Plan Review Details - Permit 01110408
Plan Review Stops For Permit 01110408
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-30 Cont ID  
Sent By jwitmer Date 2002-05-30 Time 08:16 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-03-26 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 12:39 Rev Time 0.00
Received By jwitmer Date 2002-03-26 Time 13:22 Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110408
 SITE AMENITIES
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 BATH HOUSE & REMOTE GARAGE PLAN
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 3 COPIES OF ALL PRODUCT ACCEPTANCE TEST-
 ING REPORTS SHALL BE REQUIRED FOR: ALL
 GLAZED OPENINGS, EXT. DOORS, SKYLIGHTS,
 GLASS BLOCK,STORM SHUTTERS AS WELL AS
 ROOFING ASSEMBLIES.WHEN REPORTS ARE NOT
 FILED, PLANS ARE APPROVED, WITH THE
 STIPULATION THAT A SEPERATE PERMIT WITH
 ASSOCIATED FEES SHALL BE REQUIRED, ALSO
 THE CITIES GUIDELINES FOR LARGE PROJECTS
 REGARDING PROTECTION FOR ALL GLAZED OPEN
 INGS SHALL BE ADHERRED TO, SEE ATTACHED
 GUIDELINES. THE BUILDING OFFICIAL SHALL
 REVIEW AND APPROVE ALL PROPOSED PRE-
 STORM PREPERATION PLAN.
  
 2)- THE TRUSS & GIRDER LAYOUT DOES NOT
 INDICATE THE UPLIFT LOADS TO BE RESISTED
 THERE IS A ANCHOR SCHEDULE INDICATING
 WHAT TYPE OF ANCHORS ARE TO BE USED.
 WITH OUT THIS INFORMATION BEOFRE THE
 ISSUANCE OF A BUILDING PERMIT THE ARCH
 AND ENGINEER SHALL BE REQUIRED TO
 REVIEW THE TRUSS PLAN LAYOUT AND ENGINEE
 RING CERTIFYING BY AFFIDAVIT THAT THIS
 TRUSS LAYOUT AND ATTACHMENT SHALL MEET
 ALL THE REQUIREMENTS OF THIS CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-21 Cont ID  
Sent By jwitmer Date 2002-02-21 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2002-02-21 Time 12:39 Sent To  
Notes
2002-02-21 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110408
 SITE AMENITITES
  
 SBC= 1997 STANDARD BUILDING CODE
  
 BATH HOUSE
  
 1) SBC1804.2.7.2(3) MISSING SOILS REPORT
 2)- MISSING PRODUCT TESTING REPORTS FOR
 WINDOWS,DOORS (SWING & OVERHEAD)
 3)- THE TRUSS & GIRDER LAYOUT DOES NOT
 INDICATE THE UPLIFT LOADS THAT THE
 ANCHORS SHALL BE REQUIRED TO RESIST.THE
 ANCHOR SCHEDULE GIVES WHAT THE ANCHOR
 WILL BE ABLE TO RESIST!
  
 TRASH COMPACTOR
 COMMENTS FROM PREVIOUS REVIEWS COMPLETED
  
 REMOTE GARAGE PLAN
 1)- SBC 1804.2.7.2(3) SOIL REPORT/
 W MINIMUM BEARING VALUE.
 2)- DESIGN PERAMETERS, OPEN, PARTIALLY
 OPEN? NO INDICATION
 3)- WHAT WILL THE USAGE BE FOR THE OPEN
 HALF? CARWASH?
 4)- AGAIN THE TRUSSES DO NOT GIVE THE
 UPLIFT VALUES, ONLY AN ANCHOR SCHEDULE?
 5)- SBC1606.2.6.2 COMPONENTS & CLADDING
 3 COPIES OF PRODUCT APPROVALS, SBCCI OR
 DADE COUNTY PRODUCT TESTING REPORTS.
 FOR WINDOWS, DOORS (SWING & OVERHEAD)
 AS WELL AS ROOFING MATERIALS.
 6)- PLANS ARE TO BE SUBMITTED TO COUNTY
 BUILDING DEPT FOR ASSESSMENT FOR COUNTY
 IMPACT FEES.
 RADON FEES TO BE COLLECTED BY CITY FOR
 STATE.
 PROJECT SHALL REQUIRE A RESIDENT INSPECT
 OR, SEE DON NEELY BEFORE PERMIT CAN
 BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-08 Cont ID  
Sent By jwitmer Date 2001-12-08 Time 08:17 Rev Time 4.00
Received By jwitmer Date 2001-12-08 Time 08:17 Sent To  
Notes
2001-12-08 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW# 01110408
 ADDRESS: TO BE DETERMINED
 VILLAGE WEST LUXURY APARTMENTS
 PARCEL "D" PHASE I
 OWN: EPOCH PROPERTIES
 TEL (407) 644-9055
 FAX (407) 644-9845
  
 PLAN REVIEW WILL BE COMPLETED UNDER THE
 1997 STANDARD BUILDING CODE.
  
