | 6)- GENERAL AREA INCREASE TAAKEN FOR | | | TYPE I BUILDING, NFPA 13-R OK. | | | 7)- SHEET M2.31/ M2.32 INDICATES A RATED | | | CHASE, RESPONCE TO SEAL AT SLABS. | | | SBC 705.6 INDICATES THAT ALL PENETRA- | | | TIONS OF HORIZONTAL SLABS SHALL BE PRO- | | | TECTED BY A SHAFT ENCLOSURE. 705.6.1 | | | DOES GIVE EXCEPTION TO PENETRATIONS THAT | | | PENETRATE A SINGLE FIRE RATED FLOOR OR | | | FLOOR/ CEILING ASSEMBLY, OTHERWISE A | | | RATED SHAFT SHALL BE REQUIRED, PLEASE | | | PROVIDE A UL OR GYPSUM ASSEMBLY NUMBER. | | | 8)- MEZZANINE OK | | | 9)- COMMENT ON DRAFT STOPPING OK | | | BLOCK WALLS EXTENDING ABOVE FLOOR | | | TRUSSES VS ENTRY HALL AND STORE ROOM | | | NEED TO CLARIFY WHERE THIS REVISION | | | IS SHOWN? | | | 10)- FASTENING SUBSTITUTION FASTENING | | | SCHEDULE, NOW MISSING FROM STRUCTURAL | | | SHEETS. | | | 11)- PLANS INDICATE THE USAGE OF 5"X5" | | | STEEL COLUMNS ON THE COLUMN SCHEDULE, | | | DETAIL A/S-D11 MISSING? | | | 12)- ROOF SHEATHING SCHEDULE MISSING , | | | ENGINEER TO INDICATE NAILING SCHEDULE | | | ABOVE 35'. | | | 13)- TRUSS PLAN TO INDICATE THE LOADS | | | TO BE RESISTED AND THE FASTENERS | | | REQUIRED FOR EACH AREA. SEMCO HAS NOT | | | BEEN IN BUSINESS FOR OVER 2 YEARS! | | | 14)- COMPONENTS & CLADDING SBC1606.2.6.2 | | | (3 COPIES) OF PRODUCT TESTING REPORTS | | | FOR EACH BUILDING TYPE.SBCCI OR DADE | | | COUNTY REPORTS ARE ACCEPTED. NORANDEX | | | WINDOWS REQUIRE SITE SPECIFIC REPORT, IF | | | USED (THEY ONLY HAVE BROWARD APPROVAL). | | | WINDOWS,SLIDING GLASS DOORS, EXTERIOR | | | SWING DOORS GARAGE DOORS ASWELL AS | | | ROOFING. SEE CITY INTERPETTATION FOR | | | LARGE MISSLE IMPACT TESTING. | | | 15)- RESIDENT INSPECTOR REQUIRED, SEE | | | DON NEELY FOR INFORMATION. | | | 16)- COUNTY IMPACT FEES TO BE PAID | | | BEFORE ISSUANCE OF BUILDING PERMIT. | | | 17)- CONTRACTOR TO PAY RADON FEES | | | AT TIME OF ISSUANCE. | | | 18)- PLANS TO REFLECT WIND PRESSURE | | | ZONES, FOR WINDOWS AND DOORS, THIS | | | IS COMPLETED. | | | | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-14 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-12-14 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2001-12-14 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110409 | | | BRIGER TRACT "D" | | | BUILDING TYPE I | | | | | | FLOOR AREA: | | | 1ST FL 15,569 SQ FT | | | 2ND FL 15,470 SQ FT | | | 3RD FL9,813 SQ FT | | | LOFT 3,834 SQ FT | | | TOTAL44,686 SQ FT | | | | | | NO SITE SURVEY / PLOT PLAN TO BE ABLE TO | | | CHECK TABLE 600 ISSUES, HORIZONTAL | | | SEPERATION, NOR ADDRESSING. WHAT IS | | | FILED UNDER FIRE IS UNREADABLE AS TO | | | WHAT TYPE OF BUILDINGS OR SITE FEATURES. | | | | | | WILL SITE ADDRESSING TAKE A WINDSOR WAY | | | ADDRESS? OR WILL THERE BE A PRIVATE | | | STREET NAME BE SUBMITTED? WILL TRACT"D" | | | AND TRACT "C" HAVE THE SAME DEVELOPMENT | | | NAME? SINCE THE PROPERTIES ARE ON (2) | | | SEPERATE PROPERTIES THEY WILL REQUIRE | | | 2 ADDRESSES OR WILL THERE BE A UNITY OF | | | TITLE? | | | | | | 1006.2.1 EXTERIOR STAIRS: THE STAIRWAYS | | | DEPCTED DO NOT COMPLY WITH THE DEFINI- | | | TION OF EXTERIOR STAIRS. BREEZEWAY: A | | | COVERED PASSAGEWAY AS BETWEEN A HOUSE/ | | | GARAGE, OFTEN ENCLOSED ON BOTH SIDES, W/ | | | OPEN ENDS AND A ROOF. | | | BALCONY: A PLATFORM PROJECTING FROM THE | | | BUILDING WITH A RAILING. | | | PORCH: A COVERED ENTRANCE | | | A SAMPLE PAGE OF OPEN EXTERIOR STAIRS | | | FROM THE CODE COMMENTARY IS ATTACHED. | | | SBC 1006.2.2 THE STAIR ARANGEMENTS DO | | | NOT MEET THE CRITERIA OF THIS