Plan Review Details - Permit 01110284
Plan Review Stops For Permit 01110284
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-27 Cont ID  
Sent By mcarsill Date 2001-11-27 Time 10:11 Rev Time 0.00
Received By mcarsill Date 2001-11-27 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mcarsill Date 2001-11-13 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2001-11-13 Time 16:11 Sent To  
Notes
2001-11-13 00:00:001) NO CUT SHEETS PROVIDED FOR FIRE
 ALARM EQUIPMENT PLANNED FOR USE. PLEASE
 PROVIDE.
 2) CAN IT BE ASSUMED THAT THE DIAMONDS
 THAT CONTAIN AN F AND T NEAR OFFICE
 112 ARE FLOW AND TAMPER SWITCHES.
 3) ARE THE BACKFLOW DEVICES SUPERVISED
 WITH TAMPER SWITCHES.
 4) LINE DRAWING INDICATES A HORN AND
 PULL STATION IN MEETING 104. WHERE IS
 ROOM 104 LOCATED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910