 SITE AMENITIES: A CLEAR SITE PLAN SHALL
 BE REQUIRED DESCRIBING THE TYPES OF
 BUILDINGS, POOLS, CABANAS, THE GATE
 HOUSE, SITE WALLS OR FENCES, SIGNAGE
 AND DUMPSTER LOCATION.
  
 FAIR HOUSING ACT REQUIRES AN ACCESSIBLE
 ROUTE FROM THE PUBLIC TRANSPORTATION
 STOP, THIS ACCESSIBLE ROUTE SHALL
 CONNECT BUILDINGS ALL COMMON ELEMENTS,
 SPACES & ELEMENTS. INDICATE WHERE THE
 MAIL CENTERS WILL BE & AND A CONTINIOUS
 PATH.
  
 PHASE I TO PHASE II WILL THERE BE 2 DIF-
 FERENT PROJECT NAMES & ADDRESSES?
  
 BATH HOUSE
 A2.51/S1 BATH HOUSE PLANS DO NOT GIVE
 THE FLOOR & WALL FINISHES REQUIRED SBC
 1204.2 PUBLIC RESTROOMS, WALLS & FLOORS
 OF ALL PUBLIC RESTROOMS SHALL BE LINED
 WITH AN NONABSORBANT MATERIAL TO A
 HEIGTH OF 4'-0" ABOVE THE FLOOR.
  
 FLOOR FINISH, FAIR HOUS. ANSI TECH
 REQUIREMENTS A4.5 GROUND & FLOOR SURFACE
 REQUIRE A STATIC COEFICIENT OF FRICTION
 OF 0.6 FOR ACCESSIBLE ROUTES AND 0.8
 FOR RAMPS.
  
 SOILS TREATMENT PLANS INDICATE A TERMITE
 PRETREATMENT BEFORE PLACEMENT OF CON-
 CRETE BUT NEGLETE SECTION SBC 1814.3.3
 1814.3.3 DAMPPROOFING OF SLAB.
  
 THE ARCH. NOR STRUCTURAL PLANS DO NOT
 INDICATE THE BASIC WIND VELOCITY
 PRESSURE, NOR MEAN ROOF HEIGTH.
  
 MISSING SBC 1804.2.7.2(3) SOILS REPORT
 GIVING THE MINIMUM SAFE BEARING VALUE
  
 NOTE: ACTUAL DESIGN PRESSURES FOR ALL EX
 TERIOR WINDOWS, DOORS, GARAGE DOORS AND
 SIMILAR ENVELOPE ELEMENTS MUST BE INDICA
 TED ON CONSTRUCTION PLANS (ELEVATION).
  
 PRODUCT APPROVALS: PRODUCT APPROVALS
 SHALL BE REQUIRED (3 COPIES RESIDENET
 INSPECTOR PROGRAM) FOR ALL OPENINGS OF
 THE EXTERIOR ENVELOPE, SEE CITIES
 STANDARD FOR IMPLEMENTATION FOR HURRI-
 CANE MISSLE IMPACT PROTECTION.SBCCI OR
 DADE COUNTY REPORTS. BUCK ATTACHMENT!
  
 ROOF ASSEMBLIES SHALL REQUIRE PRODUCT
 TESTING BY AN APPROVED TESTING AGENCY.
  
 GENERAL NOTES S1.11 :
 1) REMOVE NOTES ABOUT NORTH CAROLINA
 AMENDMENTS.
 2) FOUNDATIONS SOILS REPORT REQUIRED
 3) SBC 1804.1.3 MINIMUM FOUNDATION
 DEPTH BOTTOM OF FOUNDATION MINIMUM OF
 12" BELOW GRADE.
  
 TRUSS & GIRDER LAYOUT DOESN"T INDICATE
 THE VERTICAL, HORIZONTAL NOR GRAVITY
 LOADS IMPOSED, KNEE WALL SHALL REQUIRE
 A DETAIL SHOWING CONTINIOUS LOADING.
 HURRICANE ANCHOR SCHEDULE DOESN'T INDICA
 TE THE LOCATION OF THE ANCHOR TO BE USED
  
  
 TRASH COMPACTOR:
  
 RAMP SHALL COMPLY WITH FAIR HOUSING
 ANSI 4.8 RAMPS ABOVE 30" REQUIRE AN
 INTERMEDIATE LANDING.
  
 THE RAMP THAT A HANDICAPPED PERSON
 WOULD USE, WHAT STOPS THE PRSON FROM
 GOING OVER THE EDGE?
  
