Plan Review Details - Permit 01110351
Plan Review Stops For Permit 01110351
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By lsmith Date 2001-11-19 Time 11:38 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-11-19 00:00:00************FAILED************
  
 NO DETAIL FOR GENERAL CABINET REPAIR;
 SHOW AREAS ON DRAWINGS OR SUBMIT
 INFORMATION
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT 8394

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-27 Cont ID  
Sent By btrobaug Date 2001-12-27 Time 09:02 Rev Time 2.00
Received By btrobaug Date 2001-12-27 Time 09:01 Sent To  
Notes
2001-12-27 00:00:001)PLEASE PROVIDE AN A.I.C. RATING FOR
 THE SERVICE CONNECTION AT MDP. AS PER
 110-9&110-10.
 2)PERMIT APPLICATION DOES NOT INCLUDE
 WIRING NEW A/C'S OR INTERIOR WIRING OF
 UPPER UNIT IN THE PROJECT DESCRIPTION.
 3)THE ENGINEER'S TITLE BLOCK MUST BE ON
 THE REVISED RISER DIAGRAM ALONG WITH HIS
 STAMP AS PER FS/FAC 61G 15-23.002
 4)PANEL SCHEDULES ON ARE ILLEGIBLE.
 5)NOTE "1" ON THE RISER DIAGRAM
 INDICATES #1 CU CONDUCTORS TERMINATING
 ON A 50AMP CIRCUIT BREAKER !!!
 6)METER ENCLOSURE DOES NOT SHOW AMPERAGE
 RATING, PLEASE INCLUDE.
 7)THE PLANS DON'T SHOW A LOAD
 CALCULATION FOR THE HOUSE PANEL, PLEASE
 ADD.
 8)THE NEW PANEL SHOWN IN THE UPPER
 LIVING SPACE MUST COMPLY WITH 230-79D.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-16 Cont ID  
Sent By dpalmer Date 2001-11-16 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2001-11-16 Time 10:00 Sent To  
Notes
2001-11-16 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 COMPLETE FOR COMPLETE PLAN REVIEW.
  
 2)NOTE: PLEASE NOTE THAT MIN SERVICE
 SIZE FOR UNITS. 230-79 C&D.
  
 3)NOTE: PLEASE NOTE ONE SET OF CONDCUTOR
 -S COMING FROM MDP TO GUTTER???
 PLEASE CORRECT.
  
 4)NOTE: PLEASE SUBMIT ALL CONDCUTOR
 SIZES FOR SERVICE ENTRANCE. 215-5
  
  
  
  
 6)NOTE: PLEASE CLARIFY IF PANELS SHOWN
 AS "EXT" IS EXSITING OR EXTERIOR?
  
 7)NOTE: PLEASE OUTLETS SHOWN IN THE
 MIDDLE OF FLOOR IN DINING ROOM.?
  
 8)NOTE: PLEASE NOTE SMOKE DETECTORS
 INSIDE AND OUTSIDE BEDROOM. NFPA-72
 2-2.1.1.1
  
 9)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDINGPER 250-122 BETWEEN
 MAIN/MDP AND PANELS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop Z ZONING
Rev No 1 Status N Date 2001-11-19 Cont ID  
Sent By lsmith Date 2001-11-19 Time 11:38 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***