Plan Review Details - Permit 01110271
Plan Review Stops For Permit 01110271
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-26 Cont ID  
Sent By mcarsill Date 2001-12-26 Time 10:22 Rev Time 0.00
Received By mcarsill Date 2001-12-26 Time 10:22 Sent To  
Notes
2001-12-26 00:00:00ON 12.24.01 WRITER CONTACTED BRIAN
 BURCHARD BY TELEPHONE TO DISCUSS FIRE
 ALARM SYSTEM ISSUES. HE WAS ADVISED THAT
 AN ALERT TONE OF 3-10 SECONDS FOLLOWED
 BY A MESSAGE REPEATED AT LEAST THREE
 TIMES TO INFORM THE OCCUPANTS MUST BE
 PROVIDED. HE WAS FURTHER ADVISED THAT
 NO INFORMATION WAS PROVIDED WITH
 REGARDS TO WHAT THE VOICE EVACUATION
 MESSAGE WILL SAY. ALSO HE WAS ADVISED
 THAT THE LOCATION OF THE REMOTE FIRE
 ALARM PANEL APPEARS TO HAVE BEEN
 RELOCATED. HE WAS ADVISED THAT THE
 REMOTE FIRE ALARM PANEL AND THE
 MAIN FIRE CONTROL PANEL ARE TO BE
 INSTALLED IN AREAS WITH AT LEAST A
 ONE HOUR FIRE RESISTANCE RATING AND HAVE
 AT LEAST THREE FEET OF CLEARANCE. WIRING
 FOR THE TWO MUST BE NO FARTHER APART
 THAN 100 FEET OR BE ENCLOSED IN A TWO
 HOUR RATED ENCLOSURE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By mcarsill Date 2001-11-13 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2001-11-13 Time 13:14 Sent To  
Notes
2001-11-13 00:00:001) NO CUT SHEETS PROVIDED FOR NEW FIRE
 ALARM SYSTEM.
 2) THE FIRE ALARM SYSTEM SHOULD BE
 VOICE EVACUATION. PLEASE INDICATE WHAT
 THE TAPED MESSAGE PORTION OF THE FIRE
 ALARM SYSTEM WILL SAY.
 3) PLEASE INDICATE ON PLANS THAT THE
 VALVES ON THE BACKFLOW DEVICE WILL
 BE SUPERVISED.
 4) FIRE ALARM SYSTEM TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910