SECTION, | | | THEY DO NOT MEET THE 1/2 THE DIAGONAL, | | | PLUS MEETING THE 10' OPENING PROTECTIVES | | | REQUIRED IN SBC 1006.2.4.OPENING WITHIN | | | THE 10' HORIZONTALLY FROM EACH SIDE OF | | | THE STAIRWAY SHALL BE EQUIPPED WITH FIX- | | | ED 3/4 HR ASSEMBLIES. | | | SBC TABLE 1007.1 CODE COMMENTARY INDICAT | | | ES FOR TYPE V BUILDINGS RESIDENTIAL USE | | | STAIRS 3 STORIES & GREATER REQUIRE NON- | | | COMBUSTIBLE MATERIAL, SHOW COMPLIANCE | | | WITH WOOD TRUSS FLOOR SYSTEM, STRUCTURAL | | | DRAWINGS DO NOT INDICATE THE INTERMEDI- | | | ATE FLOOR LANDINGS. | | | IF STAIR & BREEZEWAY WERE ACCEPTED, THE | | | 1 HR SEPERATION SHALL BE MAINTAINED, | | | M2.1 /M2.32 INDICATE THE BATH EXHAUST | | | THRU TO BREEZEWAY.1006.2.4. | | | | | | SHEET A.3.31-A3.34 ILLEGAL WINDER SEE | | | SECTION 1007.8.1. | | | | | | SHEET A3.34/F2.12 TYPE V FULLY SPRINKLER | | | ED BUILDING. PLANS DO NOT SHOW FIRE | | | SPRINKLERS IN GARAGE OR BREEZEWAY INTERM | | | EDIATE LANDINGS OR ROOF TRUSSES. | | | CS1.01 CODE SUMMARY(E) CONSTRUCTION TYPE | | | RESIDENTIAL FULLY SPRINKLERED.PLANS | | | INDICATE NFPA(13R) THIS SYSTEM WILL NOT | | | ALLOW FOR THE HEIGTH MODIFICATION IN | | | TABLE 500,FOOTNOTE "H".903.2 REQUIREMENT | | | CITY OF RALIEGH, PLEASE CORRECT. | | | | | | SHEET M2.31/ M2.32 NOTE#5 INDICATES A | | | RATED CHASE FOR REFRIGARANT LINES & CON- | | | DENSATE LINES? SEC 705.2.2 SHAFT ENCLOS- | | | URES, GIVE UL OR GYPSUM ASSEMBLY NUMBER. | | | | | | MEZZANINE SECTION 503.2.3: | | | TYPE I BUILD : OK | | | TYPE II BUILD: | | | BALCONY SQ FT OVER | | | SOLARIUM SQ FT OVER | | | TYPE III BUILD: | | | BALCONY SQ FT OVER | | | SOLARIUM SQ FT OVER | | | | | | SHEET A-5.33 DRAFTSTOPPING REQ. 2305.2.2 | | | (2) FL/CEIL ASSEMBLY GARAGE / 2ND FL. | | | A3.3.4 BLOCK DOES NOT EXTEND ABOVE THE | | | FLOOR TRUSSES AT ENTRY HALL? STOREROOMS? | | | | | | SHEET S1.11 FASTENING SUBSTITUTION FAST- | | | ENING SCHEDULE: STATES THAT THE NAILING | | | FASTENERS PATERNS FOR SUBSTITUTE FASTEN- | | | ERS SHALL USE THE SAME SCHEDULE CONVER- | | | SION CHART FOR "ALLOWABLE LOADS ADJUST- | | | MENT FACTORS" NOT THE SAME TENSION LOADS | | | SEE MANUFACTURES LOAD CHARTS. | | | | | | SHEET S3.13 DETAIL #12 INDICATES USE OF | | | COLUMN TO WOOD POST, WHERE IS THIS TO BE | | | USED? | | | | | | ROOF SHEATHING SCHEDULE SBC TABLE 2306.1 | | | (COUNTY AMENDMENTS) ARE GOOD TO A HEIGTH | | | OF 35'. ENGINEER SHALL INDICATE NAILING | | | SCHEDULE FOR ABOVE 35'. | | | | | | SHEET S2.35 ROOF FRAMING PLAN INDICATE | | | THE MAGNITUDE OF LOADS TO BE RESISTED, | | | VERTICAL, HORIZONTAL & GRAVITY AND THE | | | TYPE OF FASTENER REQUIRED FOR EACH AREA. | | | | | | SBC 1606.2.6.2 COMPONENTS & CLADDING | | | DOOR & WINDOW BUCK ATTACHMENTS : NOT | | | FOUND IN STRUCTURAL SHEETS. | | | GLAZED OPENINGS REQUIRE LARGE MISSLE | | | IMPACT RESISTANCE TESTING: SEE CITY | | | POLICY AS TO REQUIREMENTS FOR LARGE | | | COMPLEXES, COPY ATTACHED. (3 COPIES | | | OF PRODUCT APPROVAL SHALL BE REQUIRED | | | FOR EACH TYPE OF OPENING) | | | ROOFING : ROOFING ASSEMBLIES SHALL ALSO | | | REQURIE PRODUCT TESTING REPORTS FOR | | | WIND ZONE 110. | | | MULLIONS SHALL REQUIRE PRODUCT TESTING | | | IF GLAZED UNIT WASN'T TESTED W/ MULLION | | | DADE COUNTY OR SBCCI REPORTS ARE | | | ACCEPTED. | | | | | | THIS PROJECT SHALL QUALIFY FOR A | | | RESIDENT INSPECTOR. THE INSPETOR SHALL | | | MEET WITH ASSISTANT BUILD DON NEELY | | | TO REGISTER BEFOR ISSUANCE OF PERMIT. | | | | | | COUNTY IMPACT FEES SHALL BE PAID BY THE | | | CONTRACTOR, CONTRACTOR SHALL SUBMIT | | | PLANS TO THE COUNTY FOR IMPACT FEE | | | ASSESSMENT. | | | | | | AT TIME OF ISSUANCE CONTRACTOR WILL PAY | | | RADON FEES. | | | | | | PLANS ARE TO STATE CLEARLY ON ELEVATIONS | | | THE APPROPRIATE WIND PRESSURES FOR | | | DOORS AND WINDOWS,INCLUDING END ZONES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-29 |
