| Plan Review Stops For Permit 01110407 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-09-02 |
Time |
14:33 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2002-09-02 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2002-09-02 00:00:00 | CLUBHOUSE STRUC DETAIL STRUCTURAL | | | MULLION DETAIL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2002-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-09-02 |
Time |
14:21 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-09-02 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2002-09-02 00:00:00 | COLUMN REVISIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-25 |
Time |
11:41 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2002-06-25 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-29 |
Time |
16:35 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2002-04-29 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2002-04-29 00:00:00 | *****BUILDING PROVISO***** | | | | | | 1)-SOILS TEST REPORT INDICATESFURTHER | | | INVESTIGATION BEFORE THE PERMIT CAN BE | | | ISSUED. SHOW HOW DENSIFICATION OF SOIL | | | WILL OCCUR. | | | 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | THE CLUBHOUSE FLOOR PLAN AND ELEVATIONS | | | INDICATE THE USE OF FRENCH DOORS WITH | | | SIDELIGHTS, THE SUMMARY SHEET FOR PGT | | | INDICATES THE USE OF FRENCH DOORS, WE | | | ARE MISSING THE REPORT, (3 COPIES). | | | 3)- RESIDENT INSPECTOR TO REGFISTER WITH | | | ASSISTANT BUILDING OFFICIAL DON NEELY. | | | 4)- PLANS ARE TO BE SUBMITTED TO COUNTY | | | FOR IMPACT FEES. | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-26 |
Time |
16:56 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2002-04-29 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110409 | | | BRIGER TRACT "D" | | | BUILDING TYPE I | | | THIRD REVIEW | | | | | | SBC= 1997 STANDARD BUILDING REVIEW | | | | | | 1)- SBC 1804.1.8THE AREA UNDER FOOTING | | | FOUNDATIONS, CONRETE SLABS ON GRADE | | | SHALL HAVE ALL VEGETATION AND FOREIGN | | | MATERIALS REMOVED PRIOR TO THEIR CON- | | | STRUCTION.THE TEST BORING B-1 INDICATES | | | THAT IN THE UPPER ZONE AN ORGANIC CON- | | | TENT OF 10% WAS FOUND. PRIOR TO BUILDING | | | FURTHER TESTING AND REMOVAL SHALL BE | | | REQUIRED BEFORE BUILDING PAD CAN BE DEVE | | | LOPED. AS PER SOILS REPORT. | | | | | | 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | THREE COPIES OF ALL PRODUCT ACCEPTANCE | | | TESTING REPORTS SHALL BE REQUIRED FOR | | | ALL GLAZED OPENINGS, EXT DOORS,SKYLIGHTS | | | GLASS BLOCK, STORM SHUTTERS AND ROOFING | | | ASSEMBLIES. WHEN PRODUCT TESTING REPORTS | | | ARE NOT FILED WITH THE PLANS AND THE | | | BUILDING IS APPROVED, THE STIPULATION | | | THAT A SEPERATE PERMIT WITH ASSOCIATED | | | FEES SHALL BE REQUIRED, ALSO THE CITIES | | | GUIDELINE FOR LARGE PROJECTS REGARDING | | | PROTECTION FOR ALL GLAZED OPENINGS | | | SHALL BE ADHERED TO, SEE ATTACHED GUIDE- | | | LINES. THE BUILDING OFFICIAL SHALL | | | REVIEW AND APPROVE ALL PROPOSED PRE- | | | STORM PREPERATION PLANS. | | | | | | 3)-SHEET S-D1.1 INDICATES A COLUMN | | | DETAIL MISSING INFO FOR WELDS. | | | | | | 4)- RESIDENT INSPECTOR REQUIRED, SEE | | | ASSIS. BUILD. OFF. DON NEELY FOR INFORMA | | | TION. | | | 5)- COUNTY IMPACT FEES TO BE PAID, CON- | | | TRACTOR TO SUBMIT PLANS TO COUNTY FOR | | | ASSESSMENT. | | | CONTTRACTOR TO PAY RADON FEES AT TIME OF | | | ISSUANCE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-26 |
