| 2001-12-08 00:00:00 | BUILDING PLAN REVIEW |
| | PLAN REVIEW# 01110408 |
| | ADDRESS: TO BE DETERMINED |
| | VILLAGE WEST LUXURY APARTMENTS |
| | PARCEL "D" PHASE I |
| | OWN: EPOCH PROPERTIES |
| | TEL (407) 644-9055 |
| | FAX (407) 644-9845 |
| | |
| | PLAN REVIEW WILL BE COMPLETED UNDER THE |
| | 1997 STANDARD BUILDING CODE. |
| | |
| | SITE AMENITIES: A CLEAR SITE PLAN SHALL |
| | BE REQUIRED DESCRIBING THE TYPES OF |
| | BUILDINGS, POOLS, CABANAS, THE GATE |
| | HOUSE, SITE WALLS OR FENCES, SIGNAGE |
| | AND DUMPSTER LOCATION. |
| | |
| | FAIR HOUSING ACT REQUIRES AN ACCESSIBLE |
| | ROUTE FROM THE PUBLIC TRANSPORTATION |
| | STOP, THIS ACCESSIBLE ROUTE SHALL |
| | CONNECT BUILDINGS ALL COMMON ELEMENTS, |
| | SPACES & ELEMENTS. INDICATE WHERE THE |
| | MAIL CENTERS WILL BE & AND A CONTINIOUS |
| | PATH. |
| | |
| | PHASE I TO PHASE II WILL THERE BE 2 DIF- |
| | FERENT PROJECT NAMES & ADDRESSES? |
| | |
| | BATH HOUSE |
| | A2.51/S1 BATH HOUSE PLANS DO NOT GIVE |
| | THE FLOOR & WALL FINISHES REQUIRED SBC |
| | 1204.2 PUBLIC RESTROOMS, WALLS & FLOORS |
| | OF ALL PUBLIC RESTROOMS SHALL BE LINED |
| | WITH AN NONABSORBANT MATERIAL TO A |
| | HEIGTH OF 4'-0" ABOVE THE FLOOR. |
| | |
| | FLOOR FINISH, FAIR HOUS. ANSI TECH |
| | REQUIREMENTS A4.5 GROUND & FLOOR SURFACE |
| | REQUIRE A STATIC COEFICIENT OF FRICTION |
| | OF 0.6 FOR ACCESSIBLE ROUTES AND 0.8 |
| | FOR RAMPS. |
| | |
| | SOILS TREATMENT PLANS INDICATE A TERMITE |
| | PRETREATMENT BEFORE PLACEMENT OF CON- |
| | CRETE BUT NEGLETE SECTION SBC 1814.3.3 |
| | 1814.3.3 DAMPPROOFING OF SLAB. |
| | |
| | THE ARCH. NOR STRUCTURAL PLANS DO NOT |
| | INDICATE THE BASIC WIND VELOCITY |
| | PRESSURE, NOR MEAN ROOF HEIGTH. |
| | |
| | MISSING SBC 1804.2.7.2(3) SOILS REPORT |
| | GIVING THE MINIMUM SAFE BEARING VALUE |
| | |
| | NOTE: ACTUAL DESIGN PRESSURES FOR ALL EX |
| | TERIOR WINDOWS, DOORS, GARAGE DOORS AND |
| | SIMILAR ENVELOPE ELEMENTS MUST BE INDICA |
| | TED ON CONSTRUCTION PLANS (ELEVATION). |
| | |
| | PRODUCT APPROVALS: PRODUCT APPROVALS |
| | SHALL BE REQUIRED (3 COPIES RESIDENET |
| | INSPECTOR PROGRAM) FOR ALL OPENINGS OF |
| | THE EXTERIOR ENVELOPE, SEE CITIES |
| | STANDARD FOR IMPLEMENTATION FOR HURRI- |
| | CANE MISSLE IMPACT PROTECTION.SBCCI OR |
| | DADE COUNTY REPORTS. BUCK ATTACHMENT! |
| | |
| | ROOF ASSEMBLIES SHALL REQUIRE PRODUCT |
| | TESTING BY AN APPROVED TESTING AGENCY. |