Time |
11:43 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-04-29 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2003-04-29 00:00:00 | THIS REV,CORRECTLY INCREASES THE SERVICE | | | CONDUCTOR FOR 1200 AMPS (ALUMINUM) AND | | | CORRECTS THE VOLTAGE TO 240 FROM 208. | | | COPPER CONDUCTORS WERE SPEC'D.SAME SIZE | | | AL WERE INSTALLED INCORRECTLY./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-29 |
Time |
08:44 |
Rev Time |
1.50 |
| Received By |
btrobaug |
Date |
2002-11-13 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2002-11-13 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT ALL COUNTERTOP | | | RECEPTACLES MUST COMPLY WITH | | | 210-8(A)(6).SHEETS 3.11 THROUGH 3.15 | | | HAVE SOME "GFI" NOTATIONS REMOVED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-19 |
Time |
20:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-19 |
Time |
20:32 |
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | STAMPED 6/20/02 | | | DV PALMER. | | 2002-06-19 00:00:00 | ****************** NOTE *************** | | | | | | NOTE REDLINED ON PLANS, PERMITS APPLIED | | | FOR AFTER JAN 1,2002 ARE REQ`D TO HAVE | | | ARC FAULT PROTECTION PER 210-12 "99" NEC | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-13 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-13 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2002-06-13 00:00:00 | ************ UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE SAME NOTES AS BEFORE | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-05-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-09 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-09 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2002-05-09 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT E- SHEETS DO | | | NOT HAVE ORIGINAL SIGNATURE FROM THE | | | ARCH/ENGINEER OF RECORD WHICH IS REQ`D | | | UNDER FS/FAC 471.025/481.221 | | | MUST BE AN ORIG SIGNATURE. | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACINGS | | | STILL NEED TO MEET 210-52. PLEASE SEE | | | 210-52C-1AND 210-52A 123 | | | PLEASE ALSO NOTE THAT RAIL SPACE IS | | | CONSIDERED TO BE WALL SPACE. | | | | | | 3)NOTE: PLEASE NOTE THAT PLANS HAVE | | | GONE BACK AND FORTH IN REF TO RIGID AND | | | EMT. PLEASE NOTE THAT PER LOCAL AMEND. | | | EMT SHALL NOT BE USED , IN DIRECT | | | CONTACT WITH EARTH, POURED ETC . PLEASE | | | NOTE IT WAS JUST A NOTE, RIGID MAY BE | | | USED AND ALSO PVC, IMC. PLEASE SEE | | | 348-5 LOCAL AMENDMENTS. | | | | | | 4)NOTE:PLEASE NOTE THAT PER FS/ FAC | | | 553-80, PLANS THAT ARE DENIED MORETHAN | | | 3 TIMES FOR THE SAME COMMENTS ARE | | | SUBJECT TO 4X FEE FOR THE PORTION SET | | | ASIDE FOR PLAN REVIEW OF THE TOTAL | | | PERMIT FEE. (30%) | | | | | | PLEASE NOTE THAT IF A MEETING IS REQ`D | | | OR A CONFERENCE CALL TO CLARIFY ANYTHING | | | AS TO DATE, NO ONE HAS CONTACTED ME | | | WITH ANY QUESTIONS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-18 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-18 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2002-03-18 00:00:00 | ********************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE MISSING LT REQ`D FOR | | | MECH ROOM UPSTAIRS PER 210-70. | | | | | | 2)NOTE: PLEASE NOTE OUTLET SPACING STILL | | | NEEDS TO MEET 210-52. BALCONY/LOFT WALL. | | | BEDROOM WALLS. 