 GAURDHOUSE
 IS THIS STUCTURE HANDICAPPED ACCESSIBLE?
 THERE ARE NO RESTROOM FACILITIES?
 PRODUCT APPROVALS REQUIRED.
 TRUSS LAYOUT WITH ANCHOR SCHEDULE & THE
 LOADS TO BE REISTED.
 ROOFING REPORTS MISSING.
  
 REMOTE GARAGE PLAN:
 THE PREVIOUS COMMENTS FROM THE BATH
 HOUSE ARE IN AFFECT. SOILS REPORT,
 DAMP PROOFING, PRODUCT APPROVALS,
 DESIGN PRESSURES TO BE INDICATED ON PLAN
 MISSING INFORMATION AS TO TRUSS TIE
 DOWN.
 HOW IS THIS BUILDING DESIGNED? SCLOSED,
 PARTIALLY OPEN OR OPEN? USE FACTOR?
 SBC AMENDMENT 1606.4.2 EXCEPTION(6).
  
 WHAT IS THE ACTUAL USAGE OF THIS BUILD-
 ING, IS HALF OF THE BUILDING TO BE A
 CAR WASH?
  
 THE INTERIOR FINISH NOT GIVEN, WALLS
 & CEILING?
  
 THE ENCLOSED SECTION OF THIS STRUCTURE
 DOES NOT MEET THE EGRESS REQUIREMENTS
 OF 1012.1.1.
  
 PLANS ARE NOT INCLUDED INDICATING FRONT
 ENTRY GATES, WIDTH OF OPENINGS.PHASE 1
 TO PHASE II, WILL THERE BE A CONTINIOUS
 ROAD BETWEEN THE 2 PHASES?
  
 BEFORE ISSUANCE OF PERMIT,CONTRACTOR
 SHALL HAVE PLANS ASSESSED FOR COUNTY
 IMPACT FEES, COUNTY BUILDING DEPARTMENT
  
 STATE RADON FEES TO BE PAID TO CITY
 AT TIME OF ISSUANCE @ $.01 SQ.FT.
  
 THIS SITE SHALL REQUIRE A RESIDENT IN-
 SPECTOR, A MEETING WITH ASSISTANT BUILD-
 ING OFFICIAL DON NEELY SHALL BE REQUIRED
 TO REGISTER THE COMPANY & INSPECTOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-06-20 Cont ID  
Sent By dpalmer Date 2002-06-20 Time 05:50 Rev Time 0.00
Received By dpalmer Date 2002-06-20 Time 05:50 Sent To  
Notes
2002-06-20 00:00:00PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-05-10 Cont ID  
Sent By dpalmer Date 2002-05-10 Time 07:00 Rev Time 0.00
Received By dpalmer Date 2002-05-10 Time 07:00 Sent To  
Notes
2002-05-10 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE SHEET E2.51 DOES
 NOT HAVE AN ORIGINAL "WET" SIGNATURE.
 PLEASE NOTE THAT PER FS/FAC PLANS
 THAT ARE SIGNED AND SEALED MUST HAVE
 ORIG SIGNATURE. 471.025/481.221 FOR
 ARCHS/ENGINEERS.
  
 PLEASE SUBMITNEW SHEETS FOR E 2.51.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-18 Cont ID  
Sent By dpalmer Date 2002-03-18 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2002-03-18 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2002-02-06 Time 19:15 Sent To  
Notes
2002-02-06 00:00:00********************* UNSAT ************
  
 PLEASE NOTE THAT NNOTES FROM
 FIRST REVIEW WERE NOT ADDRESSED.
  
  
 1)NOTE: PLEASE NOTE MEANS OF DISCONNECT
 AT EACH DETACHED BLDG. 225-31
  
 2)NOTE: PLEASE CLARFIY GROUNDING
 ELECTRODE FOR GARAGE. #10? PLEASE SEE
 250-32.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 16:45 Sent To  
Notes
2001-11-28 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE MEANS OF DISCONNETCS
 FOR EACH DETACHED BLDG.225-31
  
