Plan Review Details - Permit 01110351
| Plan Review Stops For Permit 01110351 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-11-19 |
Time |
11:38 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | ************FAILED************ | | | | | | NO DETAIL FOR GENERAL CABINET REPAIR; | | | SHOW AREAS ON DRAWINGS OR SUBMIT | | | INFORMATION | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 659-8096 EXT 8394 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2001-12-27 |
Time |
09:02 |
Rev Time |
2.00 |
| Received By |
btrobaug |
Date |
2001-12-27 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2001-12-27 00:00:00 | 1)PLEASE PROVIDE AN A.I.C. RATING FOR | | | THE SERVICE CONNECTION AT MDP. AS PER | | | 110-9&110-10. | | | 2)PERMIT APPLICATION DOES NOT INCLUDE | | | WIRING NEW A/C'S OR INTERIOR WIRING OF | | | UPPER UNIT IN THE PROJECT DESCRIPTION. | | | 3)THE ENGINEER'S TITLE BLOCK MUST BE ON | | | THE REVISED RISER DIAGRAM ALONG WITH HIS | | | STAMP AS PER FS/FAC 61G 15-23.002 | | | 4)PANEL SCHEDULES ON ARE ILLEGIBLE. | | | 5)NOTE "1" ON THE RISER DIAGRAM | | | INDICATES #1 CU CONDUCTORS TERMINATING | | | ON A 50AMP CIRCUIT BREAKER !!! | | | 6)METER ENCLOSURE DOES NOT SHOW AMPERAGE | | | RATING, PLEASE INCLUDE. | | | 7)THE PLANS DON'T SHOW A LOAD | | | CALCULATION FOR THE HOUSE PANEL, PLEASE | | | ADD. | | | 8)THE NEW PANEL SHOWN IN THE UPPER | | | LIVING SPACE MUST COMPLY WITH 230-79D. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-16 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-16 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | COMPLETE FOR COMPLETE PLAN REVIEW. | | | | | | 2)NOTE: PLEASE NOTE THAT MIN SERVICE | | | SIZE FOR UNITS. 230-79 C&D. | | | | | | 3)NOTE: PLEASE NOTE ONE SET OF CONDCUTOR | | | -S COMING FROM MDP TO GUTTER??? | | | PLEASE CORRECT. | | | | | | 4)NOTE: PLEASE SUBMIT ALL CONDCUTOR | | | SIZES FOR SERVICE ENTRANCE. 215-5 | | | | | | | | | | | | | | | 6)NOTE: PLEASE CLARIFY IF PANELS SHOWN | | | AS "EXT" IS EXSITING OR EXTERIOR? | | | | | | 7)NOTE: PLEASE OUTLETS SHOWN IN THE | | | MIDDLE OF FLOOR IN DINING ROOM.? | | | | | | 8)NOTE: PLEASE NOTE SMOKE DETECTORS | | | INSIDE AND OUTSIDE BEDROOM. NFPA-72 | | | 2-2.1.1.1 | | | | | | 9)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | | -MENT GROUNDINGPER 250-122 BETWEEN | | | MAIN/MDP AND PANELS? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-11-19 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|