| | |
| | GENERAL NOTES S1.11 : |
| | 1) REMOVE NOTES ABOUT NORTH CAROLINA |
| | AMENDMENTS. |
| | 2) FOUNDATIONS SOILS REPORT REQUIRED |
| | 3) SBC 1804.1.3 MINIMUM FOUNDATION |
| | DEPTH BOTTOM OF FOUNDATION MINIMUM OF |
| | 12" BELOW GRADE. |
| | |
| | TRUSS & GIRDER LAYOUT DOESN"T INDICATE |
| | THE VERTICAL, HORIZONTAL NOR GRAVITY |
| | LOADS IMPOSED, KNEE WALL SHALL REQUIRE |
| | A DETAIL SHOWING CONTINIOUS LOADING. |
| | HURRICANE ANCHOR SCHEDULE DOESN'T INDICA |
| | TE THE LOCATION OF THE ANCHOR TO BE USED |
| | |
| | |
| | TRASH COMPACTOR: |
| | |
| | RAMP SHALL COMPLY WITH FAIR HOUSING |
| | ANSI 4.8 RAMPS ABOVE 30" REQUIRE AN |
| | INTERMEDIATE LANDING. |
| | |
| | THE RAMP THAT A HANDICAPPED PERSON |
| | WOULD USE, WHAT STOPS THE PRSON FROM |
| | GOING OVER THE EDGE? |
| | |
| | GAURDHOUSE |
| | IS THIS STUCTURE HANDICAPPED ACCESSIBLE? |
| | THERE ARE NO RESTROOM FACILITIES? |
| | PRODUCT APPROVALS REQUIRED. |
| | TRUSS LAYOUT WITH ANCHOR SCHEDULE & THE |
| | LOADS TO BE REISTED. |
| | ROOFING REPORTS MISSING. |
| | |
| | REMOTE GARAGE PLAN: |
| | THE PREVIOUS COMMENTS FROM THE BATH |
| | HOUSE ARE IN AFFECT. SOILS REPORT, |
| | DAMP PROOFING, PRODUCT APPROVALS, |
| | DESIGN PRESSURES TO BE INDICATED ON PLAN |
| | MISSING INFORMATION AS TO TRUSS TIE |
| | DOWN. |
| | HOW IS THIS BUILDING DESIGNED? SCLOSED, |
| | PARTIALLY OPEN OR OPEN? USE FACTOR? |
| | SBC AMENDMENT 1606.4.2 EXCEPTION(6). |
| | |
| | WHAT IS THE ACTUAL USAGE OF THIS BUILD- |
| | ING, IS HALF OF THE BUILDING TO BE A |
| | CAR WASH? |
| | |
| | THE INTERIOR FINISH NOT GIVEN, WALLS |
| | & CEILING? |
| | |
| | THE ENCLOSED SECTION OF THIS STRUCTURE |
| | DOES NOT MEET THE EGRESS REQUIREMENTS |
| | OF 1012.1.1. |
| | |
| | PLANS ARE NOT INCLUDED INDICATING FRONT |
| | ENTRY GATES, WIDTH OF OPENINGS.PHASE 1 |
| | TO PHASE II, WILL THERE BE A CONTINIOUS |
| | ROAD BETWEEN THE 2 PHASES? |
| | |
| | BEFORE ISSUANCE OF PERMIT,CONTRACTOR |
| | SHALL HAVE PLANS ASSESSED FOR COUNTY |
| | IMPACT FEES, COUNTY BUILDING DEPARTMENT |
| | |
| | STATE RADON FEES TO BE PAID TO CITY |
| | AT TIME OF ISSUANCE @ $.01 SQ.FT. |
| | |
| | THIS SITE SHALL REQUIRE A RESIDENT IN- |
| | SPECTOR, A MEETING WITH ASSISTANT BUILD- |
| | ING OFFICIAL DON NEELY SHALL BE REQUIRED |
| | TO REGISTER THE COMPANY & INSPECTOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X8412 |