| Plan Review Stops For Permit 01110217 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-07 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-07 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | 1) AFTER INSTALLATION, SYSTEM IS TO | | | BE TESTED WITH FIRE RESCUE PERSONNEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-13 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-13 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | 1) PLANS DO NOT INDICATE THAT THIS | | | ARRANGEMENT WILL MEET THE "SPECIAL | | | LOCKING ARRANGEMENT" CRITERIA LISTED | | | IN THE LIFE SAFETY CODE. PLEASE SEE | | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDITION, SECTION 5-2.1.6.1. ALL OF | | | THESE REQUIREMENTS ARE TO BE MET BEFORE | | | APPROVAL CAN BE GIVEN. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|