Plan Review Details - Permit 01110339
Plan Review Stops For Permit 01110339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-28 Cont ID  
Sent By jwitmer Date   Time 10:30 Rev Time 2.50
Received By jwitmer Date 2001-12-28 Time 10:30 Sent To  
Notes
2001-12-28 00:00:00 
 BUILDING PROVISO
 PERMIT# 01110339
 1617 N FLAGLER DR
 CONT FORTUNE CONSTRUCTION
 TEL: (305) 970-8453
 CONTACT PERSON: ARTURO PENA
  
 1)- AS PER CONVERSATION WITH ARTURO
 COMMENT #8 HAS NOT BEEN SATISFIED,SBC
 2304.3.4 18" VERTICAL CLEARENCE BETWEEN
 THE TRAILER AND SOILS, FLOOR JOIST ARE
 INDICATED AS SPF, SPRUCE/PINE/FIR.
 CONTRACTOR AGREES TO RETAIN SOILS WITH
 A PRESSURE TREATED RETAINING WALL,
 A AIR GAP REQUIRED FOR TERMITE PROTEC-
 TION. A DETAIL SHEET TO FOLLOW BEFORE
 FIRST INSPECTION.J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By jwitmer Date 2001-11-26 Time 08:10 Rev Time 2.00
Received By jwitmer Date 2001-11-26 Time 08:10 Sent To  
Notes
2001-11-26 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110339
 1617 N FLAGLER DR
 CONT: FORTUNE CONSTRUCTION
 TEL: (305) 460-9900
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)-SBC 104.2.2* ADDITIONAL INFORMATION
 THE PERMIT APPLICATION INDICATES LOTS
 5,6,7 & 8. THE COUNTY TAX MAPS INDICATE
 3 LOTS:
 LOT:4274 43 43 15 18 000 0420
 LOT: 574 43 43 15 00 006 0050
 LOT: 974 43 43 15 00 006 0090
  
 IS THERE A UNITY OF TITLE FOR THESE (3)
 LOTS?
  
 2)- SURVEY: FL S S 61G15-002(1) A PROFES
 SIONAL ENGINEER SHALL AFIX HIS SEAL TO
 ALL PLANS THAT ARE TO BE BUMITTED FOR
 PUBLIC RECORD. SURVEY MISSING SIGNATURE
 SEAL AND DATE.
  
 3)- SBC* 1804.2.7.2.(3) ALL SOILS
 REPORTS SHALL INDICATE THE MINIMUM SAFE
 BEARING VALUE OF THE SOIL.
 MISSING REPORT.
  
 4)- NOTE: FLOOD ZONE A 5= MINIMUM ELEVA-
 TION 7.5'.
  
 5)- SBC104.2.2* ADDITONAL INFORMATION.
 DISCREPANCY? SHEET C-4 INDICATES F.F.@
 8'-0" IS THIS FINISH FLOOR? THE RAMPS
 AND STAIRS INDICATE A FINISH ELEVATION
 OF 9.4'.
  
 6)- FL ACCESS CODE 4.3.8 THE ELEVATED
 RAMP ELE. 9.4' VS OFFICE ENTRY AT 9.5'.
 THE FL ACC. CODE ALLOWS FOR A 1/2"
 CHANGE IN GRADE, OTHERWISE A RAMP ELEVA-
 TOR OR PLATFORM LIFT SHALL BE REQUIRED.
  
 7)- RAISED PLATFORMS SHALL REQUIRE A
 FRAMING PLAN.
  
 8)- INDICATE ON THE EARTHENED HANDICAPP-
 ED RAMP HOW SOILS SHALL BE RETAINED?
 VERTICAL CLEARENCES OF 18" SHALL BE MAIN
 TAINED.SBC 2304.3.4 REQUIRES PRESSURE
 TREATED FLOOR JOIST WHEN CLOSER THAN 18"
 TO THE GROUND.
  
 9)- FL ACCES CODE 4.8.5 HANDRAILS
 IF A RAMP RUN HAS A RISE GREATER THAN 6"
 THEN IT SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 10)- SBC 1007.3.1. INDICATE THE TREAD &
 RISE OF THE STAIRS. 2R+ 1T= 24-25".
  
 11)- LETTER FROM DEPARTMENT OF COMMUNITY
 AFFAIRS THAT THIS IS A APPROVED
 MANUFACTURED BUILDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-08 Cont ID  
Sent By btrobaug Date 2002-03-08 Time 15:24 Rev Time 0.00
Received By btrobaug Date 2002-03-08 Time 15:15 Sent To  
Notes
2002-02-28 00:00:00 
 *******************UNSAT!***************
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT FOR REVIEW.
  
 1) WATTAGE OF FIXTURES.(HIGH VOLTAGE OR
 LOW VOLTAGE?)
  
 2) CONDUIT & WIRE SIZE AND TYPE.
  
 3) SIZE OF OVERCURRENT PROTECTION.
  
 4) NUMBER OF CIRCUITS FEEDING FIXTURES A
 ND CIRCUIT NUMBERS.
  
 5) THE PLANS HAVE A TITLE BLOCK WITH NO
 SEAL. PLEASE COMPLY WITH 481-2.2.1.(FS/F
 AC.)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 21:36 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 21:35 Sent To  
Notes
2001-11-19 00:00:00********** NOTE*****
  
 1)NOTE: PLEASE NOTE THAT TRAILER IS
 EXEMPT FROM ELECTRICAL PLAN REVIEW.
 NOTHING WAS SUBMITTED FOR TRAILER HOOK-
 -UP. NO RISER DIAGRAM SUBMITTED.
  
 PLEASE SUBMIT FOR REVIEW, OR SEPARATE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-11-21 Cont ID  
Sent By mamini Date 2001-11-21 Time 16:24 Rev Time 1.00
Received By mamini Date 2001-11-21 Time 16:23 Sent To  
Notes
2001-11-21 00:00:00PASSED WITH PROVISOS:
 1. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT FROM CITY ENGINEER'S
 OFFICE , 659-8040.
 2. BACKFLOW PREVENTERS AND ALL THE
 CONNECTIONS TO CITY SERVICES MUST BE
 APPROVED BY PUBLIC UTILITIES DEPT.
 659-8040.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 21:50 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 21:49 Sent To  
Notes
2001-11-21 00:00:00PASSED/PROVISO
  
 PLUMBING CONTRACTOR TO SUPPLY A VALVE
 AND ADAPTOR FOR IRRIGATION CONTRACTOR
 TO TIE INTO. IRRIGATION BACKFLOW REQUIR-
 ED (N36 WATTS). SEPARATE IRRIGATION
 PERMIT REQUIRED.
 2 WAY CLEANOUT REQUIRED NEAR JUNCTION OF
 DRAIN AND SEWER.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 07:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***