Time |
15:16 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2002-03-26 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110407 | | | CLUBHOUSE | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- FLORIDA ENERGY CODE 1997 EDITION | | | 400.0 FLORIDA ENERGY CODE REQUIRES | | | ENERGY CODE COMPLIANCE METHOD A WHOLE | | | BUILDING, CODE CALCULATIONS INCLUDING | | | MANUAL J. | | | | | | 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | THREE COPIES OF ALL PRODUCT ACCEPTANCE | | | TESTING REPORTS SHALL BE REQUIRED FOR | | | ALL GLAZED OPENINGS, EXT DOORS,SKYLIGHTS | | | GLASS BLOCK, STORM SHUTTERS AS WELL AS | | | ROOFING ASSEMBLIES. WHEN REPORTS ARE NOT | | | FILED WITH THE PLANS AND THE BUILDING | | | IS APPROVED, THE STIPULATION THAT A | | | SEPERATE PERMIT WITH ASSOCIATED FEES | | | SHALL BE REQUIRED, ALSO THE CITIES | | | GUIDE LINES FOR LARGE PROJECTS REGARDING | | | PROTECTION FOR ALL GLAZED OPENINGS SHALL | | | BE ADHERRED TO, SEE ATTACHED GUIDELINES. | | | THE BUILDING OFFICIAL SHALL REVIEW & | | | APPROVE ALL PROPOSED ALL PROPOSED PRE- | | | STORM PREPERATION PLAN. | | | | | | 3)-THE TRUSS & GIRDER LAYOUT DOES NOT | | | INDICATE THE UPLIFT LOADSTO BE RESISTED. | | | THEREIS A ANCHOR SCHEDULE INDICATING | | | WHAT TYPE OF ANCHOR IS TO BE USED. WITH | | | OUT THIS INFORMATION BEFORE THE ISSUANCE | | | OF A BUILDING PERMIT THE ARCHETECT AND | | | ENGINEER SHALL BE REQUIRED TO REVIEW THE | | | TRUSS PLAN LAYOUT WITH THE TRUSS ENGIN- | | | EERING CERTIFYING BY AFFIDAVIT THAT THIS | | | TRUSS LAYOUT AND ATTACHMENT SHALL ALL | | | THE REQUIREMENTS OF THE CODE. | | | ANCHOR SSCHEDULE INDICATES: | | | H-16 ALLOWABLE @160% 1475 UPL. NOT 1600 | | | HGT 4 ALLOWABLE @160 9250 UPL NOT 9685 | | | | | | CONTRACTOR TO TRANSPORT PLANS TO COUNTY | | | FOR IMPACT FEE ASSESSMENT. | | | | | | BUILDING PLAN REVIEW | | | (561)659-8096X 8412 | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-21 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-04-29 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2002-02-21 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW# 01110407 | | | CLUBHOUSE | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)ADDITIONAL INFORMATION REQUIRED, | | | SOILS REPORT | | | FL ENERGY CALCS INCLUDING MANUAL J | | | PRODUCT APPROVAL FOR ALL OPENINGS OF THE | | | BUILDING ENVELOPE, 3 SETS/ BLDG | | | MEAN ROOF HEIGTH S1.11INDICATES TO | | | MEAN ROOF HEIGTHS, SBC 1606.2.4.2 WHERE | | | MORE THAN ONE LOAD CASE EXISTS, BUILD- | | | INGS SHALL BE DESIGNED FOR ALL LOAD | | | CASES. | | | PRODUCT APPROVALS: 3 COPIES OF PRODUCT T | | | ESTING REPORTS SBC 1606.2.6.2 FOR ALL | | | EXTERIOR OPENINGS & ROOFING MATERIALS. | | | SBCCI OR DADE COUNTY PRODUCT TESTING RE- | | | PORTS ARE REQUIRED.GABLE END WALL DETAIL | | | GIVES INFORMATION ON BRACING OF THE | | | BOTTOM CORD, NO ADDITIONAL INFORMATION | | | IS GIVEN ON THE 14' VERTICAL MEMBERS OF | | | THE TRUSS? | | | TRUSS PLAN S2.62 INDICATES THE UPLIFT | | | LOADS FOR THE CONNECTORS BUT THERE IS NO | | | REFRENCE TO THE ACTUAL LOAD CONDITIONS | | | IMPOSED ON THE TRUSS ITSELF? | | | PLANS ARE TO BE SUBMITTED TO COUNTY FOR | | | REVIEW FOR IMPACT FEES. | | | CITY TO COLLECT FEES FOR RADON FOR STATE | | | COMPLEX SHALL REQUIRE A RESIDENT INSPEC- | | | TOR BEFORE ISSUANCE, SEE DON NEELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-08 |