2' OF WALL. | | | | | | 3)NOTE: PLEASE NOTE, IT IS NOTED THAT | | | THE FEEDER CONDUITS TO APT UNITS WERE | | | ALSO CHANGED TO "RIGID" CONDUIT. THE | | | COMMENT FROM THE PREVIOS REVIEW WAS FOR | | | SERVICE ENTRANCE CONDUIT ONLY COMING | | | FROM FPL. PLEASE NOTE IF RIGID IS SHOWN | | | THE IT WILL BE REQ`D TO BE INSTALLED. | | | PLEASE VERIFY IF CHANGING APT FEEDER | | | CONDUIT STILL STANDS. RIGID STANDS TO | | | BE MUCH MORE OF AN EXSPENSE. | | | | | | 4)NOTE: PLEASE REMOVE ALL OLD E-SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-06 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-06 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLETS PER | | | 210-52. BALCONY AND WALLS IN BEDROOMS. | | | | | | 2)NOTE: MISSING REQ`D SD`S AT BOTTOM OF | | | STAIRS. NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE CLARIFY EMT AS TYPE OF | | | CONDUIT FOR SERVICE? EMT IS NOT ALLOWED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: PLEASE NOTE THAT OCP NEEDS TO | | | BE SHOWN FOR UNITS. CAN BE TYPICAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-27 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-27 |
Time |
19:46 |
Sent To |
|
|
| Notes |
| 2001-11-27 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE PROVIDE A ONE-LINE | | | DIAGRAM FOR SERVICE RISER. | | | 215-5 | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM.250-50 | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 6)NOTE: PLEASE PROVIDE THE INFORMATION | | | FOR THE FAIR HOUSING ACT 24CFR 100.205 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 7)NOTE: PLEASE PROVIDE EXIT LTS PER | | | FIRE DEPT COMMENTS. | | | | | | 8)NOTE: PLEASE NOTE THAT CLEARENCE FOR | | | STORAGE ROOM LIGHTING FIXTURES.410-8 | | | | | | 9)NOTE: PLEASE NOTE THAT PER LOCAL CODE | | | ALL METHODS IN NOTES FOR SE,NMC MAY NOT | | | BE USED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-05-29 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | N/A | | | 1. SEE PERMIT # 02050423 FOR CIVIL/SITE | | | WORKS REVIEW AND PERMITTING FOR PARCEL-D | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-13 |
Time |
11:00 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-11-13 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | FAILED : | | | 1. SEE PERMIT # 01110408 | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-21 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-21 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-20 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-20 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-04 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-04 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2002-04-04 00:00:00 | A) CIVIL DRAWINGS INDICATING FIRE MAIN | | | LOCATIONS, SIZES AND FIRE HYDRANT | | | LOCATIONS NOT YET APPROVED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-12 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2002-02-12 00:00:00 | 1) CIVIL DRAWINGS ARE REQUIRED SO A | | | REVIEW CAN OCCUR FOR FIRE MAIN, FIRE | | | HYDRANTS, ETC. WET FIRE HYDRANTS ARE | | | REQUIRED PRIOR TO,DURING AND AFTER | | | CONSTRUCTION. | | | 2) DOORS INTERSECT WITH ONE ANOTHER | | | ON THE FIRST FLOOR PLAN. | | | 3) ARCHITECTURAL MATRIX DOES NOT | | | INDICATE ANY FIRE HYDRANT LOCATIONS. | | | ALSO IT APPEARS THAT SECURITY ARMS | | | OR GATES ARE BEING PROVIDED. WHAT | | | PROVISIONS ARE MADE