Plan Review Details - Permit 01110401
Plan Review Stops For Permit 01110401
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-11 Cont ID  
Sent By hpiskura Date 2002-01-11 Time 09:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-12 Cont ID  
Sent By hpiskura Date 2001-12-12 Time 08:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-12-12 00:00:00THE PRIMARY USE OF THIS BUILDING AS
 DESCRIBED IN SBC 310 IS MERCANTILE.AS
 SUCH IT APPEARS TO EXCEED THE AREA
 ALLOWED BY SBC TABLE 500 FOR A TWO
 STORY TYPE IV, FS BUILDING.(27 KSF)
  
 FURTHER, THE SERVICE PORTIONS, GROUP
 "S"FOR THE SAME CONSTRUCTION TYPE IS 48
 KSFWITH THE AREA INCREASES ALLOWED BY
 SBC 503 APPLIED.
  
 PLEASE PROIDE A RECENT PROPERTY SURVEY,
 ONE YEAR OR LESS OLD.
  
 INDICATE ON THE SITE PLAN THE LOCATION
 OF ANY FIRE WALLS.(SEE SBC 202 "FIRE
 WALL")
  
 IS THE SPRINKLER A SINGLE RISER SYSTEM?
 PLEASE PROVIDE AN ENGINEER'S ANALYSIS
 OF THE SYSTEM FOR THE ENTIRE BUILDING
 SO THAT COMPLIANCE WITH SECTION 4-2.1
 OF NFPA 13-96 MAY BE DETERMINED.
  
 SHEET A4 SECTION 2/A4 CALLS OUT THE USE
 OF PLYWOOD WHICH IS NOT PERMITTED IN
 TYPE IV CONSTRUCTION, SEE SBC 606 AND
 SBC APPENDIX F 102.2.7.
  
 SHEET S1, SECTION C, WHAT IS THE SPACING
 OF THE L3X3X1/4 ?
  
 SHEET S2 CITES THE SFBC, PLEASE REVISE
 TO INCLUDE, AND ASCERTAIN COMPLIANCE
 WITH, THE 1997 SBC.
  
 PLEASE PROVIDE THE TESTING AND OR
 NNOTICE OF ACCEPTANCE REPORTS FOR THE
 DOORS, WINDOWS AND ROOF COVERINGS.
 ALSO, INDICATE HOW THE GLAZED PORTIONS
 OF THE ADDITION WILL RESIST HURRICANE
 MISSILE IMPACT.DESIGNATE THE LOADS ON
 THE PLANS FOR THE ABOVE MENTIONED ITEMS.
  
 SHEET A2, SHOW THE CALCULATIONS FOR THE
 SIZING OF THE ROOF EMERGENCY OVERFLOW
 SCUPPER IN ACCORDANCE WITH SECTION 1109
 OF THE 1994 STANDARD PLUMBING CODE.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND ACOPY OF
 THE RECEIPT ATTACHE TO THE PERMIT
 APPLICATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 17:19 Rev Time 0.00
Received By dpalmer Date 2002-03-19 Time 16:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-06 Cont ID  
Sent By dpalmer Date 2001-12-06 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2001-12-06 Time 06:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-15 Cont ID  
Sent By hpiskura Date 2002-01-15 Time 10:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-01-15 Cont ID  
Sent By mcarsill Date 2002-01-15 Time 10:29 Rev Time 0.00
Received By mcarsill Date 2002-01-15 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-09 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2002-01-09 Time 12:55 Sent To  
Notes
2002-01-09 00:00:001) THE LETTER PREPARED BY MR. TOM
 DICKMAN, PROTECTION DESIGN COMPANY, INC.
 TO HAROLD PISKURA WITH REGARDS TO
 BUILDING AREA APPEARS TO CONFLICT WITH
 THE DRAWINGS. THE DRAWINGS INDICATE AN
 EXISTING TWO-STORY VEHICLE SALES AND
 SERVICE BUILDING COMPRISING 46,690
 SQUARE FEET. THERE APPEARS TO BE A
 DISCREPANCY BETWEEN THE TWO.
 2) FURNITURE LAYOUT REVIEWED. IT APPEARS
 THAT AN ITEM IS LOCATED IN FRONT OF
 EXIT DOORS. PLEASE BE ADVISED THAT
 " MEANS OF EGRESS SHALL BE FREE OF
 OBSTRUCTIONS WHICH WOULD PREVENT ITS
 USE". RE: NFPA 101, THE LIFE SAFETY
 CODE, 1985 EDITION, SECTION 5-1.7.3.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By mcarsill Date 2001-12-11 Time 08:41 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 08:41 Sent To  
Notes
2001-12-11 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997 EDITION.
 2) PLEASE INDICATE HOW FIRE RESCUE
 ACCESS IS ACCOMPLISHED THRU THE
 RELOCATED FENCE AND GATES.
 3) THE BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. TYPE VI CONSTRUCTION IS
 NOT PERMITTED IN THE CITY FIRE LIMITS.
 PLEASE SEE APPENDIX F OF THE STANDARD
 BUILDING CODE AND CHAPTER 11 OF THE
 CITY CODE.
 4) WRONG INFORMATION REGARDING BUILDING
 CODE INFORMATION. BROWARD COUNTY
 EDITION REFERENCED ON PLANS IS
 INCORRECT.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 6) PLEASE INDICATE WHAT SAFETY MEASURES
 WILL BE TAKEN FOR THE DISPLAY OF
 VEHICLES.
 7) PLEASE IDENTIFY EXIT AISLES IN THE
 MINI SHOWROOM SO PERSONS CAN REACH THE
 EXIT DOORS ON THE NEW ADDITION.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF FIRE SPRINKLER
 SYSTEM.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW FIRE ALARM EQUIPMENT SHOWN
 ON THE PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 11:08 Rev Time 0.35
Received By pkrauss Date 2002-01-11 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By pkrauss Date 2001-12-11 Time 09:06 Rev Time 0.50
Received By pkrauss Date 2001-12-11 Time 08:58 Sent To  
Notes
2001-12-11 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 INDICATE IS THERE ANY PRECAUTIONS BEING
 TAKEN FOR "CARBON MONOXIDE" IN THE DISPL
 AY AREA.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-03 Cont ID  
Sent By kstevens Date 2001-12-03 Time 18:58 Rev Time 0.75
Received By kstevens Date 2001-12-03 Time 18:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2001-11-28 Cont ID  
Sent By sgraham Date 2001-11-28 Time 08:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-11-16 Cont ID  
Sent By sgraham Date 2001-11-16 Time 11:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-11-16 00:00:00NEED DSI AMENDMENT