Plan Review Details - Permit 01110376
Plan Review Stops For Permit 01110376
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-29 Cont ID  
Sent By jwitmer Date 2001-11-29 Time 07:32 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-29 00:00:00REVISION SUBMITTAL DATE 11/28/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-23 Cont ID  
Sent By jwitmer Date 2001-11-23 Time 09:53 Rev Time 0.60
Received By jwitmer Date 2001-11-23 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-10 Cont ID  
Sent By dpalmer Date 2001-12-10 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2001-12-10 Time 19:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By dpalmer Date 2001-11-16 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2001-11-16 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-20 Cont ID  
Sent By mcarsill Date 2001-11-20 Time 08:50 Rev Time 0.00
Received By mcarsill Date 2001-11-20 Time 08:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-12-11 Cont ID  
Sent By pkrauss Date 2001-12-11 Time 14:12 Rev Time 0.35
Received By pkrauss Date 2001-12-11 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 13:10 Rev Time 1.00
Received By pkrauss Date 2001-11-27 Time 11:16 Sent To  
Notes
2001-11-27 00:00:00*******************PROVISO**************
  
  
 1.PLAN SHEET M-1, EXISTING CORRIDOR
 INDICATES TO DAMPERS IN A FIRE
 RATED WALL. DAMPERS ARE NOT SHALL BE
 IDENTIFIED AS FIRE DAMPERS.
  
 2.PLANS DO NOT PROVIDE INSTALLATION
 DETAILS FOR FIRE DAMPERS.FIRE
 DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABEL OF AN APPROVED
 TESTING AGENCY AS PER 1997 SMC
 610.1.1.
  
 3.PLANS TO DO INDICATE MATERIAL OF
 PIPING FOR CONDENSER WATER.PLEASE
 NOTE SHOULD COPPER PIPE BE INSTALLED
 IT SHALL BE BRAZED AS PER 1997 SMC
 TABLE 1205.
  
 4.PLAN SHEET M-2 AND M-3 CONTRADICT
 TERMINATION OF EMERGENCY DRAIN FOR
 AUXILIRY DRAIN PAN.EMERGENCY DRAIN
 LINE SHALL NOT TERMINATE TO RISER AS
 INDICATED ON PLAN SHEET M-3.DRAIN
 SHALL COMPLY WITH 1997 SMC 304.8.6.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-04 Cont ID  
Sent By kstevens Date 2002-01-04 Time 18:32 Rev Time 0.50
Received By kstevens Date 2002-01-04 Time 18:31 Sent To  
Notes
2002-01-04 00:00:00REVISION APPROVED

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By pschmitz Date 2001-11-19 Time 07:32 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-19 00:00:00PLUMBING PLAN REVIEW,PROVISO
 SHTS P-1 & P-3
 SEPERATE PERMIT FOR MEDICAL GAS.