FOR FIRE RESCUE | | | ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN | | | LOSS OF POWER OCCURS. ALL ROADS ARE TO | | | BE A MINIMUM OF AT LEAST 20 FEET IN | | | CLEAR WIDTH AND ABLE TO SUPPORT FIRE | | | APPARATUS. WHAT IS THE DIFFERENCE | | | BETWEEN PHASE ONE AND PHASE TWO. | | | 4) BUILDING ADDRESSES REQUIRED. | | | 5) PLEASE SEE PREVIOUS FIRE PLAN | | | REVIEW NOTES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-26 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-26 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | 1) IT DEPENDS WHEN THE BUILDING IS | | | OFFICIALLY SUBMITTED FOR PERMIT AS TO | | | WHAT FIRE CODE THE BUILDING WILL BE | | | REVIEWED UNDER. JANUARY 1, 2002, THE | | | FIRE PREVENTION CODE WILL BE APPLICABLE | | | WHICH INVOKES THE 2000 LIFE SAFETY CODE. | | | 2) BUILDING ADDRESS REQUIRED. | | | 3) SITE PLAN FOR FIRE PROTECTION | | | DRAWINGS DOES NOT INDICATES STREET | | | NAMES. | | | 4) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH SPRINKLER PLANS. | | | 5) ILLUMINATED EXIT SIGNS NOT SHOWN | | | ON ELECTRICAL DRAWINGS, FLOOR PLANS. | | | 6) FIRE DEPARTMENT CONNECTIONS TO BE | | | LOCATED NO FARTHER 150 FEET TO FIRE | | | HYDRANTS. | | | 7) THE CITY OF RALEIGH NOTED ON PAGE | | | F1.11 | | | 8) TRAVEL DISTANCE UNDER THE 1985 | | | EDITION OF THE LIFE SAFETY CODE ALLOWS | | | ONLY 150 FEET IN SPRINKLERED APARTMENT | | | BUILDINGS. | | | 9) PLEASE EXPLAIN USE OF LOFTS. | | | 10) THIRD FLOOR PLAN ON LS1.12, FIRE | | | RATING APPEARS TO RUN IN MIDDLE OF | | | CORRIDOR. | | | 11) GARAGE DOORS SHWON ON PAGE A2.11 | | | APPEAR TO INTERSECT WITH ONE ANOTHER. | | | 12) WHAT FIRE RATING IS PRESENT FOR THE | | | ALCOVES FROM THE GARAGE AND STORAGE | | | AREAS. | | | 13) IS THERE ANY FIRE SEPARATION FOR | | | THE STORAGE ROOMS. | | | 14) PLEASE INDICATE HEADROOM CLEARANCES | | | FOR THE MEANS OF EGRESS AREAS. | | | 15) WHAT ARE THE ROOMS ADJACENT TO THE | | | STOREROOMS USED FOR. | | | 16) PLEASE VERIFY SEPARATION DISTANCES | | | OF STAIRS. DIMENSIONS ON PAGE A2.11 DO | | | NOT MEET DISTANCES ON PAGE LS1.11. | | | 17) FIRE SPRINKLER PROTECTION NOT SHOWN | | | FOR UNITS A,B, AND C A3.11,A3.12,AND | | | A3.13. | | | 18) DRYER EXHAUST VENTS APPEAR TO | | | PENETRATE EXIT CORRIDORS AND ONE HOUR | | | WALLS. | | | 19) GARAGE DOORS LABELED IN CORRECTLY | | | ON PAGE A5.11. | | | 20) NO RATINGS PRESENT ON DOOR SCHEDULE | | | FOR GARAGE DOORS WHICH APPEAR TO BE | | | PART OF EXIT ACCESS AND COMMUNICATES | | | WITH EXIT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-29 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-29 |
Time |
08:23 |
Sent To |
E |
|
| Notes |
| 2003-04-29 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-03-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-14 |
Time |
10:06 |
Sent To |
B |
|
| Notes |
| 2003-03-14 00:00:00 | TO JW DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-12 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-12 |
Time |
13:31 |
Sent To |
B |
|
| Notes |
| 2002-12-12 00:00:00 | JIM W./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-14 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-14 |
Time |
16:23 |
Sent To |
B |
|
| Notes |
| 2002-11-14 00:00:00 | TO JIM W./WRT | | | TO JIM W./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-06 |
Time |
