Plan Review Details - Permit 01110260
Plan Review Stops For Permit 01110260
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-23 Cont ID  
Sent By jwitmer Date 2001-11-23 Time 11:09 Rev Time 1.00
Received By jwitmer Date 2001-11-23 Time 11:09 Sent To  
Notes
2001-11-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01110260
 1901 PALM BEACH LAKES BLVD.
 PLAN REVIEW
 SUNBURST HOSPITALITY CORP
 TEL: (305) 684-0032
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
 1997
 1)- PLANS DO NOT COMPLY WITH SEC.9.1.2-
 9.5 OF THE FL. ACCESSIBILITY CODE 1997.
 SHOW COMPLIANCE FOR THE COMPLETE SUITE
 WITH AN ACCESSIBLE ROUTE AROUND ALL
 FURNATURE.
 SEE SECTION 9.1.5 FOR VISUAL ALARMS,
 NOTIFICATION DEVICES AND TELEPHONES FOR
 COMPLIANCE WITH 9.1.3.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By dpalmer Date 2001-11-16 Time 15:35 Rev Time 0.00
Received By dpalmer Date 2001-11-16 Time 15:35 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 16:14 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By mcarsill Date 2001-11-19 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2001-11-19 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 15:48 Rev Time 0.35
Received By pkrauss Date 2001-11-27 Time 15:46 Sent To  
Notes
2001-11-27 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 18:22 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 18:22 Sent To  
Notes
2001-11-16 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A2, ELEVATION #1. HEIGHT OF W/C
 TO BE 17" TO 19" PER FACBC SEC 4.16.3
 NOT 1'3" AS SHOWN.
  
 2) PAGE A2, ELEVATION #1. CONTROLS FOR
 FLUSH VALVE ON W/C TO BE ON WIDE SIDE AS
 PER FACBC SEC 4.16.5 NOT AS SHOWN ON
 WALL SIDE.
  
 3) PAGE A2, ELEVATIONS #1 & #4. LAVS TO
 COMPLY WITH FACBC SEC 4.19.4. HOT WATER
 AND DRAIN PIPES UNDER LAVS SHALL BE IN-
 SULATED ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 16:14 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***