Time |
14:35 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-12-08 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2001-12-08 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01110409 | | | ADDRESS TO BE DETERMINED | | | VILLAGE WEST LUXUARY APARTMENTS | | | PARCEL "D" PHASE I | | | CLUBHOUSE | | | OWN: EPOCH PROPERTIES | | | TEL: ( 407) 644-9055 | | | FAX: (407)644-9845 | | | | | | | | | PLAN REVIEW WILL BE COMPLETED UNDER THE | | | 1997 STANDARD BUILDING CODE. | | | | | | CLUBHOUSE: | | | ASSEMBLY A-2 | | | TYPE V UNPROTECTED, FULLY SPRINKLERED | | | AREA 12,453 | | | | | | CS1.01 INDICATES THE ABOVE INFORMATION, | | | "FULLY SPRINKLERED" SBC TABLE 500 | | | FOOTNOTE "J" BUILDINGS ARE TO BE FULLY | | | SPRINKLERED IN ACCORDANCE WITH THE | | | STANDARDS LISTED IN 903.2 FOR ALLOWABLE | | | AREA INCREASES. SHEET F2.61 INDICATES | | | THE USE OF NFPA 13-R. THIS IA NOT | | | ACCEPTIBLE SEE SBC903.2 AUTOMATIC | | | FIRE SPRINKLER SYSTEMS PERMITTED BY | | | THIS CODE SHALL COMPLY WITH NFPA 13. | | | | | | ADDITIONAL INFORMATION REQUIRED: | | | SOILS REPORT | | | FL. ENERGY CALS & WORKSHEETS. | | | PRODUCT APPROVAL AS STATED UNDER | | | SITE AMENITIES. | | | | | | FAIR HOUSING: SHEET AO.61 CLOSET 104 | | | DOESN'T MEET 18" ACCESS AT LATCH SIDE OF | | | THE DOOR. | | | MAIL BOXES: A5.63 DETAIL 3 TO COMPLY | | | WITH ANSI 117.1 (308) REACH RANGES | | | AADAAG COEFICIENT OF SLIP RESISTANCE | | | FOR ACCESSIBLE AREAS (FLOORS) 0.6 | | | AND 0.8 FOR RAMPS. | | | | | | MEAN ROOF HEIGTH NOT GIVEN. ALSO THE | | | PRESSURES EXERTED ON ALL OPENINGS DOORS | | | AND WINDOWS, PLEASE INDICATE ON ELEVA- | | | TIONS. | | | | | | PRODUCT APPROVALS: FRONT ENTRY IS INDICA | | | TING A FRENCH DOOR, SIDELITES & TRANSOM. | | | THE PRODUCT TESTED NEEDS TO SHOW THIS | | | CONFIGURATION OR TESTING OF MULLIONS | | | CULMINATING WITH THIS CONFIGURATION. | | | | | | DISCREPANCY SHEET A5.65 DETAIL #2 INDICA | | | TES A FRAME WALL & COLUMNS VS. S2.62 | | | GIRDER GT, ADDITIONAL INFORMATION | | | REQUIRED. | | | | | | DISCREPANCY SHEET A5.62 REAR ELEVATION | | | WORKOUT ROOM 84'-0" IS THE SAME AS THE | | | FLOOR PLAN, VS 81' ON THE ROOF PLAN. | | | | | | A GABLE WALL SECTION DETAIL FOR THE WALL | | | OF THE WORK OUT ROOM SHALL BE REQUESTED. | | | ADDITIONAL INFOR. THIS GABLE TRUSS IS | | | 14' VERTICALLY, WHAT TYPE OF REINFORCE- | | | MENT SHALL BE REQUIRED? OR IS THIS TO | | | BE A RAKE BEAM? | | | SHEET S3.12 DETAIL #3 SIMPSON HGAM (10) | | | SEE FOOTNOTE (2) MANUFAC. SPEC CATALOG | | | TRUSS TO BE A MINIMUM OF 21/2 " THICK. | | | WHAT TYPE OF ANCHOR IS TO BE USED IN | | | THIS APPLICATION? | | | | | | GLAZED FIXED PANELS NEXT TO SWING DOORS | | | A HAZARDOUS LOCATION SBC 2405.2.1(4) | | | | | | SHEET S2.61 FOOTER (TS1) INDICATES A | | | BEARING WALL BETWEEN THE EXERCISE ROOM | | | AND HALL 120A/ RESTROOM 121. S2.62 NOTE | | | 12 ALSO INDICATES A BEARING WALL, THERE | | | IS NO INFO. ON A HEADER OR GIRDER TO | | | PICK UP LOAD WHERE WALL ENDS. TI/ T2 | | | ARE A SPLIT TRUSS WILL THEY BEAR ON THIS | | | WALL? | | | | | | TRUSS PLAN MISSING THE LOADS TO BE | | | RESISTED, VERTICAL, HORIZONTAL & GRAVITY | | | COORALTE WITH ANCHOR SCHEDULE. | | | | | | PLANS ARE TO BE SUBMITTED TO THE | | | COUNTY BUILDING DEPART FOR ASSESMENT OF | | | COUNTY IMPACT FEES BEFORE ISSUANCE | | | OF A BUILDING PERMIT. | | | | | | STATE RADON FEES COLLECTED BY THE CITY. | | | | | | COMPLEX WILL REQUIRE A RESIDENT INSPECT- | | | OR CONTACT DON NEELY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-27 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-04 |
Time |
09:40 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-04 |
Time |
07:55 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2002-08-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-09 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-08-09 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2002-08-09 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATIONAND RESUBMIT FOR REVIEW: | | | | | | 1} PLEASE NOTE THAT ON THE PREVIOUS SIX | | | REVIEWS THE SERVICE WAS 3 PHASE AND ON | | | THIS REVIEW IT IS SINGLE PHASE,PLEASE | | | VERIFY THAT ALL THE EQUIPMENT IS BEING | | | CHANGED TO SINGLE PHASE.THE MECHANICAL | | | DRAWINGS NEED TO BE RESUBMITTED TO | | | REFLECT THESE CHANGES AND ALSO TO SHOW | | | THE LOCATIONS AND CALCULATIONS OF THE | | | THREE UNITS BEING ADDED. | | | | | | 2} THE AIC RATINGS REMAINED THE SAME | | | FROM THE 3 PHASE CALCULATION TO THE | | | SINGLE PHASE CALCULATIONS,PLEASE | | | RECALCULATE. | | | | | | 3} PANELS "A" & "B" ARE LISTED AT 208 | | | VOLTS AND THE SERVICE IS SHOWN AS | | | 240V,PLEASE CLARIFY. | | | | | | 4} PANEL "B" IS LISTED AS A 100 AMP | | | PANEL BUT IS CALCULATED WITH A 142 AMP | | | LOAD,PLEASE CLARIFY. | | | | | | 5} PANEL "B" FEEDERS ARE SHOWN AS BEING | | | PROTECTED BY 150 AMP OCP,SEE NOTE #4. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2002-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-18 |
Time |
06:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-18 |
Time |
06:29 |
Sent To |
|
|
| Notes |
| 2002-07-18 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT EQUIPMNET | | | GROUNDING CONDUCTORS ARE BEING SHOWN | | | BETWEEN GUTTER AND FIRST MEANS OF DSIC? | | | PLEASE NOTE THIS A PARALLELING THE | | | NEUTRAL, WHICH IS NOT PERMITTED. | | | PLEASE NOTE THAT EQUIPMENT GRNDS ONLY | | | GET INSTALLED AFTER THE FIRST MEANS | | | OF DISC, DUE TO THE FACT THAT THE | | | NEUTRAL IS BONDED AT THAT LOCATION. | | | | | | 2)NOTE: PLEASE NOTE, A NEW PANEL IS | | | BEING ADDED AND IS NOT SHOWN BEING ADDED | | | TO CLUBHOUSE LOAD CALCULATION.?? | | | PLEASE NOTE THAT PER LOAD CALCUALTIONS, | | | THIS NEW LOAD WOULD PUT SERVICE WAY OVER | | | SERVICE ENTRANCE CONDUCTOR SIZES>>> | | | PLEASE NOTE THAT LOAD SHOWN FOR PANEL | | | "D" DOES NOT CORRELATE WITH LOAD ON | | | PANEL SCHEDULE LOAD. | | | | | | 3)NOTE: PLEASE CLARFIY CONDUCTORS, | | | PANELS ARE SHOWN AS 3-PHASE AND # OF | | | CONDUCTORS DO NOT SEEM TO CORRELATE. | | | PLEASE GIVE A MORE DETAIL BREAKDOWN OF | | | "CIRCLE" DETAILS ON RISER DIAGRAM. | | | 3PH4W?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-20 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-20 |