12:35 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-11-06 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2002-11-06 00:00:00 | REVISIONS DENIED - SPOKE WITH TOM | | | DESSOYE (EPOCH), REQUEST A SUMITTAL LTR | | | FROM THE ENG STATING WHY A DROP IN THE | | | WALK-IN CLOSET IS NEED & REDUCTION OF | | | TONNAGE IN THE A/C UNITS.DUCT MATERIAL | | | & LAYOUT ARE TO GO ACCORDING TO THE | | | APPROVED PLANS ON THE MASTER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-09-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-30 |
Time |
11:21 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-09-30 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2002-09-30 00:00:00 | REVISED PLAN SHEETS M3.11, M3.12, M3.13, | | | M3.14, M3.15, M3.16 - REVISED DUCT LAY | | | OUT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-21 |
Time |
10:01 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-21 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-14 |
Time |
10:03 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-05-14 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2002-05-14 00:00:00 | PLEASE NOTE SOME OF THE MECHANICAL | | | PAGES HAVE A "STAMPED" SIGNATURE FOR THE | | | ENGINEER INSTEAD OF A SIGNATURE.UNDER | | | THE PROVISIONS OF CHAPTER 471 OF THE | | | FLORIDA STATUES, ALL PAGES SHALL HAVE | | | AN ORIGINAL SIGNATURE NOT A STAMP. | | | | | | BUILDING PERMIT 01110409 | | | | | | PROVIDE RATING OF UL425 FOR THE DRYER | | | CHASE (1 HR, 2 HR?). | | | | | | SPECIFICATION FOR SPECIFIC DRYER ALSO | | | SUBMITTED INDICATING THE ALLOWABLE | | | LENGTH OF DUCT EXCEEDING THE CODE | | | REQUIREMENT.PLEASE NOTE DRYERS SHALL | | | BE INSTALLED FOR FINAL INSPECTION. | | | | | | DETAIL FOR THE RESTROOM EXHAUST VENTING | | | ON PLAN SHEET M5.33, PLEASE NOTE SHOULD | | | THE ALTERNATE DISCHARGE THROUGH THE ROOF | | | BE USED IT SHALL COMPLY WITH 1997 SMC | | | 610.4. (DUCTS PENETRATING MORE THAN 1 | | | FLOOR SHALL BE PROTECTED BY A SHAFT | | | ENCLOSURE). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-13 |
Time |
09:27 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2002-03-12 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2002-03-13 00:00:00 | | | | | | | DRYER EXHAUST FOR THE INTERIOR | | | APARTMENTS - HVAC SHEET NOTES - #84" | | | METAL DRYER EXHAUST VENT ROUTED UP IN | | | CHASE & THROUGH THE ROOF.PLEASE | | | PROVIDE DETAIL OF "CHASE".DUCTS | | | EXTENDINGTHROUGH MORE THAN ONE FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4. | | | | | | PLEASE NOTE, THE MAXIMUM LENGTH SHALL | | | NOT EXCEED 25 FT FROM DRYER LOCATION TO | | | WALL OR ROOF CAP.THERE SHALL BE A 5 | | | FT DEDUCTION FOR EACH 90 DEGREE BEND & | | | 2 1/2 FT DEDUCTION FOR EACH 45 DEGREE | | | BEND.THE WALL OR ROOF CAP SHALL BE | | | NONSCREENED WITH BACK DRAFT DAMPER. | | | 1997 SMC 509.3 | | | | | | BATHROOM EXHAUST - WALL CAP SHALL BE | | | SCREENED.PLEASE INDICATE ACCESS FOR | | | THE FIRE DAMPER AS PER 1997 SMC 610.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-07 |
Time |
07:59 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-07 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2002-02-07 00:00:00 | | | | | | | BUILDING TYPE I - PERMIT 01110409 | | | | | | AS PER 2000 LIFE SAFETY CODE CHAPTER 7 - | | | 7.1.3.1 EXIT ACCESS CORRIDORS | | | | | | (E) PENETRATIONS INTO AND OPENINGS | | | THROUGH AN EXIT ENCLOSURE ASSEMBLY | | | SHALL BE PROHIBITED EXCEPT FOR THE | | | FOLLOWING. | | | | | | (1) ELECTRICAL CONDUIT SERVING THE | | | STAIRWAY | | | (2) REQUIRED EXIT DOORS | | | (3) DUCTWORK & EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION | | | (4) WATER OR STEAM PIPING NECESSARY | | | FOR THE HEATING OR COOLING OF THE | | | EXIT ENCLOSURE | | | (5) SPRINKLER PIPING | | | (6) STANDPIPES | | | | | | ALSO AS PER 1997 SMC 610.1.2, FIRE | | | DAMPERS REQUIRED WHERE DUCTS PENETRATE | | | WALLS OR PARTITIONS HAVING A FIRE | | | RESISTANCE RATING OF 1 OR MORE HOURS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-12 |