 2)NOTE: PLEASE CLARIFY "GROUNDING "
 SHOWN AT GARAGE ON E2.51
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2002-05-10 Cont ID  
Sent By mamini Date 2002-05-10 Time 12:53 Rev Time 0.00
Received By mamini Date 2002-05-10 Time 12:53 Sent To  
Notes
2002-05-10 00:00:00N/A
 1. SEE PERMIT # 02050423 FOR CIVIL/SITE
 WORK REVIEW AND PERMITTING FOR PARCEL-D
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-04-30 Cont ID  
Sent By mamini Date 2002-04-30 Time 15:53 Rev Time 0.00
Received By mamini Date 2002-04-30 Time 15:53 Sent To  
Notes
2002-04-30 00:00:00FAILED:
 1. SEE ENGINEERING REVIEW COMMENTS DATED
 11-13-01.
 2. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDERGROUND UTILITIES /SITE
 WORKS WILL BE REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mamini Date 2001-11-13 Time 10:46 Rev Time 1.00
Received By mamini Date 2001-11-13 Time 10:45 Sent To  
Notes
2001-11-13 00:00:00FAILED :
 1. INSUFFICENT INFORMATIONS FOR CIVIL
 ENGINEERING REVIEW, PLEASE SUBMIT CIVIL
 PLANS FOR OUR REVIEW AND APPROVAL.
 CIVIL PLANS SHOULD INCLUDE STORM WATER
 CALCULATIONS, PERVIOUS AND IMPERVIOUS
 CALCULATIONS AND POLLUTOIN PREVENTION
 FOR ENTIRE SITE.
 2. WE RECOMMEND A SEPARATE PERMIT
 APPLICATION FOR UNDERGROUND UTILITIES /
 PAVEMENT AND SITE WORKS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-03-27 Cont ID  
Sent By mcarsill Date 2002-03-27 Time 13:16 Rev Time 0.00
Received By mcarsill Date 2002-03-27 Time 13:16 Sent To  
Notes
2002-03-27 00:00:00A) CIVIL DRAWINGS INDICATING FIRE MAIN
 LOCATIONS, SIZES AND FIRE HYDRANT
 LOCATIONS NOT YET APPROVED.
 B) MORE DETAILS REQUIRED ON ENTRY
 DETAIL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 09:33 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 09:33 Sent To  
Notes
2001-11-26 00:00:001) ANY AND ALL SECURITY FEATURES MUST
 BE APPROVED BY THIS DEPARTMENT. PLEASE
 CONFIRM WITH THIS DEPARTMENT IN WRITING
 ANY SECURITY FEATURES THAT ARE PLANNED.
 THESE INCLUDE GATES, ETC. PROVISIONS
 MUST BE MADE FOR FIRE RESCUE ACCESS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-09-07 Cont ID  
Sent By hmoser Date 2002-09-07 Time 07:15 Rev Time 1.00
Received By hmoser Date 2002-09-07 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-21 Cont ID  
Sent By pkrauss Date 2002-06-21 Time 09:12 Rev Time 0.40
Received By pkrauss Date 2002-06-21 Time 09:12 Sent To  
Notes
2002-06-21 00:00:00APPROVED 3/15/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-14 Cont ID  
Sent By pkrauss Date 2002-03-14 Time 08:54 Rev Time 0.30
Received By pkrauss Date 2002-03-14 Time 08:54 Sent To  
Notes
2002-03-14 00:00:00 
 PLAN REVIEW FOR POOL BATHROOM - APPROVED
  
 NO MECHANICAL PLANS SUBMITTED FOR THE
 GARAGE OR THE GUARD HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-05-24 Cont ID  
Sent By kstevens Date 2002-05-24 Time 19:37 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 19:36 Sent To  
Notes
2002-05-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEWS. SUBMIT PLANS
 TO PLAM BEACH COUNTY HEALTH DEPT FOR
 REVIEW PRIOR TO PLUMBING PLAN REVIEW.
 FOURTH NOTICE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-03-15 Cont ID  
Sent By kstevens Date 2002-03-15 Time 09:47 Rev Time 0.50
Received By kstevens Date 2002-03-15 Time 09:47 Sent To  
Notes
2002-03-15 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FROM PREVIOUS REVIEWS. SUBMIT PLANS
 TO PALM BEACH COUNTY HEALTH DEPT FOR
 REVIEW BEFORE PLUMBING PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 17:24 Rev Time 0.50
Received By kstevens Date 2002-02-08 Time 17:24 Sent To  
Notes
2002-02-08 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PER PREVIOUS REVIEW - SHT A2.51 BATH
 HOUSE PLAN. PALM BEACH COUNTY HEALTH
 DEPT. PLAN REVIEW AND COMMENTS PRIOU TO
 PLUMBING PLAN REVIEW. RESPONSE NOTED,
 BUT PLANS SHALL BE REVIEWED AND STAMPED
 BEFORE PLUMBING PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By kstevens Date 2001-11-30 Time 17:11 Rev Time 0.50
Received By kstevens Date 2001-11-30 Time 17:10 Sent To  
Notes
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A2.51 BATH HOUSE PLANS. PALM
 BEACH COUNTY HEALTH DEPT. PLAN REVIEW
 AND COMMENTS PRIOR TO PLUMBING PLAN RE-
 VIEW.
  
 2) IRRIGATION PLANS AND LOCATION OF BACK
 FLOW REQUIRED. BACKFLOW INSTALLATION TO
 BE BY PLUMBING CONTRACTOR.
  
 3) APPROVED CIVIL PLANS REQUIRED FOR
 PLUMBING PLANS APPROVAL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377