Time |
06:22 |
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | PLANS STAMPED | | | DEWEY PALMER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-05-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-10 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-10 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2002-05-10 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT UNDER FS/FAC | | | 471.025/481.22 PLANS MUST HAVE AN | | | ORIGINAL "WET" SIGNATURE. | | | E2.61, E4.61 | | | | | | PLEASE SUBMIT SUBMIT THE ABOVE FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-18 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-18 |
Time |
06:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-06 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | *****************UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SIGNED, DATED AND SEALED BY THE | | | ENGINEER OF RECORD. PER FS/FAC 471.025 | | | | | | 2)NOTE: PLEASE NOTE NO EQUIPMENT GROUND | | | TO BE INSTALLED UNTIL AFTER FIRST MEANS | | | OF DISCONNECT. (PARALLELING NEUTRAL) | | | ALSO SHOWING AN EQUIPMENT GROUNDING | | | CONDUCTOR COMING FROM FPL? | | | | | | 3)NOTE: PLEASE CLARIFY CIRCLES ON PLANS | | | FOR RISER,,,250VOLT/3 WIRE+NEU/ | | | DISC SIZE AND SIZE OF FUSES? PLEASE | | | CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-28 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-27 |
Time |
21:31 |
Sent To |
|
|
| Notes |
| 2001-11-28 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT LOAD CALCULAT- | | | -IONS DO NOT CORRELATE WITH LOAD | | | CALCULATIONS SHOWN FOR CLUBHOUSE IN THE | | | CENTER OF E4.61. PLEASE VERIFY AND | | | ADJUST. | | | | | | 2)NOTE: PLEASE CLARIFY CONDUCTORS SHOWN | | | FOR PANEL "D" 2-SETS OF 350MCM FOR 400A | | | AND 2- SETS OF 3/0`S FOR PANEL "A" 400A | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL.' | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | PLEASE NOTE THAT PER LOCAL AMENDMENTS | | | SE,NMC ETC SHALL NOT BE USED. PER | | | NOTES 22. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-05-29 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | N/A | | | 1. SEE PERMIT # 02050423 FOR CIVIL/SITE | | | WORKS REVIEW AND PERMITTING FOR PARCEL-D | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-13 |
Time |
10:07 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-11-13 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | FAILED : | | | 1. SEE PERMIT # 01110408 | | | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-06-21 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-06-21 |
Time |
10:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2002-05-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-23 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-23 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2002-05-23 00:00:00 | 1) CORRIDOR 116 AND CORRIDOR 120 NEED | | | EMERGENCY LIGHTING. | | | | | | 2) SIX INCH UNDEGROUND FIRE LINE RUN | | | UNDERNEATH THE BUILDING. THIS IS NOT | | | ACCEPTABLE. | | | | | | ON 5.23.02, WRITER SPOKE TO MR. WEEKS | | | BY TELEPHONE REGARDING THESE MATTERS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-27 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-27 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | A) CIVIL DRAWINGS INDICATING FIRE MAIN | | | LOCATIONS, SIZES, AND FIRE HYDRANT | | | LOCATIONS NOT YET BEEN APPROVED. | | | B) SIX INCH UNDERGROUND PIPE TO | | | MECHANICAL ROOMSTILL SHOWN RUN | | | UNDERNEATH PORTIONS OF THE BUILDING. | | | C) FIRE DEPARTMENT CONNECTION NOT SHOWN | | | ON FIRE SPRINKLER PLANS. | | | D) BUILDING ADDRESS REQUIRED ON BUILDING | | | E) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-12 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2002-02-12 00:00:00 | 1) FIRE SPRINKLER PIPING RUN UNDERNEATH | | | BUILDING TO MECHANICAL ROOM IS NOT | | | PERMITTED. THE PLAN REVIEW RESPONSE | | | IS NOT ACCEPTABLE TO THIS OFFICE. NFPA | | | 24 REQUIRES THAT PRIVATE FIRE SERVICE | | | MAINS NOT BE RUN UNDERNEATH BUILDINGS | | | EXCEPT WHEN ABSOLUTELY NECESSARY. | | | 2) FIRE SPRINKLER RISER SIZE COULD NOT | | | BE LOCATED ON THE PLANS. PLEASE INDICATE | | | ON PLANS RISER SIZE AND UNDERGROUND MAIN | | | SIZE. | | | 3) PLEASE REMOVE 13R REFERENCE FROM PAGE | | | F2.61 SINCE IT IS NOT APPLICABLE TO | | | THE CLUBHOUSE. | | | 4) HYDRAULIC CALCULATIONS SUBMITTED | | | APPEAR TO BE BUILDING TYPE 1, NOT THE | | | CLUBHOUSE. | | | 5) THIS OFFICE WILL REQUIRE FIRE | | | SPRINKLER PROTECTION FOR THE PORCH AREA. | | | 6) EXIT SIGN LOCATIONS DOES NOT | | | CORRELATE WITH OTHER ONES. | | | 7) PLEASE INCLUDE ALL CHANGES ON THE | | | PLAN REVIEW RESPONSES INTO THE DESIGN | | | DOCUMENTS. | | | 8) THIS OFFICE NEEDS CIVIL DRAWINGS | | | SUBMITTED TO DETERMINE FIRE MAIN AND | | | FIRE HYDRANT LOCATIONS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-21 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-21 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | 1) PLEASE BE ADVISED THAT WHEN THIS | | | PROJECT IS PERMITTED WOULD STIPULATE | | | THE APPLICABLE FIRE CODE THAT WOULD BE | | | USED TO REVIEW THE CLUBHOUSE. EFFECTIVE | | | JANUARY 1, 2002, THE NEW FLORIDA FIRE | | | PREVENTION CODE WOULD BE APPLICABLE TO | | | THE CLUBHOUSE WHICH WOULD INVOKE THE | | | 2000 EDITION OF THE LIFE SAFETY CODE. | | | PRIOR TO THE ABOVE SUBJECT DATE, THE | | | 1985 EDITION OF THE LIFE SAFETY CODE | | | WOULD BE APPLICABLE. | | | 2) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS DUE TO OCCUPANCY PROJECTIONS. | | | 3) PLEASE INDICATE HOW THE MAIN EXIT | | | IS CAPABLE OF PROVIDING EXITING CAPACITY | | | FOR AT LEAST 50 PERCENT OF THE PROJECTED | | | OCCUPANCY LOAD. | | | 4) BUILDING ADDRESS REQUIRED ON | | | CLUBHOUSE. | | | 5) A KNOX-BOX WILL BE REQUIRED FOR FIRE | | | RESCUE ACCESS. | | | 6) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 7) OCCUPANT LOAD FOR CLUBHOUSE WILL | | | BE DETERMINED BY FIRE RESCUE. | | | 8) FIRE DEPARTMENT CONNECTION IS TO BE | | | WITHIN 150 FEET OF A FIRE HYDRANT. | | | 9) NO FIRE HYDRANTS SHOWN ON SITE PLAN. | | | 10) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH PLANS. | | | 11) WALL POST INDICATOR VALVE SHOWN | | | BELOW FIRE DEPARTMENT CONNECTION COULD | | | INTERFERE WITH CONNECTING HOSES TO IT. | | | 12) UNDERGROUND PIPE RUN UNDERNEATH | | | THE BUILDING TO MECHANICAL ROOM IS | | | NOT PERMITTED. | | | 13) PLEASE EXPLAIN USE OF CHILDREN'S | | | ROOM. | | | 14) THE PORCH IF OVER FOUR FEET WIDE AND | | | COMBUSTIBLE IS REQUIRED TO BE FIRE | | | SPRINKLER PROTECTED. | | | 15) IT IS RECOMMENDED THAT DUCT SMOKE | | | DETECTORS BE INSTALLED IN THE RETURNS | | | IN UNITS 2000 CFM. | | | 16) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE ALARM SYSTEM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-04 |
Time |
09:40 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-20 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2002-03-20 00:00:00 | | | | PROVISO: | | | | | | EXHAUST FROM THE MEDIA ROOM SHALL | | | TERMINATE IN SUCH A MANNER AS NOT TO | | | CREATE A NUISANCE & FROM WHICH CANNOT | | | AGAIN BE READILY DRAWN IN BY A | | | VENTILATING SYSTEM. EXHAUST SHALL | | | TERMINATE A MINIMUM OF 10 FT ABOVE THE | | | ADJOINING GRADE.(1997 SMC 501.3 & | | | 506.1, RESPECTIVELY) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. | | | | | | | | | DISREGARD THIS REVSION.THIS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-06 |
Time |
08:27 |
Rev Time |
2.45 |
| Received By |
pkrauss |
Date |
2002-02-06 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | | | | CLUBHOUSE PERMIT 01110407 | | | | | | PLAN SHEET M2.61 - 1) HVAC SHEET NOTES, | | | #14 "RUN VERTICAL DICT THRU VERTICAL | | | SHAFT.SEE ARCHITECTURAL DWG.PLEASE | | | SPECIFY WHICH ACHITECTURAL DWG.NO | | | DETAIL FOUND.2)#7 TRANSFER DUCT, | | | PLEASE CLARIFY TRANSFERING AIR FROM THE | | | CORRIDOR INTO THE BATHROOM? | | | | | | PLANS SHEET M4.61 - OUTSIDE AIR | | | REQUIREMENT, AS PER ASHRAE 62-89 TABLE | | | 2 FOR GAME ROOM - 25 CFM PER PERSON. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
16:26 |
Rev Time |
8.00 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | MECHANICAL ROOM 110 IS INDICATED AS | | | HAVING FIRE RESISTANCE RATING OF HOUR. | | | PLEASE IDENTIFY FIRE DAMPERS ON DUCTS | | | PENETRATING THESE WALLS. | | | | | | PLAN SHEET M2.61, INDICATE WHERE AHU | | | CH-1 IS LOCATED (ABOVE CEILING OR IN A | | | ROOM).HVAC NOTES ITEM #3, CONDENSATE | | | DRAIN LINE ROUTE TO FLOOR DRAIN.AS | | | PER THE COUNTY WIDE AMENDMENTS 1994 | | | SPC, UNITS LARGER THAN 3 TONS THE | | | CONDENSATE SHALL TERMINATE. | | | | | | 1. INTO AN APPROVED DRYWELL. | | | 2. CONNECTION AT GROUND FLOOR LEVEL OF | | | THE STORM DRAINAGE SYSTEM. | | | | | | PLEASE NOTE, FAN SHUTDOWN REQUIRED FOR | | | UNITS WITH CAPACITY OF 2,000 CFM OR | | | GREATER.WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | | | | | | | | | | REVIEW OF THE APARTMENTS - | | | | | | 1.EXHAUST FOR THE DRYER VENTS. | | | NOTE, 25' MAXIMUM LENGTH INCLUDING | | | A 2 1/2' DEDUCTION FOR EACH 45 AND | | | A 5' DEDUCTION FOR EACH 90 DEGREE | | | BEND. | | | 2.PLEASE INDICATE HOW COMBUSIBLE LINT | | | IN TO BE REMOVED/CLEANED FROM DUCT. | | | CLEANOUTS ARE NOT INDICATED ON PLAN. | | | 3.PROVIDE A DETAIL OF CONDENSATE | | | TERMINATION LOCATION. | | | 4.PLANS INDICATE DRYER EXHAUST TO BE | | | NON-SCREENED WITH A BACK DRAFT | | | DAMPER.NOTHING IS SPECIFIED FOR | | | THE TOILET EXHAUST.TOILET EXHAUST | | | TERMINATION SHALL BE SCREENED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-25 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-25 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-14 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-14 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-18 |