Time |
14:10 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-12 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | RESTAMP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
F |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-06 |
Time |
18:45 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-12-06 |
Time |
18:45 |
Sent To |
|
|
| Notes |
| 2002-12-06 00:00:00 | REVISION OK - CHANGED VENT THRU ROOF TO | | | C/2 STACKS | | | | | | REVIEW CHANGED TO FAILED - NO CHANGES TO | | | MASTER - ALL REVISIONS TO BE SUBMITTED | | | FOR EACH PERMIT NUMBER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2002-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-06 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-06 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2002-09-06 00:00:00 | REVISION OK - SHT P5.11 SANT RISERS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-08-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-28 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-28 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2002-08-28 00:00:00 | REVISION OK - SHT P2.11 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2002-07-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-22 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-22 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2002-07-22 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SANITARY RISERS A1, A2, B1, & B2- | | | NO KITCHEN SINK OR WASHING MACHINE TRAP | | | SHALL BE PLACED ON A 2" COMBINED WASTE | | | AND VENT. 3" WASTE AND VENT STACK REQD. | | | SECT. 911.4-SHT P5.11 | | | | | | 2) NO VENT THRU ROOF SHOWN ON ANY STACK. | | | PLEASE INDICATE WICH STACK/STACKS WILL | | | VENT THRU ROOF.SHT P5.11 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2002-07-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-11 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-11 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2002-07-11 00:00:00 | REVISION OK - CHANGED BLDG DRAIN TO ONE | | | LINE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-14 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-14 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-14 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-14 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-08 |
Time |
18:08 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-03-08 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2002-03-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN | | | MANUAL | | | | | | 1) FROM PREVIOUS REVIEW - SHT A0.11 UNIT | | | TYPE A, B, & C NOW, INDICATE SPECIFICAT- | | | A OR B, ONE OR THE OTHER. BOTH A OR B | | | IS NOT AN OPTION. | | | 2) FROM PREVIOUS REVIEW - SHT A0.11 SEE | | | REVIEW NOTE #1. SEE FHA DESIGN MANUAL | | | FOR DIFFERENCE BETWEEN SPECIFICATION A | | | OR B ON FLOOR LAY OUT. | | | 3) FROM PREVIOUS REVIEW - CLEAR FLOOR | | | SPACE FOR LAVS NOT SHOWN. CLEAR FLOOR | | | SPACE FOR SHOWERS NOT SHOWN. | | | 4) FROM PREVIOUS REVIEW - ALL DIMENTIONS | | | FOR ALL W/'S NOT SHOWN. SEE BATHROOMS | | | #B307 & #C110. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA AMEND-98 DESIGN | | | MANUAL | | | | | | 1) SHT A0.11 UNIT TYPE A, INDICATE SPEC- | | | IFICATION A OR B FOR BATHROOM AS REQUES- | | | TED IN PREVIOUS PLAN REVIEW. | | | 2) SHT A0.11 HAS SPECIFICATION B LAY OUT | | | AND SPEC. A CALLED OUT. TYPICAL FOR RM | | | #'S B201, A101, AND C101. PLEASE CLAIRFY | | | 3) SHT A0.11 CLEAR FLOOR SPACE NOT SHOWN | | | ON KITCHEN FIXTURES AND/OR APPLIANCES AS | | | REQUIRED IN FHA DESIGN MANUAL. | | | 4) SHT A0.11 SHOW CLEAR FLOOR SPACE FOR | | | ALL LAVS WHICH SHALL BE CENTERED ON | | | CLEAR FLOOR SPACE, AND SHOW CLEAR FLOOR | | | SPACE PROPERLY AT ALL TUBS AND SHOWERS. | | | SEE FHA DESIGN MANUAL FOR EXAMPLES. | | | 5) SHT A0.11 ALL DIMENSIONS FOR WATER | | | CLOSETS NOT SHOWN. SEE B-307 AN C-110. | | | SHOWN IS 15" TO CENTER FROM ONE SIDE BUT | | | NO MEASUREMENT FROM OTHER SIDE. 33" MIN. | | | REQUIRED. | | | 6) SHT 2.12 SHOW ALL CLEANOUTS ON RISER | | | DIAGRAM, | | | 7) SHT P5.11 SANITARY RISER (B-2) STILL | | | REDUCES FROM 3" TO 2" ON RISER. 3" SHALL | | | RUN UNDIMINISHED FROM CONNECTION TO BLDG | | | DRAIN TO CONNECTION TO STACK VENT. | | | SPC SEC 714.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-30 |
Time |
14:24 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2001-11-30 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2001-11-30 00:00:00 | DENIED | | | REFERENCE: SPC-94- FHA AMEND-98 | | | DESIGN MANUAL | | | | | | 1) SHT A0.31 FAIR HOUSING PLANS. FHA-98 | | | DESIGN MANUAL, PLEASE COMPLY WITH REQ- | | | UIREMENTS 1 THRU 7. REQ 7 PART B, PLEASE | | | INDICATE SPECIFICATION A OR B FOR EACH | | | FIRST FLOOR UNIT. | | | 2) SHT A0.31, PLEASE SHOW CLEAR FLOOR | | | SPACE FOR ALL REQUIRED FIXTURES. (SEE | | | PAGE 7.43) | | | 3) TYPICAL DOUBLE LAV - OFFSET BASIN AT | | | DOUBLE LAVS, (SEE PAGE 7.48), FOR COUNT- | | | ER AT LEAST 60" LONG. FOR SHORTER COUNT- | | | ERS FORWARD APPROACH IS REQUIRED AND THE | | | VANITY WILL HAVE TO BE REMOVABLE. (SEE | | | PAGE 7.49) GIVE A DETAIL IN PLANS | | | 4) SHOW DEMENSIONS FOR ALL 1ST FLOOR W/C | | | OPENINGS THAT HAVE NO DEMEMTIONS. | | | 5) SHT P2.31 2-WAY CLEAN OUTS ARE REQUI- | | | RED AT EACH BREEZWAY. SPC SEC 710.2.4 | | | MAXIMUM 80' BETWEEN C/O'S. | | | 6) TYPICAL OF ALL UNITS, MAXIMUM 6' FOR | | | 2" TRAP FROM VENT. SPC TABLE 908.1. TUBS | | | SCALE OUT TO BE FARTHER THAN ALLOWED. | | | 7) PROVIDE SANITARY RISER DIAGRAM FOR | | | FIRST FLOOR HORIZONTAL BLDG DRAIN. SHOW | | | ALL PIPE SIZES AND DRAINAGE FIXTURE | | | UNITS EACH SECTION OF PIPE DRAINS. SHOW | | | NUMBER OF FIXTURE UNITS DRAINING FROM | | | EACH SANITARY RISER. (STACK) | | | 8) SHT P4.31 WATER HEATER DETAIL. DI- | | | ELECTRIC UNIONS NOT APPROVED. | | | 9) SHT P4.31 DETAILS 6D & 7D WATER METER | | | NOT APPROVED PER CITY CODE SEC 31-29 | | | SEE ATTACHED SHEET. | | | 10) SHT PR.31 WATER HEATER DETAIL. SAFE- | | | TY PAN SHALL BE OF SUFFICIENT SIZE AND | | | SHAPE TO RECIEVE ALL DRIPPINGS OR CON- | | | DENSATE FROM TANK OR HEATER - DRAIN | | | VALVE MUST BE INSIDE PAN. SEC 507.8.2 | | | 11) SHT P4.31 ELECT. WATER HEATER SCHED. | | | PER SPC TABLE 504 B-UNITS SHALL HAVE 40 | | | GAL W/HEATERS. C-UNITS SHALL HAVE 50 GAL | | | W/HEATERS. ONLY 30 & 40 ARE SHOWN. | | | 12) SHT P5.31 SANITARY RISERS B1 & B2 | | | SHALL NOT REDUCE TO 2", BUT SHALL RUN | | | UNDIMINISHED IN SIZE FROM ITS CONNECTION | | | TO THE BLDG DRAIN TO ITS CONNECTION TO | | | THE STACK VENT. SPC SEC 714.2 | | | 13) AN APPROVED CIVIL DRAWING IS REQUIR- | | | ED FOR FINAL APPROVAL OF PLUMBING PLANS. | | | 14) RPZ BACKFLOW REQUIRED FOR EACH BLDG. | | | TYPE I, 2, & 3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|