Time |
12:52 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-03-18 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2002-03-18 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEWS, SHT A7.61 DE- | | | TAIL #10 BAR SINK. DETAIL DOES NOT COM- | | | PLY WITH FACBC SEC 4.24. COUNTER HEIGTH | | | SHALL BE 2'10" NOT 3'0" AS SHOWN. SEC | | | 4.24.2. KNEE CLEARANCE NOT SHOWN, SEC | | | 4.24.3. CLEAR FLOOR SPACE NOT SHOWN, SEC | | | 4.24.5. | | | 2) FROM PREVIOUS REVIEW, SHT A7.61 DE- | | | TAILS #8 & #9, PLEASE SHOW CLEAR FLOOR | | | SPACE. LAV TO BE CENTERED ON CLEAR FLOOR | | | SPACE MINIMUM OF 15" OFF WALL TO CENTER. | | | 3) FROM PREVIOUS REVIEW, SHT A7.61 DE- | | | TAILS #8 & #9 DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE OF ANY FIXTURE, SEC | | | 4.17.5 & 4.22.2 OR THE TURNING RADIUS | | | SEC 4.22.3. | | | 4) FROM PREVIOUS REVIEW, PLEASE SHOW | | | CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES. | | | SHT A7.61 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-09 |
Time |
12:43 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-02-09 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2002-02-09 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW, SH A2.61 PLEASE | | | PROVIDE DETAIL FOR SERVICE BAR SINK SHOW | | | COMPLIANCE WITH FACBC SEC 4.24 | | | 2) SHT A7.61 EACH PUBLIC OR COMMON USE | | | FACILITY SHALL COMPLY WITH FACBC SEC | | | 4.22, TOILET ROOMS 114 & 115. SHOW CLEAR | | | FLOOR SPACE, LAV TO BE CENTERED IN FLOOR | | | SPACE MIN. 15" OFF WALL TO CENTER. | | | 3) SHT A7.61 DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE 4.17.5/4.22.2 OF ANY | | | FIXTURE OR THE TURNING RADIUS 4.22.3. | | | 4) SHT A7.61 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR ALL HDCP FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-30 |
Time |
13:20 |
Rev Time |
1.75 |
| Received By |
kstevens |
Date |
2001-11-30 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2001-11-30 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PLEASE PROVIDE CALCULATIONS FOR MIN- | | | IMUM FACILITIES USING SPC TABLE 407. | | | 2) SHT A2.61 PLEASE PROVIDE ELEVATION | | | FOR SERVICE BAR SINK. PROVIDE DETAILS | | | FOR COMPLIANCE WITH FACBC SEC 4.24. | | | 3) SHT P2.61 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS TO BE LOCATED CLOSE TO | | | FIXTURES IN AN EFFECTIVE RANGE, NOT AT | | | TOP OF DROP AS SHOWN. | | | 4) WATER RISER DIAGRAM DETAILS #4 & #6 | | | WATER TO EACH RESTROOM TO BE SEPARATE & | | | SHUT OFF VALVES ARE REQUIRED FOR EACH | | | ROOM. SPC SEC 610.4.1 | | | 5) SHT P4.61 WATER HEATER DETAIL, DIELE- | | | CTRIC UNIONS AND REMOTE WATER HEATERS | | | NOT APPROVED. CITY CODE SEC 31-29 | | | 6) SHT P4.61 WATER HEATER #3, PLEASE | | | PROVIDE DETAILS SHOWING HOW HEATER IS | | | READILY ACCESSIBLE PER SPC SEC 501.7 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|